Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ALLEGHENY WOOD WORKS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ALLEGHENY WOOD WORKS, INC. in 10003 RAILROAD ST, LAKE CITY, PA 16423 (NAICS 321911). OSHA activity number 346337942.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Allegheny Wood Works, INC. — free Get an email when a new federal OSHA severe-injury report for Allegheny Wood Works, INC. is published. One employer, no account, unsubscribe in one click.
Site address
10003 RAILROAD ST
City
LAKE CITY
State
PA
ZIP
16423
Mailing
10003 RAILROAD ST, LAKE CITY, PA 16423
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321911
Employees
23
Ownership type
A

4 citations on file for this inspection.

1910.303 G01 II

Serious Gravity 1 1 instance 2 exposed
Issued
May 8, 2023
Abate by
Jun 2, 2023
Penalty
Initial $2,277 · Current $800 Reduced
29 CFR  1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a.)  Allegheny Wood Works, Inc.; East Wall; Zone A - On or about 11/10/22 and at times prior thereto, the area in front of an electrical panel box was used for storage.  The items stored in front of the panel box included, but was not limited to, pieces of wood and a 55 gallon cardboard drum.  ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $800
  • — Z (S) $2277

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
May 8, 2023
Abate by
Jun 2, 2023
Penalty
Initial $0 · Current $0
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a.)  Allegheny Wood Works, Inc.; East Wall; Zone A - On or about 11/10/22 and at times prior thereto, household fans were being utilized .  The fans were not listed and labeled for an industrial work environment.  ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 2 instances 2 exposed
Issued
May 8, 2023
Abate by
Jun 2, 2023
Penalty
Initial $3,036 · Current $2,000 Reduced
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):     a.) Allegheny Wood Works, Inc.; East Wall; Zone A -  On or about 11/10/22, and at times prior thereto, the electrical panel box was missing a blank in the unused hole of the panel box.  ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $3036

1910.22 A01

Other-than-serious 1 instance 2 exposed
Issued
May 8, 2023
Abate by
Jun 2, 2023
Penalty
Initial $0 · Current $0
29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition.   a.)  Allegheny Wood Works, Inc.- On or about 11/10/22 and at times prior thereto, a housekeeping program was not established to address the frequency of cleaning the wood dust.  Dust accumulations were noted on the floor, lights, duct work and ceiling beams.   ABATEMENT CERTIFICATION REQUIRED: Abatement certification is required within 10 days after the abatement date noted on the citation (see below).  This certification shall include a statement that abatement is complete, the date abatement was completed, method of abatement, and state that employees and their representatives were informed of this abatement.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Allegheny Wood Works, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346337942.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.