ONTARIO, CA —
OSHA Inspection: CALIFORNIA ARMY NATIONAL GUARD - FMS #1
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CALIFORNIA ARMY NATIONAL GUARD - FMS #1 in 950 N. CUCAMUNGA AVE., ONTARIO, CA 91764 (NAICS 811111). OSHA activity number 346394976.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CALIFORNIA ARMY NATIONAL GUARD - FMS #1
- Site address
- 950 N. CUCAMUNGA AVE.
- City
- ONTARIO
- State
- CA
- ZIP
- 91764
- Mailing
- 950 N. CUCAMUNGA AVE., ONTARIO, CA 91764
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811111
- Employees
- 12
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.305 G01 IV A
- Issued
- Jan 13, 2023
- Abate by
- Feb 9, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure In the Managers office: On and or/before December 15, 2022, the employer permitted the use of a flexible extension cord as a source of permanent power for laptops. Employee(s) were potentially exposed to electrical shock and/or fire hazards.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Jan 13, 2023
- Abate by
- Feb 9, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling On and/or before December 20, 2022 multiple appliances such as microwaves, coffee makers and space heaters were plugged into relocatable power taps and/or "daisy chained" in which were not used according to listing and labeling instructions. This condition potentially exposed employee(s) to electrical shock and/or fire hazards. In the following locations: a) 1st floor production control office b) 2nd floor supervisor's office c) 2nd floor Break room The California Army National Guard was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 1544767, citation number 1, item number 1 and was affirmed as a final order on October 12, 2021, with respect to a workplace located at 11302 Independence Road Bldg. 279, Los Alamitos, CA. 90720.
Recent events (1)
- — Z (R) $0
1910.157 E02
- Issued
- Jan 13, 2023
- Abate by
- Feb 2, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly On and/or before December 15, 2022, fire extinguisher(s) that were mounted for emergency use by employee(s) were not inspected monthly and/or maintained according to N.F.P.A No. 10 A-1970. This condition potentially exposed employee(s) to fire hazard(s). In the following locations: a) 2nd floor hallway b) Bay 3, adjacent to garage door
Recent events (1)
- — Z (O) $0
1910.303 G01 II
- Issued
- Jan 13, 2023
- Abate by
- Feb 9, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage Maintenance Main Office: On and/or before December 15,2022 the employer did not ensure at least 3 feet in front of the electrical panel and switch box was clear. The circuit breaker panel had a cabinet, box, and Christmas reef obstructing the panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).
Recent events (1)
- — Z (O) $0
More inspections at California Army National Guard - FMS #1
View California Army National Guard - FMS #1's full OSHA safety record →
More inspections in this industry (NAICS 811111)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346394976.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.