JOHNSTON, RI —
OSHA Inspection: J. ARAKELIAN INC./UNIQUE PLATING COMPANY
Complaint inspection · Health discipline
At a glance
On , OSHA opened a complaint health inspection of J. ARAKELIAN INC./UNIQUE PLATING COMPANY in 66 MILL ST., JOHNSTON, RI 02919 (NAICS 339993). OSHA activity number 346495740.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- J. ARAKELIAN INC./UNIQUE PLATING COMPANY
- Site address
- 66 MILL ST.
- City
- JOHNSTON
- State
- RI
- ZIP
- 02919
- Mailing
- 66 MILL ST., JOHNSTON, RI 02919
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 339993
- Employees
- 10
- Ownership type
- A
Citations
14 citations on file for this inspection.
1910.36 D01
- Issued
- Jul 17, 2023
- Abate by
- Aug 9, 2023
- Penalty
- Initial $4,688 · Current $0 Reduced
General-duty citation text
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: (a) Stringing Department: On or about February 9, 2023 an exit door in the northeast corner of the building that was marked as an exit was locked with a locking knob lock and a deadbolt style lock that were maintained locked so that the door could not be readily opened. (b) Plating Department: On or about February 9, 2023 an exit door on the west side of the building, adjacent to the acid copper bath, was corroded shut so that it could not be opened. (c) Vibrating Department: On or about February 9, 2023 an exit door on the west side of the building, adjacent to several large vibrators, was corroded shut so that it could not be opened.
Recent events (3)
- — F (S) $0
- — C (S) $4688
- — Z (S) $4688
1910.132 D01
- Issued
- Jul 17, 2023
- Abate by
- Aug 3, 2023
- Penalty
- Initial $4,688 · Current $0 Reduced
General-duty citation text
29 CFR 1910.132(d)(1):The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE): (a) Facility-wide: On or about February 9, 2023 the employer had not assessed the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE) in that employees using corrosive and irritating chemicals including acetone and Enprep 222SE to clean parts were not required to use adequate chemically resistant gloves and adequate eye and face protection.
Recent events (3)
- — F (S) $0
- — C (S) $4688
- — Z (S) $4688
1910.133 A01
- Issued
- Jul 17, 2023
- Abate by
- Aug 3, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.133(a)(1): Protective eye equipment was not required where there was a reasonable probability of injury that could be prevented by such equipment: (a) Plating Area: On or about February 9, 2023 the employer did not require that employees working with corrosive chemicals, including Enprep 222SE, when cleaning parts utilize face shields and proper eye protection to protect their eyes.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.151 A
- Issued
- Jul 17, 2023
- Abate by
- Jan 5, 2024
- Penalty
- Initial $4,688 · Current $0 Reduced
General-duty citation text
29 CFR 1910.151(a): Medical personnel were not readily available for advice and consultation on matters of plant health: (a) Plating Area: On or about February 9, 2023 the employer did not ensure that emergency medical services, including those equipped with effective cyanide antidotes, were readily available in the event of an acute cyanide overexposure in the workplace. The employer uses several cyanide based plating solutions including copper cyanide and sodium cyanide.
Recent events (3)
- — F (S) $0
- — C (S) $4688
- — Z (S) $4688
1910.219 C03
- Issued
- Jul 17, 2023
- Abate by
- Jan 5, 2024
- Penalty
- Initial $3,349 · Current $0 Reduced
General-duty citation text
29 CFR 1910.219(c)(3): Vertical or inclined shafting seven feet or less from floor or working platform was not enclosed with stationary casing(s): (a) Wastewater Pretreatment Slurry Tank adjacent to Tumbling Area: On or about February 9, 2023, the inclined shafting on the spindle mixer used in the batching tank was not protected by stationary casing(s) enclosing shafting completely or by trough(s) enclosing sides and top or sides and bottom of shafting, exposing employees to the spinning shaft when adding materials to the tank.
Recent events (3)
- — F (S) $0
- — C (S) $3349
- — Z (S) $3349
1910.219 F03
- Issued
- Jul 17, 2023
- Abate by
- Aug 3, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(f)(3): Sprocket wheels and chains which were seven (7) feet or less above floors or platforms were not enclosed: (a) Tumbling Area adjacent to Boiler and Vibrating Area: On or about February 9, 2023, the employer did not maintain proper guarding on the large horizontal tumbling machine where employees were exposed to nip points and rotating parts when the chain and rotating sprocket was left unguarded.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.303 G01 II
- Issued
- Jul 17, 2023
- Abate by
- Aug 3, 2023
- Penalty
- Initial $3,349 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) Office Area, Main Electrical Service: On or about February 9, 2023, the employer allowed the build-up of storage, such as but not limited to push-cart with cardboard boxes and a cardboard container within 3 feet of the main electrical service . b) Plating Area: On or about February 9, 2023, the employer allowed the build-up of storage, such as but not limited to 5 gallon plastic buckets and plastic bins within 3 feet of an electrical panel in the Plating Area.
Recent events (3)
- — F (S) $0
- — C (S) $3349
- — Z (S) $3349
1910.305 B01 II
- Issued
- Jul 17, 2023
- Abate by
- Aug 9, 2023
- Penalty
- Initial $4,688 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Anti-Tarnish Area: On or about February 9, 2023, the employer did not effectively close all openings inside the circuit junction box that energizes the tumbler machine, exposing employees to electrical hazards.
Recent events (3)
- — F (S) $0
- — C (S) $4688
- — Z (S) $4688
1910.305 B02 I
- Issued
- Jul 17, 2023
- Abate by
- Aug 3, 2023
- Penalty
- Initial $4,688 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) Anti-Tarnish Area Tumbler: On or about February 9, 2023, the employer did not provide a proper enclosure for an electrical contactor box in the Anti-Tarnish Vibrator while engaging the Start/Stop buttons, exposing employees to electrical shock and burn hazards.
Recent events (3)
- — F (S) $0
- — C (S) $4688
- — Z (S) $4688
1910.305 J02 IV
- Issued
- Jul 17, 2023
- Abate by
- Aug 9, 2023
- Penalty
- Initial $4,688 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location: a) Eye Wash Station adjacent to the parts cleaning operation: The employer did not ensure that a receptacle was GFCI protected. This outlet is used to power corded Sawzalls on a regular basis, exposing employees to electrical shock hazards. b) Tumbler Area: The employer did not ensure that a receptacle was GFCI protected . This outlet is used to power cord and plug appliances, such as tumblers, on a regular basis and to supply power to extension cords used to operate pumps, exposing employees to electrical shock hazards.
Recent events (3)
- — F (S) $0
- — C (S) $4688
- — Z (S) $4688
1910.1200 E01
- Issued
- Jul 17, 2023
- Abate by
- Jan 5, 2024
- Penalty
- Initial $3,349 · Current $0 Reduced
General-duty citation text
29 CFR 1910.1200(e)(1):Employer had not developed or implemented a written hazard communication program, including the requirements outlined in 29 CFR 1910.1200(e)(1)(i) and (e)(1)(ii): (a) Workplace: On or about February 9, 2023, the employer had not developed a written chemical hazard communication program, including the requirements outlined in 29 CFR 1910.1200(e)(1)(i) and (e)(1)(ii).
Recent events (3)
- — F (S) $0
- — C (S) $3349
- — Z (S) $3349
1910.1200 H01
- Issued
- Jul 17, 2023
- Abate by
- Jan 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: (a)Workplace: On or about February 9, 2023, the employer had not trained new employees in the hazards of chemicals in their work place at the time of hire and job assignment.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.134 D01 III
- Issued
- Jul 17, 2023
- Abate by
- Oct 31, 2024
- Penalty
- Initial $376 · Current $0 Reduced
General-duty citation text
29 CFR 1910.134(d)(1)(iii): The employer did not identify and evaluate the respiratory hazard(s) in the workplace; including a reasonable estimate of employee exposures to respiratory hazards and identification of the contaminant's chemical state and physical form: (a) Plating Area: The employer did not identify and evaluate the respiratory hazard(s) in the workplace, such as nitric and sulfuric acid; including a reasonable estimate of employee exposures to respiratory hazards and identification of the contaminant's chemical state and physical form before discontinuing the maintenance of the area's ventilation systems.
Recent events (4)
- — P (O) $0
- — F (O) $0
- — C (O) $376
1910.305 G01 IV A
- Issued
- Jul 17, 2023
- Abate by
- Jan 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Stringing Department: On or about February 9, 2023, the employer was utilizing multiple extensions cords to operate electrical devices in lieu of permanent wiring, such as but not limited to a refrigerator, a microwave oven, and a toaster oven, exposing employees to electrical hazards. b) Wastewater Treatment Area: On or about February 9, 2023, the employer was utilizing multiple extensions cords to operate electrical devices in lieu of permanent wiring exposing employees to electrical hazards. c) Office Area: On or about February 9, 2023, the employer was utilizing multiple extensions cords to operate electrical devices in lieu of permanent wiring exposing employees to electrical hazards.
Recent events (3)
- — F (O) $0
- — C (O) $0
- — Z (O) $0
More inspections at J. Arakelian Inc./Unique Plating Company
View J. Arakelian Inc./Unique Plating Company's full OSHA safety record →
More inspections in this industry (NAICS 339993)
More inspections in RI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346495740.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.