ROCHESTER, NY —
OSHA Inspection: ADVANTAGE METALWORK & FINISHING, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ADVANTAGE METALWORK & FINISHING, LLC in 1000 UNIVERSITY AVE SUITE 700, ROCHESTER, NY 14607 (NAICS 332322). OSHA activity number 346705403.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ADVANTAGE METALWORK & FINISHING, LLC
- Site address
- 1000 UNIVERSITY AVE SUITE 700
- City
- ROCHESTER
- State
- NY
- ZIP
- 14607
- Mailing
- 1000 UNIVERSITY AVE SUITE 700, ROCHESTER, NY 14607
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332322
- Employees
- 95
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.107 B05 I
- Issued
- Jul 17, 2023
- Abate by
- Aug 8, 2023
- Penalty
- Initial $6,250 · Current $4,688 Reduced
General-duty citation text
29 CFR 1910.107(b)(5)(i): The average air speed over the open face of the paint spray booth was less than 100 linear feet per minute: a) On or about 05/23/2023 in the paint area; where the air flow across the face of two spray booths was 50 linear feet per minute or less. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $4687.5
- — Z (S) $6250
1910.107 B05 I
- Issued
- Jul 17, 2023
- Abate by
- Aug 8, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(b)(5)(i): There were no visible gauges, audible alarms or pressure activated devices installed in paint spray booths to indicate or ensure that the required air speed was maintained. a) On or about 05/23/2023 in the paint area; where the air flow across the face of two spray booth was less than 100 linear feet per minute, there was no gauge, alarm, or device to measure the air speed. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Jul 17, 2023
- Abate by
- Aug 8, 2023
- Penalty
- Initial $4,687 · Current $3,515 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) On or about 05/16/2023 in the press brake area; where two temporary power taps (power strips) were daisy-chained together and were used to supply power a pedestal fan (a motor operated device). ABATEMMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $3515.25
- — Z (S) $4687
1910.305 G01 IV A
- Issued
- Jul 17, 2023
- Abate by
- Aug 8, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) On or about 05/16/2023 in the press brake area; where an extension cord was used in place of fixed wiring to supply power to two temporary power taps which were used to energized equipment including a pedestal fan. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.304 G05
- Issued
- Jul 17, 2023
- Abate by
- Aug 8, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5):The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: a) On or about 05/23/2023 in the press brake area; where the plug for a pedestal fan was missing the ground pin. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B07 I
- Issued
- Jul 17, 2023
- Abate by
- Aug 8, 2023
- Penalty
- Initial $6,250 · Current $4,688 Reduced
General-duty citation text
29 CFR 1910.303(b)(7)(i):Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: a) On or about 05/23/2023 in the grinding department; where there were unused openings in lighting panel LP28, potentially exposing employees to live electrical circuits. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $4687.5
- — Z (S) $6250
1910.151 C
- Issued
- Jul 17, 2023
- Abate by
- Aug 2, 2023
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.151(c):Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: a) On or about 05/23/2023 at the wash line; where employees were exposed to corrosives such as Gardobond A (pH 4.2-4.8). The portable eye wash stations had not been inspected since April of 2022. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Advantage Metalwork & Finishing, LLC
View Advantage Metalwork & Finishing, LLC's full OSHA safety record →
More inspections in this industry (NAICS 332322)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 346705403.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.