CLERMONT, FL —
OSHA Inspection: DUKE ENERGY FLORIDA, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of DUKE ENERGY FLORIDA, LLC in 13303 SULLIVAN ROAD CAMP LAKE SUBSTATION, CLERMONT, FL 34715 (NAICS 221122). OSHA activity number 347013203.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DUKE ENERGY FLORIDA, LLC
- Site address
- 13303 SULLIVAN ROAD CAMP LAKE SUBSTATION
- City
- CLERMONT
- State
- FL
- ZIP
- 34715
- Mailing
- 525 S TRYON ST, CHARLOTTE, NC 28202
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 27600
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.269 M02 IV A
- Issued
- Dec 1, 2023
- Abate by
- Dec 28, 2023
- Penalty
- Initial $10,547 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(m)(2)(iv)(A): When two or more crews were working on the same lines or equipment, the crews did not coordinate their activities under paragraph (m) by designating a single employee in charge of the clearance for all of the crews and follow the requirements of paragraph (m) of this section as if all of the employees formed a single crew: a. On or about 9/19/2023, at the Camp Lake Substation, 13303 Sullivan Road, Clermont, Florida, 34715, employees were exposed to electric shock and electrocution hazards in that, while replacing electrical insulators on overhead powerlines, the employer did not designate a single employee to be in charge of the clearance while two crews formed a single crew.
Recent events (2)
- — I (S) $0
- — Z (S) $10547
1910.269 N02
- Issued
- Dec 1, 2023
- Abate by
- Dec 28, 2023
- Penalty
- Initial $0 · Current $10,547
General-duty citation text
29 CFR 1910.269(n)(2): For any employee to work transmission and distribution lines or equipment as deenergized, the employer did not ensure that the lines or equipment were deenergized under the provisions of paragraph (m) of this section and did not ensure proper grounding of the lines or equipment as specified in paragraphs (n)(3) through (n)(8) of this section: On or about 9/19/2023, at the Camp Lake Substation, 13303 Sullivan Road, Clermont, Florida, 34715, while replacing electrical insulators, Transmission Construction and Maintenance employees were exposed to electric shock and electrocution hazards because proper grounding of overhead powerlines was not conducted at the site. Duke Energy work methods are in place that require grounding to be completed before starting work and requires employees to maintain minimum approach distance until energized equipment is properly deenergized, tested, and grounded, while wearing all required personal protective equipment.
Recent events (2)
- — I (S) $10547
- — Z (S) $0
More inspections at Duke Energy Florida, LLC
View Duke Energy Florida, LLC's full OSHA safety record →
More inspections in this industry (NAICS 221122)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347013203.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.