Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DUKE ENERGY FLORIDA, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of DUKE ENERGY FLORIDA, LLC in 13303 SULLIVAN ROAD CAMP LAKE SUBSTATION, CLERMONT, FL 34715 (NAICS 221122). OSHA activity number 347013203.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Duke Energy Florida, LLC — free Get an email when a new federal OSHA severe-injury report for Duke Energy Florida, LLC is published. One employer, no account, unsubscribe in one click.
Site address
13303 SULLIVAN ROAD CAMP LAKE SUBSTATION
City
CLERMONT
State
FL
ZIP
34715
Mailing
525 S TRYON ST, CHARLOTTE, NC 28202
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
27600
Ownership type
A

2 citations on file for this inspection.

1910.269 M02 IV A

Deleted Serious Gravity 10 1 instance 4 exposed
Issued
Dec 1, 2023
Abate by
Dec 28, 2023
Penalty
Initial $10,547 · Current $0 Reduced
29 CFR 1910.269(m)(2)(iv)(A): When two or more crews were working on the same lines or equipment, the crews did not coordinate their activities under paragraph (m) by designating a single employee in charge of the clearance for all of the crews and follow the requirements of paragraph (m) of this section as if all of the employees formed a single crew:  a.	On or about 9/19/2023, at the Camp Lake Substation, 13303 Sullivan Road, Clermont, Florida, 34715, employees were exposed to electric shock and electrocution hazards in that, while replacing electrical insulators on overhead powerlines, the employer did not designate a single employee to be in charge of the clearance while two crews formed a single crew.
Recent events (2)
  • — I (S) $0
  • — Z (S) $10547

1910.269 N02

Serious Gravity 10 1 instance 4 exposed
Issued
Dec 1, 2023
Abate by
Dec 28, 2023
Penalty
Initial $0 · Current $10,547
29 CFR 1910.269(n)(2): For any employee to work transmission and distribution lines or equipment as deenergized, the employer did not ensure that the lines or equipment were deenergized under the provisions of paragraph (m) of this section and did not ensure proper grounding of the lines or equipment as specified in paragraphs (n)(3) through (n)(8) of this section:   On or about 9/19/2023, at the Camp Lake Substation, 13303 Sullivan Road, Clermont, Florida, 34715, while replacing electrical insulators, Transmission Construction and Maintenance employees were exposed to electric shock and electrocution hazards because proper grounding of overhead powerlines was not conducted at the site. Duke Energy work methods are in place that require grounding to be completed before starting work and requires employees to maintain minimum approach distance until energized equipment is properly deenergized, tested, and grounded, while wearing all required personal protective equipment.
Recent events (2)
  • — I (S) $10547
  • — Z (S) $0

View Duke Energy Florida, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347013203.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.