Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: VIEJAS CASINO & RESORT

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of VIEJAS CASINO & RESORT in 5003 WILLOWS ROAD EXTERIOR OF G102B, ALPINE, CA 91901 (NAICS 721120). OSHA activity number 347054793.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Viejas Casino & Resort — free Get an email when a new federal OSHA severe-injury report for Viejas Casino & Resort is published. One employer, no account, unsubscribe in one click.
Site address
5003 WILLOWS ROAD EXTERIOR OF G102B
City
ALPINE
State
CA
ZIP
91901
Mailing
5000 WILLOWS ROAD, ALPINE, CA 91901
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721120
Employees
500
Ownership type
A

5 citations on file for this inspection.

1910.110 B06 II

Deleted Serious Gravity 10 2 instances 10 exposed
Issued
Jan 11, 2024
Abate by
Jan 31, 2024
Penalty
Initial $15,625 · Current $0 Reduced
29 CFR 1910.110(b)(6)(ii): Each individual container was not located the minimum specified distance from an important building or group of buildings in accordance to Table H-23: 25 ft for aboveground tanks with 500 - 2,000 gallons capacity.  On and/or before October 23, 2023, the employer did not ensure that the propane tanks used for their laundry equipment was properly distanced from the facility itself. Employees were potentially exposed to fire and/or explosion hazard(s) in the following locations: a) Patio Area Tank b) Vaporizer Tank
Recent events (2)
  • — I (S) $0
  • — Z (S) $15625

1910.110 B05 II

Serious Gravity 5 1 instance 10 exposed
Issued
Jan 11, 2024
Abate by
Jan 29, 2024
Penalty
Initial $0 · Current $10,938
29 CFR  1910.110(b)(5)(ii): Markings specified shall be on a metal nameplate attached to the container and located in such a manner as to remain visible after the container is installed.  Exterior of Bldg. 5003 (Laundry Facility), Patio Propane Tank: On and/or before October 23, 2023, the employer did not ensure that the patio propane tank used for their laundry equipment had a legible metal nameplate to properly identify the tanks water capacity of the container in pounds or gallons and pressure in p.s.i.g., for which the container is designed. This condition potentially exposed employees to fire and/or explosion hazard(s).
Recent events (2)
  • — I (S) $10938
  • — Z (S) $0

1910.110 B16

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 11, 2024
Abate by
Jan 31, 2024
Penalty
Initial $15,625 · Current $15,625
29 CFR  1910.110(b)(16): Personnel performing removal, operation, and/or maintenance on LPG equipment were not properly trained in such functions.  Exterior of Bldg. 5003 (Laundry Facility), LP-Gas Vaporizer: On and/or before October 23, 2023, the employer did not ensure that the plumbing employees were properly trained to service equipment that handled liquified petroleum gas. This condition potentially exposed employees to fire and/or explosion hazards.
Recent events (2)
  • — I (S) $15625
  • — Z (S) $15625

1910.132 D02

Serious Gravity 10 1 instance 2 exposed
Issued
Jan 11, 2024
Abate by
Jan 31, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.132(d)(2): The employer did not verify that the required workplace hazard assessment had been performed through a written certification that identified the workplace evaluated;  the person certifying that the evaluation has been performed;  the date(s) of the hazard assessment;  and which identifies the document as a certification of hazard assessment:  Exterior of Bldg. 5003 (Laundry Facility), LP-Gas Vaporizer: On and/or before October 23, 2023, the employer did not ensure that a hazard assessment was completed for the preventative maintenance of the LP-Gas Vaporizer. Employees were potentially exposed to fire and/or explosion hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.110 B06 VI

Other-than-serious Gravity 10 2 instances 10 exposed
Issued
Jan 11, 2024
Abate by
Jan 29, 2024
Penalty
Initial $15,625 · Current $10,938 Reduced
29 CFR  1910.110(b)(6)(vi): Readily ignitable material such as weeds and long dry grass was not removed within 10 feet of any container.  On and/or before October 23, 2023, the employer did not ensure that the propane tanks used for their laundry equipment were free in it's surrounding of ignitable material such as weeds and/or dry grass. Employees were potentially exposed to fire and/or explosion hazard(s) in the following locations: a) Patio Area Tank b) Vaporizer Tank
Recent events (2)
  • — I (O) $10938
  • — Z (S) $15625

View Viejas Casino & Resort's full OSHA safety record →