OSHA Inspection: ASSOCIATED ELECTRIC COOPERATIVE INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ASSOCIATED ELECTRIC COOPERATIVE INC. in 41 ST. JUDE INDUSTRIAL PARK, MARSTON, MO 63866 (NAICS 221122). OSHA activity number 347423899.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Associated Electric Cooperative INC. — free Get an email when a new federal OSHA severe-injury report for Associated Electric Cooperative INC. is published. One employer, no account, unsubscribe in one click.
Site address
41 ST. JUDE INDUSTRIAL PARK
City
MARSTON
State
MO
ZIP
63866
Mailing
P.O. BOX 156, NEW MADRID, MO 63869
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
145
Ownership type
A

2 citations on file for this inspection.

1910.269 D02 VIII A

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Aug 9, 2024
Penalty
Initial $7,052 · Current $0 Reduced
29 CFR 1910.269(d)(2)(viii)(A): Retraining was not provided for all authorized and affected employees whenever there is a change in their job assignments, a change in machines, equipment, or processes that present a new hazard or whenever there is a change in the energy control procedures:  On or about March 14, 2024, employees of Associated Electric Cooperation Inc. were testing in the neutral cabinet on Generator Unit 2 located at 41 St. Jude Industrial Park in Marston, Missouri.  The employer had recently installed new monitoring equipment onto Generator 2 and did not train employees on the changes. The employer did not update the lockout/tagout procedures for the addition of the new monitoring equipment. An employee unaware of the power signal from the monitoring equipment was shocked when removing a lead on the current transformer.
Recent events (2)
  • — I (S) $0
  • — Z (S) $7052

1910.269 D06 III

Other-than-serious Gravity 5 1 instance 2 exposed
Issued
Aug 9, 2024
Penalty
Initial $10,372 · Current $10,372
29 CFR 1910.269(d)(6)(iii): All energy isolating devices that are needed to control the energy to the machine or equipment shall be physically located and operated in such a manner as to isolate the machine or equipment from energy sources:  On or about March 14, 2024, employees of Associated Electric Cooperation Inc. were testing in the neutral cabinet on Generator Unit 2 located at 41 St. Jude Industrial Park in Marston, Missouri. The employer did not locate and isolate a 120V breaker providing power to a monitoring system recently added onto Generator Unit 2. The uncontrolled energy source unexpectedly shocked an employee when removing the ground lead on the current transformer.