MARCH AIR RESERVE BASE, CA —
OSHA Inspection: MARCH ARB MAIN EXCHANGE
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of MARCH ARB MAIN EXCHANGE in 23640 N. STREET, MARCH AIR RESERVE BASE, CA 92518 (NAICS 445110). OSHA activity number 347504227.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MARCH ARB MAIN EXCHANGE
- Site address
- 23640 N. STREET
- City
- MARCH AIR RESERVE BASE
- State
- CA
- ZIP
- 92518
- Mailing
- 23640 N. STREET, MARCH AIR RESERVE BASE, CA 92518
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445110
- Employees
- 35
- Ownership type
- D
Citations
6 citations on file for this inspection.
1910.212 A05
- Issued
- Jun 24, 2024
- Abate by
- Jul 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(5): Fan blade guards, where the periphery of the blades was less than seven feet above the floor or working level, had openings larger than one half inch. Warehouse, Soft Line Area: On and/or before May 24, 2024, employee(s) engaged in unboxing clothing item(s) from deliveries throughout the day that was within close proximity to an unguarded portable fan. The employer did not ensure the Portable Vornado Compact Air Circulator Fan was guarded. This condition potentially exposed employee(s) to unguarded moving blade parts and/or amputation hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 B02
- Issued
- Jun 24, 2024
- Abate by
- Jul 9, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. On and/or before May 24, 2024, multiple appliance such as the Haier Mini Fridge, Goldstar Microwave Oven and a Brentwood Toaster were plugged into a relocatable power tap in which were not used according to listing and labeling instructions. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s). In the following location(s): a) Warehouse Office - Haier Mini Fridge b) Employee Breakroom - Goldstar Microwave c) Employee Breakroom - Brentwood Toaster
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jun 24, 2024
- Abate by
- Jul 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. Warehouse, Shoe Stock Room: On and/or before May 24, 2024, flexible cords and/or cables were used as a source of permanent power for the portable white box fan. This condition potentially exposed employees to electrical shock and/or fire hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.334 B01
- Issued
- Jun 24, 2024
- Abate by
- Jul 5, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(b)(1): Load rated switches, circuit breakers or other devices specifically designed as disconnecting means were not used for the opening, reversing or closing of electric power and lighting circuits under load conditions. Cleaning Closet: On and/or before May 24, 2024, employee(s) accessed cleaning supplies inside the cleaning closet. The employer allowed employees to open and close circuit breakers daily when they were not designed for this purpose. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1960.8 A
- Issued
- Jun 24, 2024
- Abate by
- Sep 6, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1960.8(a): The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm to employees from hazards associated with posting maximum safe load limits on pallet racks. Warehouse: On and/or before May 24, 2024, employee(s) used pallet jack(s) to load/unload industrial rack system(s). The industrial rack system(s) did not have any postings of safe load limits. This condition exposed employee(s) to rack system(s) potentially tipping over creating crushing hazard(s).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.22 A03
- Issued
- Jun 24, 2024
- Abate by
- Jul 9, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(3): The employer did not ensure that walking-working surfaces are maintained free of hazards such as sharp or protruding objects, loose boards, corrosion, leaks, spills, snow, and ice. On and/or before May 24, 2024, employee(s) engaged in various customer service activities. The employer did not ensure walking working surfaces were maintained free of protruding objects such as the various size(s) of Portable Plug-in throughout the facility with wire(s) extending out on the floor. Employee(s) were potentially exposed to trip and fall hazard(s). In the following location(s): a) Power Zone-Industrial fan b) Stockroom Office- Tower fan c) Receiver desk- table fan d) Softline's Stockroom Area- table fan e) MCSS Counter- Floor stand fan f) Jewelry Counter- Box Fan g) Greeter's desk- Industrial fan h) Customer Service- Table Fan i) Class Six- Industrial Fan j) Admin Office- Tower fan
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at March ARB Main Exchange
View March ARB Main Exchange's full OSHA safety record →
More inspections in this industry (NAICS 445110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347504227.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.