Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: EFS PLASTICS US INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of EFS PLASTICS US INC. in 504 WHITE BIRCH ROAD, HAZLETON, PA 18202 (NAICS 325211). OSHA activity number 347566028.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch EFS Plastics US INC. — free Get an email when a new federal OSHA severe-injury report for EFS Plastics US INC. is published. One employer, no account, unsubscribe in one click.
Site address
504 WHITE BIRCH ROAD
City
HAZLETON
State
PA
ZIP
18202
Mailing
504 WHITE BIRCH ROAD, HAZLETON, PA 18202
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
325211
Employees
31
Ownership type
A

6 citations on file for this inspection.

1910.212 A01

Serious Gravity 5 2 instances 4 exposed
Issued
Sep 25, 2024
Penalty
Initial $6,453 · Current $4,500 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  a) Extruder 1: On or about June 18, 2024, employees were exposed to burn hazards while operating the extruder due to protective covers being removed from the melt filters.  b) Extruder 2: On or about June 18, 2024, employees were exposed to burn hazards while operating the extruder due to protective covers being removed from the melt filters.  Corrected during the inspection.
Recent events (2)
  • — I (S) $4500
  • — Z (S) $6453

1910.305 G01 IV A

Serious Gravity 1 4 instances 10 exposed
Issued
Sep 25, 2024
Penalty
Initial $4,839 · Current $3,500 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) Washer 1: On or about June 18, 2024, employees working at the washer were exposed to shock hazards due to flexible cords being used to power a fan for at least 1 year.  b) Washer 2: On or about June 18, 2024, employees working at the washer were exposed to shock hazards due to flexible cords being used to power 2 fans for at least 1 year.  c) Granulator: On or about June 18, 2024, employees working at the granulator were exposed to shock hazards due to flexible cords being used to power a fan for at least 1 year.  d) Shipping Desk: On or about June 18, 2024, employees working in the shipping department were exposed to shock hazards due to flexible cords being used to power a relocatable power tap that was supplying power to office equipment, a refrigerator, and a pallet scale.  Corrected during inspection.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $4839

1910.305 G01 IV D

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 25, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces  a) Shipping desk: On or about June 18, 2024, an employee working in the shipping department were exposed to shock hazards due to flexible cords being attached to the framework of the "bulktech" tanks.  Corrected during inspection.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 25, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) Shipping desk: On or about June 18, 2024, an employee working in the shipping department was exposed to shock hazards due to a relocatable power tap being piggybacked into several flexible cords to supplying power to office equipment, a refrigerator, and a pallet scale.  Abatement certification required.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.36 G02

Other-than-serious 1 instance 1 exposed
Issued
Sep 25, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  a) Shipping area, Door 41: On or about June 18, 2024, an employee working in the shipping department was exposed to fire hazard due to one of several access routes to exit doors being partially blocked by pallets.  Corrected during inspection.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.132 D02

Other-than-serious 1 instance 31 exposed
Issued
Sep 25, 2024
Abate by
Nov 8, 2024
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated, the person certifying that the evaluation has been performed, the date(s) of the hazard assessment, and, which identifies the document as a certification of hazard assessment:  a) 504 White Birch Road, Hazleton, PA 18202: The employer did not maintain a certification that a hazard assessment had been completed, when it was completed, and who completed it.  Abatement certification required.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View EFS Plastics US INC.'s full OSHA safety record →