Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: THE DAYTON POWER AND LIGHT COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of THE DAYTON POWER AND LIGHT COMPANY in 1065 WOODMAN DRIVE, DAYTON, OH 45432 (NAICS 238210). OSHA activity number 347882045.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Dayton Power and Light Company — free Get an email when a new federal OSHA severe-injury report for The Dayton Power and Light Company is published. One employer, no account, unsubscribe in one click.
Site address
1065 WOODMAN DRIVE
City
DAYTON
State
OH
ZIP
45432
Mailing
PO BOX 1247, DAYTON, OH 45401
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
20
Ownership type
A

2 citations on file for this inspection.

1910.269 A03 III

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Apr 24, 2025
Abate by
May 7, 2025
Penalty
Initial $16,550 · Current $0 Reduced
29 CFR  1910.269(a)(3)(iii): The contract employer and the host employer did not coordinate their work rules and procedures so that each employee of the contract employer and the host employer was protected as required by this section.   Dayton Power and Light doing business as AES Ohio located at 2385 Campbell Road in Sidney, Ohio;  On or about November 14, 2024 the employer did not coordinate their work rules and procedures with the contract employer to ensure contract and host employees are protected from hazards such as , but not limited to electrical energy. Employees engaged in the refurbishment of the middle metal clad switch gear cabinet were exposed to electrical shock hazards associated with contact with 12kV in that the electrical energy feeding the BK-2M Bus was not verified to be isolated.  In the alternative:  29 CFR 1926.416(a)(3):The employer began work without determining if employees could contact any part of an energized circuit and did not post warning signs and advise employees of the location of the circuit, hazards, and protective measures they need to take:  Dayton Power and Light doing business as AES Ohio located at 2385 Campbell Road in Sidney, Ohio;  On or about November 14, 2024 the employer did not ensure through direct observation or by instrumentation whether any part of an energized electrical power circuit was located in a manner to which a person, tool, or machine could come into physical or electrical contact. Employees engaged in the refurbishment of the middle metal clad switch gear cabinet were exposed to electrical shock hazards associated with contact with 12kV in that the electrical energy feeding the BK-2M Bus was not verified to be isolated.
Recent events (2)
  • — I (S) $0
  • — Z (S) $16550

1926.416 A01

Serious Gravity 10 1 instance 3 exposed
Issued
Apr 24, 2025
Abate by
May 7, 2025
Penalty
Initial $16,550 · Current $16,550
29 CFR 1926.416(a)(1): The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work:  Dayton Power and Light doing business as AES Ohio located at 2385 Campbell Road in Sidney, Ohio;  On or about November 14, 2024, the employer did not ensure employees were protected from coming into contact with electrical power circuits through the course of work. Employees engaged in the refurbishment of the middle metal clad switch gear cabinet were exposed to electrical shock hazards associated with contact with 12kV in that the BK-2M Bus was not deenergized and grounded or effectively guarded.
Recent events (2)
  • — I (S) $16550
  • — Z (S) $16550

View The Dayton Power and Light Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347882045.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.