DAYTON, OH —
OSHA Inspection: THE DAYTON POWER AND LIGHT COMPANY
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of THE DAYTON POWER AND LIGHT COMPANY in 1065 WOODMAN DRIVE, DAYTON, OH 45432 (NAICS 238210). OSHA activity number 347882045.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE DAYTON POWER AND LIGHT COMPANY
- Site address
- 1065 WOODMAN DRIVE
- City
- DAYTON
- State
- OH
- ZIP
- 45432
- Mailing
- PO BOX 1247, DAYTON, OH 45401
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 20
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.269 A03 III
- Issued
- Apr 24, 2025
- Abate by
- May 7, 2025
- Penalty
- Initial $16,550 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(a)(3)(iii): The contract employer and the host employer did not coordinate their work rules and procedures so that each employee of the contract employer and the host employer was protected as required by this section. Dayton Power and Light doing business as AES Ohio located at 2385 Campbell Road in Sidney, Ohio; On or about November 14, 2024 the employer did not coordinate their work rules and procedures with the contract employer to ensure contract and host employees are protected from hazards such as , but not limited to electrical energy. Employees engaged in the refurbishment of the middle metal clad switch gear cabinet were exposed to electrical shock hazards associated with contact with 12kV in that the electrical energy feeding the BK-2M Bus was not verified to be isolated. In the alternative: 29 CFR 1926.416(a)(3):The employer began work without determining if employees could contact any part of an energized circuit and did not post warning signs and advise employees of the location of the circuit, hazards, and protective measures they need to take: Dayton Power and Light doing business as AES Ohio located at 2385 Campbell Road in Sidney, Ohio; On or about November 14, 2024 the employer did not ensure through direct observation or by instrumentation whether any part of an energized electrical power circuit was located in a manner to which a person, tool, or machine could come into physical or electrical contact. Employees engaged in the refurbishment of the middle metal clad switch gear cabinet were exposed to electrical shock hazards associated with contact with 12kV in that the electrical energy feeding the BK-2M Bus was not verified to be isolated.
Recent events (2)
- — I (S) $0
- — Z (S) $16550
1926.416 A01
- Issued
- Apr 24, 2025
- Abate by
- May 7, 2025
- Penalty
- Initial $16,550 · Current $16,550
General-duty citation text
29 CFR 1926.416(a)(1): The employer permitted employees to work in close proximity to energized, unguarded, and ungrounded electric power circuits that the employee could contact in the course of their work: Dayton Power and Light doing business as AES Ohio located at 2385 Campbell Road in Sidney, Ohio; On or about November 14, 2024, the employer did not ensure employees were protected from coming into contact with electrical power circuits through the course of work. Employees engaged in the refurbishment of the middle metal clad switch gear cabinet were exposed to electrical shock hazards associated with contact with 12kV in that the BK-2M Bus was not deenergized and grounded or effectively guarded.
Recent events (2)
- — I (S) $16550
- — Z (S) $16550
More inspections at The Dayton Power and Light Company
View The Dayton Power and Light Company's full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347882045.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.