TOOL, TX —
OSHA Inspection: M&M BBQ COMPANY
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of M&M BBQ COMPANY in 1331 N TOOL DR., TOOL, TX 75143 (NAICS 333318). OSHA activity number 347947301.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- M&M BBQ COMPANY
- Site address
- 1331 N TOOL DR.
- City
- TOOL
- State
- TX
- ZIP
- 75143
- Mailing
- 1331 N TOOL DR., TOOL, TX 75143
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Last modified
- Data loaded
Establishment context
- NAICS code
- 333318
- Employees
- 33
- Ownership type
- A
Citations
11 citations on file for this inspection.
1910.178 L01 II
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $11,585 · Current $0 Reduced
General-duty citation text
29 CFR 1910.178(l)(1)(ii): The employer did not ensure that each operator had successfully completed the training required by paragraph (l), except as permitted by paragraph (l)(5), prior to permitting an employee to operate a powered industrial truck: a) On or about December 19, 2024, and at times prior to, in the production area, where an employee operated a powered industrial truck without having first completed training consisting of formal instruction, practical training, and an evaluation of the operators performance in the workplace.
Recent events (2)
- — I (S) $0
- — Z (S) $11585
1910.252 B02 III
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $11,585 · Current $5,792 Reduced
General-duty citation text
29 CFR 1910.252(b)(2)(iii): Workers and other persons adjacent to the welding area were not protected from the rays by noncombustible or flameproof screens or shields: (a) On or about December 19, 2024 and at times prior to, in the welding areas, workers and other persons adjacent to the welding areas were not protected from arc welding rays by appropriate screens or shields.
Recent events (2)
- — I (S) $5792
- — Z (S) $11585
1910.303 B02
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $11,585 · Current $5,792 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) On or about December 19, 2024, and at times prior to, in the fabrication/welding area, where relocatable power tap/power strip was plugged into extension cords to provide power to angle grinder, chargers stations, drills, and to other extension cord for chargers.
Recent events (2)
- — I (S) $5792
- — Z (S) $11585
1910.303 B07 I
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(i):Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: a) On or about December 19, 2024, and at times prior to, in the Fabrication/Welding Area, where employees used electrical boxes that did not have covers installed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.303 F02
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) On or about December 19, 2024, and at times prior to, in the welding area, where circuit breaker panels were not marked to indicate the purpose of individual breakers. b) On or about December 19, 2024, and at times prior to, in the managers office, where circuit breaker panels were not marked to indicate the purpose of individual breakers.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $11,585 · Current $5,793 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a) On or about December 19, 2024,and at times prior to, in the welding/fabrication area, where there was an electrical box that had exposed wiring because the cover was hanging open and not installed properly.
Recent events (2)
- — I (S) $5793
- — Z (S) $11585
1910.305 C04
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(c)(4):Faceplates for flush-mounted snap switches. Snap switches mounted in boxes did not have faceplates installed so as to completely cover the opening and seat against the finished surface: a) On or about December 19, 2024, and at times prior to, in the office area where employees used snap switches that did not have faceplates installed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) On or about December 19, 2024, and at times prior to, in the welding/grinding department, where a 10 gauge extension cord was being used by employees as permanent wiring to operate equipment.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii):Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: (a) On or about December 19, 2024, in the production area, a Lincoln Electric MIG Welder Power MIG 260 was found with damage to the sheathing on its male cord end fitting.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.132 D02
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.132(d)(2):The employer did not verify, through a written certification, that the required workplace hazard assessment had been performed: (a) On or about December 19, 2024, and at times prior thereto, the employer did not provided written certification documentation that the required workplace hazard assessment had been performed for the manufacturing operations within the workplace located at 1331 North Tool Drive, Tool, Texas, 75143.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.157 C01
- Issued
- Jun 17, 2025
- Abate by
- Jul 15, 2025
- Penalty
- Initial $930 · Current $0 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): The employer did not have portable fire extinguishers that they are readily accessible to employees without subjecting the employees to possible injury: On or about December 16, 2024, fire extinguishers were blocked and not readily accessible: (a) Lincoln Electric MIG Welder Power MIG 260 in front of the fire extinguisher in fabrication/welding area. (b) Fire extinguisher behind Metal Shear in fabrication/welding area.
Recent events (2)
- — I (O) $0
- — Z (O) $930
More inspections at M&M BBQ Company
View M&M BBQ Company's full OSHA safety record →
More inspections in this industry (NAICS 333318)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347947301.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.