Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: STRATEGIC MATERIALS, INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of STRATEGIC MATERIALS, INC in 3240 ROBINSON ROAD, MIDLOTHIAN, TX 76065 (NAICS 423930). OSHA activity number 348147000.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Strategic Materials, INC — free Get an email when a new federal OSHA severe-injury report for Strategic Materials, INC is published. One employer, no account, unsubscribe in one click.
Site address
3240 ROBINSON ROAD
City
MIDLOTHIAN
State
TX
ZIP
76065
Mailing
17220 KATY FREEWAY SUITE 150, HOUSTON, TX 77094
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Last modified
Data loaded
NAICS code
423930
Employees
24
Ownership type
A

6 citations on file for this inspection.

1910.140 C13 II

Serious Gravity 5 1 instance 5 exposed
Issued
Sep 29, 2025
Abate by
Oct 28, 2025
Penalty
Initial $11,348 · Current $11,348
29 CFR  1910.140(c)(13)(ii): Anchorages were not designed, installed, and used, under the supervision of qualified person, as part of a complete personal fall protection system that maintains a safety factor of at least two:  On or about March 31, 2025, and times prior thereto, anchor point(s) utilized by employee(s) were not designed, installed or safely used as part of a complete personal fall protection system to maintain a safety factor of at least two in the 12 Mesh Building (hole rough cut in metal plate adjacent to Crusher).
Recent events (2)
  • — C (S) $11348
  • — Z (S) $11348

1910.303 B07 IV

Serious Gravity 1 1 instance 8 exposed
Issued
Sep 29, 2025
Abate by
Oct 28, 2025
Penalty
Initial $8,512 · Current $8,512
29 CFR  1910.303(b)(7)(iv): Electrical equipment was not free of damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:    On or about March 31, 2025, and times prior thereto, electrical flex conduit was not maintained free of physical damage from a transformer to the main control panel in the 5/8 Building along the South Wall.
Recent events (2)
  • — C (S) $8512
  • — Z (S) $8512

1910.28 B15

Repeat Gravity 1 1 instance 5 exposed
Issued
Sep 29, 2025
Abate by
Oct 28, 2025
Penalty
Initial $85,116 · Current $85,116
29 CFR  1910.28(b)(15): Walking-working surfaces not otherwise addressed. Except as provided elsewhere in this section or by other subparts of this part, the employer did not ensure each employee on a walking working surface 4 feet (1.2 m) or more above a lower level is protected from falling by one of the systems listed in 1910.28(b)(15)(i)-(iii):   On or about March 31, 2025, and times prior thereto, employee(s) worked from an elevated work platform measuring more than four (4) feet above the lower level without a complete guard rail system in the 12 Mesh Building.   Strategic Materials Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.28(b)(15), which was contained in OSHA inspection number 1655540, citation number Three, item number One and was affirmed as a final order on June 28, 2024, with respect to a workplace located at 3240 Robinson Road in Midlothian, TX; and  Strategic Materials Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.28(b)(15), which was contained in OSHA inspection number 1500353, citation number One, item number Two and was affirmed as a final order on January 19, 2021, with respect to a workplace located at 3240 Robinson Road in Midlothian, TX.
Recent events (2)
  • — C (R) $85116
  • — Z (R) $85116

1910.303 B07 III

Repeat Gravity 5 2 instances 11 exposed
Issued
Sep 29, 2025
Abate by
Oct 28, 2025
Penalty
Initial $70,938 · Current $70,938
29 CFR  1910.303(b)(7)(iii): Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, were damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues:  On or about March 31, 2025, and times prior thereto and thereafter, internal components of live electrical boxes and cabinets were contaminated by a foreign substance identified as the byproduct of the glass recycling process in the following instances:  a) 5/8 Building, South Wall, Main Panel Area b) Optical Building, Blower Controls Area  Strategic Materials Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(7)(iii), which was contained in OSHA inspection number 1655540, citation number One, item number Seven-b and was affirmed as a final order on June 28, 2024, with respect to a workplace located at 3240 Robinson Road in Midlothian, TX.
Recent events (2)
  • — C (R) $70938
  • — Z (R) $70938

1910.303 G02 I

Repeat Gravity 1 1 instance 8 exposed
Issued
Sep 29, 2025
Abate by
Oct 28, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  On or about March 31, 2025, and times prior thereto, employee(s) were exposed to accidental contact of unguarded live electrical equipment rated for more than 50-volts in the 5/8 Building, Main Panel Area on the South Wall.   Strategic Materials Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(g)(2)(i), which was contained in OSHA inspection number 1655540, citation number One (1), item number Eight - a (8a), and was affirmed as a final order on June 28, 2024, with respect to a workplace located at 3240 Robinson Road in Midlothian, TX.
Recent events (2)
  • — C (R) $0
  • — Z (R) $0

1910.147 C06 II

Other-than-serious 1 instance 13 exposed
Issued
Sep 29, 2025
Abate by
Oct 28, 2025
Penalty
Initial $1,594 · Current $1,594
29 CFR  1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed:                                                                                                                                On or about March 31, 2025, and times prior thereto, the employer had not certified in accordance with this subpart that periodic inspections of their energy control procedures had been performed.
Recent events (2)
  • — C (O) $1594
  • — Z (O) $1594

View Strategic Materials, INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348147000.