Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEPARTMENT OF TRANSPORTATION - FAA

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPARTMENT OF TRANSPORTATION - FAA in 4201 EMPIRE AVE, BURBANK, CA 91505 (NAICS 926120). OSHA activity number 348159625.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Department of Transportation - FAA — free Get an email when a new federal OSHA severe-injury report for Department of Transportation - FAA is published. One employer, no account, unsubscribe in one click.
Site address
4201 EMPIRE AVE
City
BURBANK
State
CA
ZIP
91505
Mailing
4201 EMPIRE AVE, BURBANK, CA 91505
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
926120
Employees
11
Ownership type
D

6 citations on file for this inspection.

1910.303 G01 II

Serious Gravity 5 3 instances 11 exposed
Issued
May 1, 2025
Abate by
May 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage.  Telco room: On or about April 1, 2025, and at times prior thereto, the employer did not ensure at least 3 feet in front of the electrical panel was clear. The circuit breaker panel had several blueprint(s) and office equipment obstructing the panel. This condition interferes with access and immediate shutdown of a circuit in the panel, particularly in the event of an emergency. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s).  In the following location(s):  a) Telco Room b) Radio Room c) Janitorial room
Recent events (1)
  • — Z (S) $0

1910.37 A03

Other-than-serious 1 instance 10 exposed
Issued
May 1, 2025
Abate by
May 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.37(a)(3): Exit route(s) were not kept free and unobstructed.  Back office area: On or about April 3rd, 2025, and at times prior thereto, employee(s) would store portable air conditioner(s), boxes and other office equipment and/or supplies along the path of the exit route leading to the outside. This condition potentially exposed employee(s) to fire hazard(s).
Recent events (1)
  • — Z (O) $0

1910.37 A04

Other-than-serious 1 instance 1 exposed
Issued
May 1, 2025
Abate by
May 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times.  Telco room: On or about April 3rd, 2025, and at times prior thereto, a ceiling panel in the Telco room was improperly installed. This condition potentially exposed employee(s) to fire and smoke inhalation hazard(s).
Recent events (1)
  • — Z (O) $0

1910.151 B

Other-than-serious 1 instance 10 exposed
Issued
May 1, 2025
Abate by
May 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.151(b): Adequate first aid supplies were not readily available.  Office Space: On or about April 3rd, 2025, and at times prior thereto, employee(s) were tasked to perform administrative and technical duties, including, maintaining air traffic towers, navigation and radar surveillance. The employer did not ensure that the first aid kit was adequately supplied. Employee(s) were potentially exposed to workplace injuries.
Recent events (1)
  • — Z (O) $0

1910.157 E02

Other-than-serious 5 instances 11 exposed
Issued
May 1, 2025
Abate by
May 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly.  On or about April 1, 2025, and at times prior thereto, fire extinguisher(s) had not been subject to their monthly maintenance check(s). This condition potentially exposed employee(s) to extinguisher mechanical failure to put out and/or escape incipient fire hazard(s).  In the following location(s):  a) Telco room b) Office space(s) c) Break room d) Engine room e) All fire extinguisher(s) within the interior and exterior of bldg.
Recent events (1)
  • — Z (O) $0

1910.157 E03

Other-than-serious 5 instances 11 exposed
Issued
May 1, 2025
Abate by
May 13, 2025
Penalty
Initial $0 · Current $0
29 CFR  1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check.  On or about April 1, 2025, and at times prior thereto, several 10lb fire extinguisher had not been subject to their annual maintenance check(s). This condition potentially exposed employee(s) to extinguisher mechanical failure to put out and/or escape incipient fire hazard(s).  In the following location(s):  a) Telco room b) Office space(s) c) Break room d) Engine room e) All fire extinguisher(s) within the interior and exterior of bldg.
Recent events (1)
  • — Z (O) $0

View Department of Transportation - FAA's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348159625.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.