BETHLEHEM, PA —
OSHA Inspection: FRESHPET, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of FRESHPET, INC. in 176 N. COMMERCE WAY, BETHLEHEM, PA 18017 (NAICS 311111). OSHA activity number 348217662.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FRESHPET, INC.
- Site address
- 176 N. COMMERCE WAY
- City
- BETHLEHEM
- State
- PA
- ZIP
- 18017
- Mailing
- 176 N. COMMERCE WAY, BETHLEHEM, PA 18017
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311111
- Employees
- 150
- Ownership type
- A
Citations
1 citation on file for this inspection.
1910.119 D03 II
- Issued
- Sep 30, 2025
- Abate by
- Oct 27, 2025
- Penalty
- Initial $0 · Current $0
0170
General-duty citation text
29 CFR 1910.119(d)(3)(ii):The employer did not document that equipment complies with recognized and generally accepted good engineering practices. a) 176 N Commerce Way, Bethlehem, PA 18107, rooftop, piping near Condenser EC3: On or about June 26, 2025, the employer did not comply with their recognized and generally accepted good engineering practices IIAR 2-2014 section 5.14.5 in that a length of HSD ammonia piping connected to EC3 was not labeled with information of what state of ammonia was contained within, potentially resulting in inefficient or under-informed emergency response or maintenance. b) 176 N Commerce Way, Bethlehem, PA 18107, machinery room, king valve: On or about May 1, 2025, the employer did not comply with their recognized and generally accepted good engineering practices when valve RLSV101, identified as "King Valve Main Shut off," is not manually operable, which could hinder the prompt emergency shutoff of the system in critical situations. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states that employees and their representatives were informed of this abatement.
Recent events (1)
- — Z (O) $0
More inspections at Freshpet, INC.
View Freshpet, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 311111)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 348217662.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.