NORTH RICHLAND HILLS, TX —
OSHA Inspection: TYSON PREPARED FOODS INC.
Programmed Related inspection · Safety discipline
At a glance
On , OSHA opened a programmed Related safety inspection of TYSON PREPARED FOODS INC. in 6350 BROWNING COURT, NORTH RICHLAND HILLS, TX 76180 (NAICS 311612). OSHA activity number 348396318.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- TYSON PREPARED FOODS INC.
- Site address
- 6350 BROWNING COURT
- City
- NORTH RICHLAND HILLS
- State
- TX
- ZIP
- 76180
- Mailing
- 6350 BROWNING COURT, NORTH RICHLAND HILLS, TX 76180
What kind of inspection was it?
- Inspection type
- Programmed Related (J)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311612
- Employees
- 340
- Ownership type
- A
Citations
1 citation on file for this inspection.
1910.303 B07 IV
- Issued
- Jan 16, 2026
- Abate by
- Feb 17, 2026
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of electric equipment, such as parts that were broken, bent, cut or deteriorated by corrosion, chemical action, or overheating: On or about July 23, 2025, and at times prior thereto, in the site engine rooms, 480 volt load center breaker toggle handles were missing integral barriers, allowing dust and debris to enter the energized load centers in the following instances: a) Breaker HS208 FES COMP 12 BRK 1. b) Breaker HS207 FES HI STAGE 10 BRK 2. c) Breaker HS206 FES HI STAGE 9 BRK 3. d) Breaker HS209 FES HI STAGE 1 BRK 5. e) Breaker HTR202 Panel HB3 BRK 17. f) Breaker PANEL HB4 BRK 19. g) Breaker FES HI STAGE 3 BRK 16. h) Breaker FES BOOSTER 2 BRK 15. i) Breaker PANEL MAINTENANCE SHOP BRK 13. j) Breaker C101 CONTRL PNL BRK 21. k) Breaker HS104 FES #4 HI STAGE BRK 1.
Recent events (1)
- — Z (O) $0
More inspections at Tyson Prepared Foods INC.