YORK, PA —
OSHA Inspection: STANDARD REGISTER COMPANY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of STANDARD REGISTER COMPANY in 121 MOUNT ZION ROAD, YORK, PA 17402 (NAICS 323116). OSHA activity number 314244823.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STANDARD REGISTER COMPANY
- Site address
- 121 MOUNT ZION ROAD
- City
- YORK
- State
- PA
- ZIP
- 17402
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Y
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 323116
- SIC code (legacy)
- 2761
- Employees
- 110
- Ownership type
- A
- Industry flags
- Manufacturing safety.
Citations
2 citations on file for this inspection.
5(a)(1)
- Issued
- Jul 21, 2011
- Abate by
- Dec 31, 2012
- Penalty
- Initial $3,400 · Current $2,720 Reduced
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to severe burn injuries from the potential dust explosion that could have resulted from, or have been exacerbated by, recycling the air back into the building without a high speed abort gate, a lack of a back flash damper and the lack of deflagration vents for the dust collector: (a)Standard Register Company - The dust collection system was used to collect paper dust. The dust collection system, duct work leading to the dust collector and the recycled air were not protected by a deflagration vent, a back flash damper and a high speed abort gate system in the event of a fire or explosion, on or about April 1, 2011. ABATEMENT NOTE: Among other methods, one feasible and acceptable abatement method to correct this hazard includes following the National Fire Protection Association (NFPA) 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids, 2006 Edition, including, but not limited to installing a high speed abort system on the return air duct work, installing a back flash damper on the inlet side, a deflagration system or a suppression system on the dust collector and/or duct work. All proposed control measures shall be approved for each particular use by a competent engineer or other technically qualified person. Ninety (90) day progress reports are required during the abatement period. *STEP 1 Submit to the Area Director a written, detailed plan of abatement outlining a schedule for the implementation of engineering and/or administrative measures to control employee exposure to hazardous substances as referenced in this citation. This plan shall include, at a minimum, target dates for the following actions which must be consistent with the abatement dates required by this citation: 1.Evaluation of engineering/administrative control options. 2.Selection of optimum control methods and completion of design. 3.Procurement, installation and operation of selected control measures; and 4.Acceptance or modification/redesign of controls. *STEP 2 Abatement shall have been completed by the implementation of feasible engineering upon verification of their effectiveness in achieving compliance. Date by Which Violation Must be Abated:STEP - 1 10/22/11 Date by Which Violation Must be Abated:STEP - 2 07/23/12 Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (3)
- — P (S) $2720.00
- — I (S) $2720.00
- — Z (S) $3400.00
1910.22 A01
- Issued
- Jul 21, 2011
- Abate by
- Jul 26, 2011
- Penalty
- Initial $3,400 · Current $2,720 Reduced
Recent events (2)
- — I (O) $2720.00
- — Z (S) $3400.00
More inspections at Standard Register Company
View Standard Register Company's full OSHA safety record →
More inspections in this industry (NAICS 323116)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 314244823.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.