OSHA Inspection: MARINE CORP COMMUNITY SERVICES

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MARINE CORP COMMUNITY SERVICES in SEVERAL LOCATIONS MCCS, CAMP PENDLETON, CA 92055 (NAICS 452111). OSHA activity number 332802990.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Marine Corp Community Services for free Get an email when a new federal OSHA severe-injury report for Marine Corp Community Services is published. One employer, no account, unsubscribe in one click.
Site address
SEVERAL LOCATIONS MCCS
City
CAMP PENDLETON
State
CA
ZIP
92055
Mailing
BLDG 11000 MCCS, CAMP PENDLETON, CA 92055
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
452111
Employees
200
Ownership type
Federal government (D)

10 citations on file for this inspection.

1910.303 E01 I

Serious Gravity 1 1 instance 25 exposed
Issued
Apr 24, 2012
Abate by
Apr 25, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(e)(1)(i): The manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product was not identified on electrical equipment:      Retail Warehouse Shipping Area: On March 6, 2012, and at times prior thereto, a homemade electrical outlet with GFCI was not descriptively marked.
Recent events (1)
  • · Z (S) $0

1910.303 F02

Serious Gravity 1 1 instance 25 exposed
Issued
Apr 24, 2012
Abate by
Apr 25, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:      Retail Warehouse by Freezer: On March 6, 2012, and at times prior thereto, a disconnect box had no markings indicating its purpose.
Recent events (1)
  • · Z (S) $0

1910.305 B01 II

Serious Gravity 5 4 instances 25 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:      On March 6, 2012, and at times prior thereto, in the following locations, openings in circuit breaker panels were not covered by blanks;      A. San Onofre Exchange by Customer Service Area: Panel L1A which energized lighting throughout the building had several openings inside the cabinet due to an unsecured faceplate and uncovered spare spaces which exposed the live inner conductors.     B. San Onofre Exchange by stairs to upper mezzanine: Panel P2A which energized ventilation, lighting, and a freezer had several uncovered spare spaces which exposed the live inner conductors.    C. Retail Warehouse: The Intermatic Dock Light Timer was missing an internal guard and the live inner conductors were exposed.    D. Country Store: A Siemens Panel had an uncovered spare space and live inner conductors were exposed.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 25 exposed
Issued
Apr 24, 2012
Abate by
Apr 25, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used for purposes prohibited by subparagraphs (a) through (f) of this paragraph:      Retail Warehouse Mezzanine over Restrooms: On March 6, 2012, and at times prior thereto, a flexible cord was used in lieu of permanent wiring to energize an industrial fan.
Recent events (1)
  • · Z (S) $0

1910.332 B01

Serious Gravity 10 1 instance 5 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety related work practices required by 29 CFR 1910.331 through 29 CFR 1910.335 that pertained to their respective job assignments:      On March 7, 2012, and at time prior thereto, MCCS electricians had not been trained regarding what work pratices and protective equipment was required to protect them against electric shock, arc flash, and arc blast hazards while performing live electrical work, live trouble-shooting and verifying whether or not electrical equipment was properly de-energized.
Recent events (1)
  • · Z (S) $0

1910.333 A01

Serious Gravity 10 1 instance 5 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not de-energized before the employee on or near them:      On March 7, 2012, and at time prior thereto, the employer allowed MCCS Electricians to conducted live work on electrical equipment lower than 600 volts.
Recent events (1)
  • · Z (S) $0

1910.333 A02

Serious Gravity 10 1 instance 5 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a)(2): Where exposed to live parts that were not de-energized, other safety related work practices were not used to protect employees who could be exposed to the electrical hazards involved:      On March 7, 2012, and at time prior thereto, the employer had not developed and implemented an Electrical Safety Related Work Practices Program to address hazards caused by arc flash, arc blast and electric shock in the facility. MCCS Electricians conducted live work, live trouble-shooting and tested electrical equipment to ensure that it was properly de-energized
Recent events (1)
  • · Z (S) $0

1910.335 A01 I

Serious Gravity 10 1 instance 5 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with, and/or did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:      On March 7, 2012, and at time prior thereto, Personal protective equipment such as, but not limited to, voltage rated gloves, FR clothing, face shields, balaclavas, hard hats and hearing protection were not provided to employees who performed live electrical work including trouble-shooting, or who verified that electrical equipment was properly de-energized.
Recent events (1)
  • · Z (S) $0

1910.335 A02 I

Serious Gravity 5 1 instance 5 exposed
Issued
Apr 24, 2012
Abate by
Jun 6, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(2)(i): When working near exposed energized conductors or circuit parts, each employee did not use insulated tools or handling equipment when the tools or handling equipment might have made contact with such conductors or parts:      On March 7, 2012, and at time prior thereto, voltage rated tools were not provided to electricians when working near energized electrical equipment.
Recent events (1)
  • · Z (S) $0

1910.334 A02 II

Serious Gravity 5 1 instance 25 exposed
Issued
Apr 24, 2012
Abate by
Apr 25, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): When there was a defect or evidence of damage that could expose an employee to injury, the defective or damaged item was not removed from service until the repairs and tests necessary to render the electrical equipment safe had been made:      Country Store: On March 6, 2012, and at times prior thereto, a flexible power cord energizing a alarm or battery system was badly damaged and the live inner conductors were exposed.