Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: JERSEY CENTRAL POWER & LIGHT COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of JERSEY CENTRAL POWER & LIGHT COMPANY in ROUTE 88 & ARNOLD AVENUE, POINT PLEASANT BORO, NJ 08742 (NAICS 221122). OSHA activity number 333891422.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Jersey Central Power & Light Company — free Get an email when a new federal OSHA severe-injury report for Jersey Central Power & Light Company is published. One employer, no account, unsubscribe in one click.
Site address
ROUTE 88 & ARNOLD AVENUE
City
POINT PLEASANT BORO
State
NJ
ZIP
08742
Mailing
331 NEWMAN SPRINGS ROAD BUILDING 3, SUITE 325, RED BANK, NJ 07701
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
10000
Ownership type
A

3 citations on file for this inspection.

1910.269 C01

Deleted Serious Gravity 10 1 instance 3 exposed
Issued
Oct 15, 2012
Abate by
Nov 5, 2012
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.269(c)(1):     Additional job briefings were not held when a significant job change affected the safety of the employees during the course of the work:      a)  Rt. 88 & Arnold Avenue, Pt. Pleasant, NJ:  The 3 man crew on site did not conduct an additional safety meeting when the employees were preparing to attach the sling to the pot and realized that the area to attach was not in a safe reaching distance to the placement of the bucket truck, occured on or about 4/17/12.    NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
  • — J (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.67 C02 IV

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Oct 15, 2012
Abate by
Nov 5, 2012
Penalty
Initial $7,000 · Current $0 Reduced
29 CFR 1910.67(c)(2)(iv):     Employees did not always stand firmly on the floor of the basket, and were allowed to sit or climb on the edge of the basket or use planks, ladders, or other devices for a work position:    a)  Rt. 88 & Arnold Avenue, Pt. Pleasant, NJ:  The employee was not in a proper positon to reach the clamp on the top of the transformer for removal and reached around the steet side of the pole in order to put the lifting sling on the transformer which put him in close proximity to the energized transformer mounted arrester top.  The employee did not stand firmly on the floor of bucket truck #12412.  The employee wedged his feet up the inside of the bucket inorder to reach the transformer, observed on or about 4/17/12.      NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (3)
  • — J (S) $0
  • — C (S) $7000
  • — Z (S) $7000

1910.269 L02 II

Deleted Repeat Gravity 10 1 instance 1 exposed
Issued
Oct 15, 2012
Abate by
Nov 5, 2012
Penalty
Initial $38,500 · Current $0 Reduced
29 CFR 1910.269(l)(2)(ii):     The employer did not ensure that no employee(s) approached or took conductive objects closer to exposed energized parts than set forth in Tables R-6 through R-10 when the energized parts were not insulated from the employee and from any other conductive object of a different potential:    a)  Rt.88 & Arnold Avenue, Pt. Pleasant, NJ:  The employer did not ensure that minimum approach distances were maintained when an employee attempted to attach a lifting sling to the lifting ear of the middle transformer and made contact with the energized lightning arrester of the road side transformer.  The energized lightning arrester was not insulated from the employee, occurred on or about 4/17/12.    NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.     JERSEY CENTRAL POWER & LIGHT COMPANY; WAS PREVIOUSLY CITED FOR A VIOLATION OF THIS OCCUPATIONAL SAFETY AND HEALTH STANDARD, ITS EQUIVALENT, OR ESSENTIALLY SIMILAR STANDAR, 1910.269(l)(2) WHICH WAS CONTAINED IN OSHA INSPECTION NUMBER 313236101 CITATION NUMBER 01, ITEM NUMBER 03, ISSUED ON 01/08/10. NOTE: FINAL ORDER DATE - 1/12/11.
Recent events (3)
  • — J (R) $0
  • — C (R) $38500
  • — Z (R) $38500