OSHA Inspection: JERSEY CENTRAL POWER & LIGHT COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of JERSEY CENTRAL POWER & LIGHT COMPANY in 934 BROWN RD., BRIDGEWATER, NJ 08807 (NAICS 221122). OSHA activity number 348834466.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Jersey Central Power & Light Company — free Get an email when a new federal OSHA severe-injury report for Jersey Central Power & Light Company is published. One employer, no account, unsubscribe in one click.
Site address
934 BROWN RD.
City
BRIDGEWATER
State
NJ
ZIP
08807
Mailing
101 CRAWFORD RD, HOLMDEL, NJ 07733
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Last modified
Data loaded
NAICS code
221122
Employees
15
Ownership type
A

2 citations on file for this inspection.

1910.269 A02 II D

Serious Gravity 10 1 instance 3 exposed
Issued
Jun 10, 2026
Penalty
Initial $16,550 · Current $16,550
29 CFR  1910.269(a)(2)(ii)(D): The proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electric equipment, where the employer failed to endure non-insulated tools were not utilized.  A) Jersey Central Power & Light Company - On March 24, 2026, an employee sustained second?degree burns to the face and neck when a non?insulated tool contacted an exposed energized part, resulting in an arc flash. The employer failed to ensure that employees used insulated tools while securing the cut?out box, exposing them to electrical arc?flash and burn hazards in violation of 29 CFR 1910.269(a)(2)(ii)(D).   Incident occurred on March 24, 2026
Recent events (2)
  • — C (S) $16550
  • — Z (S) $16550

1910.269 L08 V D

Serious Gravity 10 1 instance 3 exposed
Issued
Jun 10, 2026
Abate by
Jul 8, 2026
Penalty
Initial $16,550 · Current $16,550
29 CFR  1910.269(l)(8)(v)(D): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective equipment consisting of at a minimum a face shield with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2 but less than 9.0 Cal/cm2.    A) Jersey Central Power & Light Company - On March 24, 2026, an employee sustained second?degree burns to the face and neck when a non?insulated tool contacted an energized part, causing an arc flash. The employer failed to ensure that the employee, while working within the arc?flash boundary, wore the required arc?rated face protection (such as a face shield with an arc rating consistent with the estimated heat?energy exposure), as mandated by 29 CFR 1910.269(l)(8)(v)(D).   Incident occurred on March 24, 2026