OSHA Inspection: JERSEY CENTRAL POWER & LIGHT COMPANY

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of JERSEY CENTRAL POWER & LIGHT COMPANY in 320 WEST MAIN ST., SAYREVILLE, NJ 08871 (NAICS 221122). OSHA activity number 347843674.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Jersey Central Power & Light Company — free Get an email when a new federal OSHA severe-injury report for Jersey Central Power & Light Company is published. One employer, no account, unsubscribe in one click.
Site address
320 WEST MAIN ST.
City
SAYREVILLE
State
NJ
ZIP
08871
Mailing
101 CRAWFORD RD, HOLMDEL, NJ 07733
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
30
Ownership type
A

3 citations on file for this inspection.

1910.269 A03 I A

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Nov 22, 2024
Abate by
Dec 19, 2024
Penalty
Initial $16,131 · Current $0 Reduced
29 CFR  1910.269(a)(3)(i)(A): Contract employer(s) were not informed by the host employer of the characteristics of the host employer's installation that are related to the safety of the work to be performed, as listed in paragraphs (a)(4)(i) through (a)(4)(v) of this section;   a) Location-320 West Main St., Sayreville, NJ 08872- JCP&L Substation  On or about 5/24/2024, contractor employee(s) conducted air quality testing within a JCP+L sub-station using hand-held multi-gas meter(s) and air sampling pumps, such as but not limited to, a Lighthouse 3016-iaq Particulate meter.  Electrical lines and/or conductors housed within the sub-station were energized during air quality testing work by employee(s).  The contract employer was not informed of the energized state and voltage(s) of lines and equipment housed in the building in which contractor work was to be performed, exposing contractor employee(s) to electrical hazard(s). An arc flash incident occurred on 5/24/2024, in which employee(s) sustained burns to both hands and face.
Recent events (3)
  • — F (S) $0
  • — C (S) $16131
  • — Z (S) $16131

1910.269 A04

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Nov 22, 2024
Abate by
Dec 19, 2024
Penalty
Initial $0 · Current $0
29 CFR  1910.269(a)(4): Existing characteristics and conditions of electric lines and equipment that were related to the safety of the work to be performed was not determined before work on or near the lines or equipment was started.  Such characteristics and conditions include, but not limited to 1910.269(a)(4)(i) through 1910.269(a)(4)(viii):  a) Location-320 West Main St., Sayreville, NJ 08872- JCP&L Substation  On or about 5/24/2024, contractor employee(s) conducted air quality testing within a JCP+L sub-station using hand-held multi-gas meter(s) and air sampling pumps, such as but not limited to, a Lighthouse 3016-iaq Particulate meter.  Electrical lines and/or conductors housed within the sub-station were energized during air quality testing work by employee(s).  Characteristics and conditions of lines and equipment within the sub-station building, including nominal voltages, were not determined and shared with the contract employer before contractor work was to be performed, exposing contractor employee(s) to electrical hazard(s). An arc flash incident occurred on 5/24/2024, in which employee(s) sustained burns to both hands and face.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.269 M03 I

Serious Gravity 10 1 instance 2 exposed
Issued
Nov 22, 2024
Abate by
Dec 19, 2025
Penalty
Initial $16,131 · Current $16,000 Reduced
29 CFR  1910.269(m)(3)(i): The employee that the employer designates pursuant to paragraph (m)(2) of this section as being in charge of the clearance did not make a request of the system operator to deenergize the particular section of line or equipment, as the designated employee in charge (as this term is used in paragraph (m)(3) of this section) and responsible for the clearance:  a) Location-320 West Main St., Sayreville, NJ -JCP&L Substation,  On or about 5/24/2024, a TRC Environmental Corporation contracted employee sustained electrical burns due to an arc flash while performing air quality testing within a JCP&L electrical power sub-station.  A JCP&L supervisor and qualified employee designated to escort the TRC Environmental Corporation employee into the substation did not verify the building was de-energized prior to the start of work.
Recent events (3)
  • — F (S) $16000
  • — C (S) $16131
  • — Z (S) $16131