OSHA Inspection: CONVERTING TECHNOLOGY, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CONVERTING TECHNOLOGY, INC. in 1557 CARMEN DRIVE, ELK GROVE VILLAGE, IL 60007 (NAICS 333514). OSHA activity number 333898450.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Converting Technology, INC. — free Get an email when a new federal OSHA severe-injury report for Converting Technology, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1557 CARMEN DRIVE
City
ELK GROVE VILLAGE
State
IL
ZIP
60007
Mailing
1557 CARMEN DRIVE, ELK GROVE VILLAGE, IL 60007
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333514
Employees
63
Ownership type
A

8 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 1 instance 3 exposed
Issued
May 2, 2012
Abate by
May 23, 2012
Penalty
Initial $3,500 · Current $1,750 Reduced
OSH ACT of 1970 Section (5)(a)(1):  The employer did not furnish employment and a place of employment which was free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to amputation and laceration hazards.    a) Blanking Department- Metal cutting saws, such as the JET Bandsaw, were not equipped with a mechanism to prevent the machine from automatically restarting upon restoration of power after a power failure.     In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.213 B03

Serious Gravity 5 1 instance 3 exposed
Issued
May 2, 2012
Abate by
May 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.213(b)(3):  On applications where injury to the operator might result if motors were to restart after power failures, provision were not made to prevent the machines from automatically restarting upon restoration of power.    a) Counter Cutting Department- Wood cutting saws, such as the Delta Vertical Bandsaw, were not equipped with a mechanism to prevent the machine from automatically restarting upon restoration of power after a power failure.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.178 L01 I

Serious Gravity 10 1 instance 40 exposed
Issued
May 2, 2012
Abate by
Jul 2, 2012
Penalty
Initial $4,900 · Current $2,450 Reduced
29 CFR 1910.178(l)(1)(i):  The employer did not ensure that each powered industrial truck operator was competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in the standard.    a) Facility wide- The employer failed to ensure that all employees who operated powered industrial trucks, such as the Clark Sit-down Forklift, were competent and had demonstrated their competency through training and an evaluation of their driving capabilities.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $4900

1910.212 A01

Serious Gravity 10 2 instances 4 exposed
Issued
May 2, 2012
Abate by
Jul 2, 2012
Penalty
Initial $4,900 · Current $2,450 Reduced
29 CFR 1910.212(a)(1):  One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks.     a) Blanking Department- The employer failed to provide one or more methods of machine guarding to protect employees from the point of operation on equipment, such as the unused portion of the metal cutting saw blade on the JET Horizontal Bandsaw.      b) Die Room- The employer failed to provide one or more methods of machine guarding that would protect employees from the point of operation on equipment, such as the Multi Bend System Bender #MB710-B.     In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $4900

1910.213 I01

Serious Gravity 10 1 instance 3 exposed
Issued
May 2, 2012
Abate by
May 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.213(i)(1): All portions of the saw blade were not enclosed or guarded, except for the working portion of the blade between the bottom of the guide rolls and the table, on wood cutting bandsaws.      a) Counter Cutting Department- The employer failed to provide wood cutting saws, such as the Delta Vertical Bandsaw, with a guard over all nonworking portions of the cutting blade.            In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.215 A04

Serious Gravity 5 4 instances 9 exposed
Issued
May 2, 2012
Abate by
May 23, 2012
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1910.215(a)(4):  On offhand grinding machines, work rests were not adjusted closely to the wheel with a maximum opening of one-eighth inch to prevent the work from being jammed between the wheel and the rest, which may cause wheel breakage.     a) Die Room- The employer failed to ensure work rest(s) were adjusted to no more than a one-eighth inch opening to support offhand grinding work on grinding machines, such as the Delta 8" Grinder #P9652, the Delta 8" Grinder #P9704, and the Delta 8" Grinder #P9816.    In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

1910.215 B09

Serious Gravity 5 4 instances 3 exposed
Issued
May 2, 2012
Abate by
May 23, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9):  The abrasive wheel machinery were not guarded with an adjustable tongue guard, and when one was provided the distance between the wheel and the adjustable tongue guard exceeded one-fourth inch.    a) Die Room- The employer failed to ensure that all abrasive wheel machinery was equipped with a tongue guard, and when equipped with a tongue guard that a distance of no more than one-fourth inch was exceeded between the tongue guard and the abrasive wheel on equipment, such as the Delta 8 Grinder #P9652, the Delta 8 Grinder # P9704, and the Delta 8 Grinder #P9816.      In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 4 instances 2 exposed
Issued
May 2, 2012
Abate by
May 23, 2012
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not installed and used in accordance with instructions included in the listing or labeling.    a) Stripping Department- The employer failed to ensure that electrical equipment, such as the 7-Outlet Ace Power Strips, were being used only to power audiovisual equipment as permitted under their listing and labeling.      In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification.  This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

View Converting Technology, INC.'s full OSHA safety record →