CAMPBELLTON, TX —
OSHA Inspection: PIONEER DRILLING COMPANY
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of PIONEER DRILLING COMPANY in MIDDLE MCCOWEN 7H LAT 29.05767, LONG -98.09129, CAMPBELLTON, TX 78008 (NAICS 213111). OSHA activity number 334197233.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- PIONEER DRILLING COMPANY
- Site address
- MIDDLE MCCOWEN 7H LAT 29.05767, LONG -98.09129
- City
- CAMPBELLTON
- State
- TX
- ZIP
- 78008
- Mailing
- 334 FLATO ROAD, CORPUS CHRISTI, TX 78403
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213111
- Employees
- 15
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.106 B06
- Issued
- Sep 18, 2012
- Abate by
- Oct 3, 2012
- Penalty
- Initial $5,000 · Current $3,000 Reduced
General-duty citation text
29 CFR 1910.106(b)(6): In locations where flammable vapors may be present, precautions were not taken to prevent ignition by eliminating or controlling sources of ignition. Sources of ignition may include open flames, lightning, smoking, cutting and welding, hot surfaces, frictional heat, sparks (static, electrical, and mechanical), spontaneous ignition, chemical and physical-chemical reactions, and radiant heat: On or about 05/04/12, and at times prior thereto, employees were exposed to an electrical/explosion hazard while working near the flammable diesel tanks storage area which had a loose bonding/grounding connector that connected the tanks to the earth ground rod.
Recent events (2)
- — I (S) $3000
- — Z (S) $5000
1910.106 D04 III
- Issued
- Sep 18, 2012
- Abate by
- Oct 3, 2012
- Penalty
- Initial $4,000 · Current $2,400 Reduced
General-duty citation text
29 CFR 1910.106(d)(4)(iii): Electrical wiring and equipment located in inside storage rooms used for Class I liquids shall be approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Class II and Class III liquids, shall be approved for general use: On or about 05/04/12, and at times prior thereto, employees were exposed to an fire/explosion hazard while working near the SCR House where flammable paint was being stored near a microwave and refrigerator that was in use.
Recent events (2)
- — I (S) $2400
- — Z (S) $4000
1910.303 C03
- Issued
- Sep 18, 2012
- Abate by
- Oct 3, 2012
- Penalty
- Initial $4,000 · Current $2,400 Reduced
General-duty citation text
29 CFR 1910.303(c)(3): Conductors were not spliced or joined with splicing devices suitable for the use, or by brazing, welding, or soldering with a fusible metal or alloy: On or about 05/04/12, and at times prior thereto, employees were exposed to an electrical/explosion hazard while working near the SCR House which was being used to store flammable paint. Inside the SCR House was an operating spark producing electrical fan which had a spliced extension cord. This splice extension cord was wrapped with black electrical tape.
Recent events (2)
- — I (S) $2400
- — Z (S) $4000
1910.1200 F05 I
- Issued
- Sep 18, 2012
- Abate by
- Oct 3, 2012
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(f)(5)(i): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the identity of the hazardous chemical(s) contained therein: On or about 05/04/12, and at times prior thereto, employees were exposed to Oil base Mud Chemicals due to the tanks not being labeled with its content.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Pioneer Drilling Company
View Pioneer Drilling Company's full OSHA safety record →
More inspections in this industry (NAICS 213111)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 334197233.