Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: CKS PACKAGING, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CKS PACKAGING, INC. in 5750 EAST FRONT STREET, KANSAS CITY, MO 64120 (NAICS 326199). OSHA activity number 334487147.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch CKS Packaging, INC. for free Get an email when a new federal OSHA severe-injury report for CKS Packaging, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
CKS PACKAGING, INC.
Site address
5750 EAST FRONT STREET
City
KANSAS CITY
State
MO
ZIP
64120
Mailing
5750 EAST FRONT STREET, KANSAS CITY, MO 64120
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
131
Ownership type
Private (A)

5 citations on file for this inspection.

1910.36 D01

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Jun 27, 2012
Penalty
Initial $4,250 · Current $0 Reduced
29 CFR 1910.36(d)(1):     Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:    (a) The exit route door in the maintenance area was locked and required special knowledge in order to open the door from the inside. Employees were exposed to fire hazards due to the exit door being locked.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4250

1910.169 B03 III

Serious Gravity 1 2 instances 1 exposed
Issued
Jun 27, 2012
Penalty
Initial $3,000 · Current $2,000 Reduced
29 CFR 1910.169(b)(3)(iii):     Safety appliances such as safety valves, indicating devices and controlling devices, were not constructed, located, and/or installed so that they could not be readily rendered inoperative by any means, including the elements:    (a) A gauge to measure air pressure on the line #3 blow molder was damaged such that the cover glass was missing and the gauge was not functioning in a reliable manner.    (b) A gauge to measure water pressure on the line #4 blow molder was damaged such that the cover glass was missing and the gauge was not functioning in a reliable manner.
Recent events (2)
  • · I (S) $2000
  • · Z (S) $3000

1910.212 A02

Deleted Serious Gravity 5 2 instances 1 exposed
Issued
Jun 27, 2012
Abate by
Jul 27, 2012
Penalty
Initial $4,000 · Current $0 Reduced
29 CFR 1910.212(a)(2):     Guard(s) on machine(s) were not affixed to the machine or secured elsewhere when attachment to the machine was not possible:    (a) Two drilling machines in the maintenance areas were not guarded in a way as to prevent employees from the caught in hazards associated with these machines. Employees use these drills for various operations and maintenance work.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4000

1910.304 G05

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 27, 2012
Abate by
Jul 27, 2012
Penalty
Initial $6,000 · Current $4,200 Reduced
29 CFR 1910.304(g)(5):     The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    (a) Employees of CKS Packaging were exposed to contact with electrical current from improper grounding of the vertical band saw machine located in the maintenance area.
Recent events (2)
  • · I (S) $4200
  • · Z (S) $6000

1910.305 G02 III

Deleted Serious Gravity 5 2 instances 2 exposed
Issued
Jun 27, 2012
Penalty
Initial $4,000 · Current $0 Reduced
29 CFR 1910.305(g)(2)(iii):     Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:    (a) Employees of CKS Packaging were exposed to contact with electrical current hazards from improper strain relief being provided to wiring of two separate pieces of equipment in the facility.
Recent events (2)
  • · I (S) $0
  • · Z (S) $4000

View CKS Packaging, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 334487147.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.