OSHA Inspection: UNITED DAIRY INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of UNITED DAIRY INC. in 300 N. FIFTH ST., MARTINS FERRY, OH 43935 (NAICS 311511). OSHA activity number 335716585.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch United Dairy INC. for free Get an email when a new federal OSHA severe-injury report for United Dairy INC. is published. One employer, no account, unsubscribe in one click.
Establishment
UNITED DAIRY INC.
Site address
300 N. FIFTH ST.
City
MARTINS FERRY
State
OH
ZIP
43935
Mailing
P.O. BOX 280, MARTINS FERRY, OH 43935
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311511
Employees
505
Ownership type
Private (A)

16 citations on file for this inspection.

1910.151 C

Serious Gravity 5 1 instance 5 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.151(c):     Where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body shall be provided within the work area for immediate emergency use.  [63 FR 33450, June 18, 1998]      a.     In the boiler room where the main operations of the plant are performed for heating,  cooling and other tasks, the employer did not have a emergency eye wash and shower in an area where the corrosive Boiler Wash was used therby exposing employees to a contact hazard.
Recent events (2)
  • · I (S) $2125
  • · Z (S) $4250

1910.178 L04 I

Serious Gravity 5 1 instance 2 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.178(l)(4)(i):     Refresher training, including an evaluation of the effectiveness of that training, shall be conducted as required by paragraph (l)(4)(ii) to ensure that the operator has the knowledge and skills needed to operate the powered industrial truck safely.      a.     In the plant where employees operated powered industrial trucks, the employer did not provide refresher training every three years thereby exposing employees to a struck-by hazard.
Recent events (2)
  • · I (S) $2125
  • · Z (S) $4250

1910.212 A02

Serious Gravity 5 4 instances 4 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.212(a)(2):     General requirements for machine guards. Guards shall be affixed to the machine where possible and secured elsewhere if for any reason attachment to the machine is not possible. The guard shall be such that it does not offer an accident hazard in itself.      a.     In the tank isle area where the milk is received for processing, the plastic guard over the shaft to the CIP Pump was not secured from being dislodged from over the pump thereby exposing employees to a struck-by hazard.    b.      In the tank isle area where the milk is received for processing, the plastic guard to the HTST No. 2  pump was not secured from being dislodged from over the pump, thereby exposing employees to a struck-by hazard.    c.       In front of the Paturized Tank Number 1, the plastic guard over the rotating shaft of the milk pump was not secured from being dislodged from over the pump thereby exposing employees to a struck-by hazard.      d.       In the case room where the hydralic pump pushes the cases through the building to be cleaned, the guard over the coupler was not secured thereby exposing employees to a struck-by hazard.
Recent events (2)
  • · I (S) $1700
  • · Z (S) $3400

1910.215 B09

Serious Gravity 5 1 instance 5 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.215(b)(9):     Exposure adjustment. Safety guards of the types described in Subparagraphs (3) and (4) of this paragraph, where the operator stands in front of the opening, shall be constructed so that the peripheral protecting member can be adjusted to the constantly decreasing diameter of the wheel. The maximum angular exposure above the horizontal plane of the wheel spindle as specified in paragraphs (b)(3) and (4) of this section shall never be exceeded, and the distance between the wheel periphery and the adjustable tongue or the end of the peripheral member at the top shall never exceed one-fourth inch. (See Figures O-18, O-19, O-20, O-21, O-22, and O-23.)       a.     In the engine room where maitenance was performed, the Black and Decker pedestal grinder had a one inch gap between the abrasive wheel and tongue guard thereby exposing employees to a struck-by hazard.
Recent events (2)
  • · I (S) $2125
  • · Z (S) $4250

1910.219 E01 I

Serious Gravity 5 1 instance 5 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.219(e)(1)(i):     Where both runs of horizontal belts are seven (7) feet or less from the floor level, the guard shall extend to at least fifteen (15) inches above the belt or to a standard height, except that where both runs of a horizontal belt are 42 inches or less from the floor, the belt shall be fully enclosed in accordance with paragraphs (m) and (o) of this section.    a.    In the regrind room where plastic bottles are ground up for recycling, at the rear of the north grinder had a belt and pulley which were located close to the floor which were not guarded at the back thereby exposing employees to a caught in hazard.
Recent events (2)
  • · I (S) $1700
  • · Z (S) $3400

1910.305 D02

Serious Gravity 5 1 instance 5 exposed
Issued
Oct 9, 2012
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.305(d)(2):     Panelboard enclosures. Panelboards shall be mounted in cabinets, cutout boxes, or enclosures designed for the purpose and shall be dead front. However, panelboards other than the dead front externally-operable type are permitted where accessible only to qualified persons.    a.    In the Trine Room where milk was processed and bottled, circuit breaker panel No. 13 had duct tape covering the energized electrical area where a circuit breaker should have been located thereby exposing employees to a contact hazard.
Recent events (2)
  • · I (S) $2125
  • · Z (S) $4250

1910.303 B06

Serious Gravity 1 1 instance 10 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $2,550 · Current $1,275 Reduced
29 CFR 1910.303(b)(6):     Deteriorating agents. Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures.    a.     Io the south wall of the pint filling area directly below the clock, the water, cleaning agents and chemicals used in the area caused the bottom of the energized 220 volt electric disconnect to rust away and the energized wires were protruding from the bottom of the disconnect thereby exposing employees to a contact hazard.
Recent events (2)
  • · I (S) $1275
  • · Z (S) $2550

1910.303 F01

Serious Gravity 1 3 instances 10 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $2,550 · Current $1,275 Reduced
29 CFR 1910.303(f)(1):     Motors and appliances. Each disconnecting means required by this subpart for motors and appliances shall be legibly marked to indicate its purpose, unless located and arranged so the purpose is evident.    a.     In the receiving area where tankers of milk come to the processing facility, at the top of the stairs going to the plant there was a energized electrical disconnect which was not marked as to the equipment it operated thereby exposing employees to a contact hazard.    b.      In the tank isle/front of the PPG, the disconnect was not marked with the equipment it operated thereby exposing employees to a contact hazard.    c.       In the Paturizing department, the disconnects were not marked with the equipment they were operating thereby exposing employees to a contact hazard.
Recent events (2)
  • · I (S) $1275
  • · Z (S) $2550

1910.305 B01 II

Serious Gravity 5 6 instances 15 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.305(b)(1)(ii):     Unused openings in cabinets, boxes, and fittings shall be effectively closed.    a.     In the gallon bottle filling area, there was a 440 volt energized electrical panel which had three circuit breakers missing from the panel thereby exposing employees to a contact hazard.    b.      In the gallon bottle filling area, there was a 440 volt energized electrical panel which had twelve missing circuit breakers from the panel thereby exposing employees to a contact hazard.    c.       On the north wall by the pint bottle filler area, there was a missing circuit breaker in the energized 220 volt electrical panel thereby exposing employees to a contact hazard.    d.       In the Trine Room, the Square D energized 220 volt electrical panel had a missing circuit breaker thereby exposing employees to a contact hazard.    e.        In the Trine Room, Panel No. 13 labeled Trine Labeler which was a 220 volt energized electrical panel had a missing circuit breaker thereby exposing employees to a contact hazard.    f.        In the regrind room, the south side of the grinder had an unused opening in the bottom of the energized 220 volt electrical junction box thereby exposing employees to a contact hazard.
Recent events (2)
  • · I (S) $2125
  • · Z (S) $4250

1910.305 B03 II

Serious Gravity 1 1 instance 5 exposed
Issued
Oct 9, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(3)(ii):     Boxes shall be closed by suitable covers securely fastened in place.  Note to paragraph (b)(3)(ii) of this section: Underground box covers that weigh over 45.4 kg (100 lbs) meet this requirement.    a.     In the regrind room, the energized electrical box on the north side of the grinder had a cover missing from the junction box thereby exposing employees to a contact hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 C04

Serious Gravity 5 1 instance 4 exposed
Issued
Oct 9, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.305(c)(4):     Faceplates for flush-mounted snap switches. Snap switches mounted in boxes shall have faceplates installed so as to completely cover the opening and seat against the finished surface.    a.     On the south end of the receiving area, there was a face plate missing on the electrical light switch used to turn the light on and off thereby exposing employees to a contact hazard.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.332 B01

Serious Gravity 5 1 instance 3 exposed
Issued
Oct 9, 2012
Abate by
Jan 30, 2013
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.332(b)(1):     Practices addressed in this standard. Employees shall be trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertain to their respective job assignments.      a.     In the plant employees who routinely performed work on or near energized parts up to 480 VAC such as testing, troubleshooting, voltage measuring, and other tasks were not provided training to understand the specific hazards associated with electrical energy and safety rerlated work practices and requirements as necessary to provide protectionfrom the electrical hazards with their respective job task.
Recent events (2)
  • · I (S) $2125
  • · Z (S) $4250

1910.333 A

Serious Gravity 5 1 instance 5 exposed
Issued
Oct 9, 2012
Abate by
Jul 30, 2013
Penalty
Initial $4,250 · Current $2,125 Reduced
29 CFR 1910.333(a):     "General." Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards.    a.     In the plant where employees routinely performed work on or near energized parts at 120 to 480 VAC such as, testing, troubleshooting, and voltage measuring, and other tasks, a flash hazard analasis was not performed to determine the proper protection required nor was a flash protection boundry established to protect employees from shock, arc flash or aec blast  thereby exposing employees to a contact hazard.      ABATEMENT NOTE:  One method of abatement amoung others, includes conducting a flash hazard analysis in compliance with NFPA 70E Standard for Electrical Safety in the Workplace (2004 Edition) Article 130.39 (or its equivilant), to determine the Flash Protection Boundry and the use of electric protective equipment necessary for the specific related hazards of the task being completed.
Recent events (2)
  • · I (S) $2125
  • · Z (S) $4250

1910.335 A01 II

Serious Gravity 5 1 instance 4 exposed
Issued
Oct 9, 2012
Abate by
Jul 30, 2013
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.335(a)(1)(ii):     Protective equipment shall be maintained in a safe, reliable condition and shall be periodically inspected or tested, as required by 1910.137.    a.     In the plant where employees worked on energized electrical equipment when troubleshooting machines, the personal protective equipment such as, but not limited to electrical gloves were not tested for energized equipment protection thereby exposing employees to a contact hazard.
Recent events (2)
  • · I (S) $1700
  • · Z (S) $3400

1910.147 C06

Other-than-serious 1 instance 5 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6):     Periodic inspection.    a.     In the plant the employer did not perform a periodic inspection of the energy control program to identify defencies or other issues where retraining would be needed thereby exposing employees to a contact hazard.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.335 B01

Other-than-serious 1 instance 50 exposed
Issued
Oct 9, 2012
Abate by
Nov 8, 2012
Penalty
Initial $0 · Current $0
29 CFR 1910.335(b)(1):     Safety signs and tags. Safety signs, safety symbols, or accident prevention tags shall be used where necessary to warn employees about electrical hazards which may endanger them, as required by 1910.145.      a.     In the plant, the service panels throughout the plant for lights and receptacles were not marked to warn employees of the potential  arc flash hazards.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

View United Dairy INC.'s full OSHA safety record →