SAIPAN, MP —
OSHA Inspection: YANTZE CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of YANTZE CORPORATION in RENOVATION OF RESTUARANT INTO OFFICES PALM ST. AND PLUMERA ST., VILLAGE OF GARAPAN, SAIPAN, MP 96950 (NAICS 236220). OSHA activity number 338819436.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- YANTZE CORPORATION
- Site address
- RENOVATION OF RESTUARANT INTO OFFICES PALM ST. AND PLUMERA ST., VILLAGE OF GARAPAN
- City
- SAIPAN
- State
- MP
- ZIP
- 96950
- Mailing
- PO BOX 503018 CHALAN KANOA, SAIPAN, MP 96950
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 9
- Ownership type
- A
Citations
6 citations on file for this inspection.
1926.403 B02
- Issued
- Apr 19, 2013
- Abate by
- Apr 29, 2013
- Penalty
- Initial $1,020 · Current $1,020
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: (a) Inside the building near the east side on or about February 13, 2013, a 2 by 4 inch electrical box was not used as designed as it lay on the floor instead of being secured on a surface. The boxes contained a 110 VAC electrical outlet that supplied power to 220 VAC portable power tools.
Recent events (1)
- — Z (S) $1020
1926.403 I02 I
- Issued
- Apr 19, 2013
- Abate by
- Apr 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(i)(2)(i): Except as required or permitted elsewhere in this subpart, live parts of electric equipment operating at 50 volts or more was not guarded against accidental contact by cabinets or other forms of enclosures, or by any of the following means: (a) Inside the building near the rear east wall on or about February 13, 2013, there was no cover on a 220 VAC panel box. The box was 13 inches wide by 31.5 inches high, and the bottom was 58 inches from the floor. The box supplied power to portable power tools.
Recent events (1)
- — Z (S) $0
1926.405 A02 II B
- Issued
- Apr 19, 2013
- Abate by
- Apr 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(B): All conductors were not protected by overcurrent devices at their ampacity. Runs of open conductors were not located where the conductors will not be subject to physical damage, and the conductors were not fastened at intervals not exceeding 10 feet (3.05 m): (a) Inside the building in an electric panel box near the rear east wall on or about February 13, 2013, number 14 wire, inside non-metallic sheathed cable, was attached to 40 amp, 220 VAC circuit breakers. The wire size must be at least number 10. (b) Inside the building near an electric panel box near the rear east wall on or about February 13, 2013, non-metallic sheathed cable, lay on the floor. The cable supplied power to an outlet in a metal box on the floor.
Recent events (1)
- — Z (S) $0
1926.405 B01
- Issued
- Apr 19, 2013
- Abate by
- Apr 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors entered were not effectively closed. Unused openings in cabinets, boxes, and fittings were not also effectively closed: (a) Inside the building near an electric panel box near the rear east wall on or about February 13, 2013, a 2 by 4 inch electrical box had a half inch diameter that was not closed. The box contained a 110 VAC electrical outlet that supplied power to 220 VAC portable power tools.
Recent events (1)
- — Z (S) $0
1926.405 B02
- Issued
- Apr 19, 2013
- Abate by
- Apr 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings were not provided with covers. When metal covers are used, they were not grounded. In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass were not provided with bushings designed for the purpose or they did not have smooth, well-rounded surfaces on which the cords may bear: (a) Inside the building near an electric panel box near the rear east wall on or about February 13, 2013, there was no cover plate on the 110 VAC outlet located in a handy box that lay on the floor. The box contained a 110 VAC electrical outlet that supplied power to 220 VAC portable power tools.
Recent events (1)
- — Z (S) $0
1926.405 J02 I
- Issued
- Apr 19, 2013
- Abate by
- Apr 29, 2013
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(j)(2)(i): Receptacles connected to circuits having different voltages, frequencies, or types of current (ac or dc) on the same premises were not of such design that the attachment plugs used on these circuits were not interchangeable: (a) Inside the building near the east side on or about February 13, 2013, outlets, designed for 110 VAC and 110 VAC plugs, were used to power a 220 VAC Bosch GBH 2-20 SRE hammer drill.
Recent events (1)
- — Z (S) $0
More inspections at Yantze Corporation
View Yantze Corporation's full OSHA safety record →
More inspections in this industry (NAICS 236220)
More inspections in MP
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338819436.