Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: YANTZE CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of YANTZE CORPORATION in RENOVATION OF RESTUARANT INTO OFFICES PALM ST. AND PLUMERA ST., VILLAGE OF GARAPAN, SAIPAN, MP 96950 (NAICS 236220). OSHA activity number 338819436.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Yantze Corporation — free Get an email when a new federal OSHA severe-injury report for Yantze Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
YANTZE CORPORATION
Site address
RENOVATION OF RESTUARANT INTO OFFICES PALM ST. AND PLUMERA ST., VILLAGE OF GARAPAN
City
SAIPAN
State
MP
ZIP
96950
Mailing
PO BOX 503018 CHALAN KANOA, SAIPAN, MP 96950
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
9
Ownership type
A

6 citations on file for this inspection.

1926.403 B02

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 19, 2013
Abate by
Apr 29, 2013
Penalty
Initial $1,020 · Current $1,020
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    (a) Inside the building near the east side on or about February 13, 2013, a 2 by 4 inch electrical box was not used as designed as it lay on the floor instead of being secured on a surface.  The boxes contained a 110 VAC electrical outlet that supplied power to 220 VAC portable power tools.
Recent events (1)
  • — Z (S) $1020

1926.403 I02 I

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 19, 2013
Abate by
Apr 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.403(i)(2)(i): Except as required or permitted elsewhere in this subpart, live parts of electric equipment operating at 50 volts or more was not guarded against accidental contact by cabinets or other forms of enclosures, or by any of the following means:    (a) Inside the building near the rear east wall on or about February 13, 2013, there was no cover on a 220 VAC panel box.  The box was 13 inches wide by 31.5 inches high, and the bottom was 58 inches from the floor.  The box supplied power to portable power tools.
Recent events (1)
  • — Z (S) $0

1926.405 A02 II B

Serious Gravity 1 2 instances 3 exposed
Issued
Apr 19, 2013
Abate by
Apr 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(B): All conductors were not protected by overcurrent devices at their ampacity.  Runs of open conductors were not located where the conductors will not be subject to physical damage, and the conductors were not  fastened at intervals not exceeding 10 feet (3.05 m):  (a) Inside the building in an electric panel box near the rear east wall on or about February 13, 2013, number 14 wire, inside non-metallic sheathed cable, was attached to 40 amp, 220 VAC circuit breakers.  The wire size must be at least number 10.  (b) Inside the building near an electric panel box near the rear east wall on or about February 13, 2013, non-metallic sheathed cable, lay on the floor.  The cable supplied power to an outlet in a metal box on the floor.
Recent events (1)
  • — Z (S) $0

1926.405 B01

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 19, 2013
Abate by
Apr 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors entered were not effectively closed.  Unused openings in cabinets, boxes, and fittings were not also effectively closed:    (a) Inside the building near an electric panel box near the rear east wall on or about February 13, 2013, a 2 by 4 inch electrical box had a half inch diameter that was not closed.  The box contained a 110 VAC electrical outlet that supplied power to 220 VAC portable power tools.
Recent events (1)
  • — Z (S) $0

1926.405 B02

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 19, 2013
Abate by
Apr 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings were not provided with covers. When metal covers are used, they were not grounded. In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass were not provided with bushings designed for the purpose or they did not have smooth, well-rounded surfaces on which the cords may bear:    (a) Inside the building near an electric panel box near the rear east wall on or about February 13, 2013, there was no cover plate on the 110 VAC outlet located in a handy box that lay on the floor.  The box contained a 110 VAC electrical outlet that supplied power to 220 VAC portable power tools.
Recent events (1)
  • — Z (S) $0

1926.405 J02 I

Serious Gravity 1 1 instance 3 exposed
Issued
Apr 19, 2013
Abate by
Apr 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.405(j)(2)(i): Receptacles connected to circuits having different voltages, frequencies, or types of current (ac or dc) on the same premises were not of such design that the attachment plugs used on these circuits were not interchangeable:     (a)  Inside the building near the east side on or about February 13, 2013, outlets, designed for 110 VAC and 110 VAC plugs, were used to power a 220 VAC Bosch GBH 2-20 SRE hammer drill.
Recent events (1)
  • — Z (S) $0

View Yantze Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 338819436.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.