SAIPAN, MP —
OSHA Inspection: YANTZE CORPORATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of YANTZE CORPORATION in HEAVEN II WIRELESS AREA, SAIPAN, MP 96950 (NAICS 236220). OSHA activity number 343250908.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- YANTZE CORPORATION
- Site address
- HEAVEN II WIRELESS AREA
- City
- SAIPAN
- State
- MP
- ZIP
- 96950
- Mailing
- P.O. BOX 500783, SAIPAN, MP 96950
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 27
- Ownership type
- A
Citations
4 citations on file for this inspection.
1926.403 B02
- Issued
- Sep 20, 2018
- Penalty
- Initial $3,298 · Current $3,298
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: Temporary power area: Metal receptacle boxes designed to be installed inside of a wall were used on the end of an extension cord powering a Bosch portable hammer drill and battery chargers. Employees were exposed to fire and electrical hazards.
Recent events (1)
- — Z (S) $3298
1926.404 B01 I
- Issued
- Sep 20, 2018
- Penalty
- Initial $3,298 · Current $3,298
General-duty citation text
29 CFR 1926.404(b)(1)(i): Employer did not use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section, or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites: Temporary power area: A yellow extension cord that supplied power to a Bosch portable hammer drill that was not protected with a ground fault circuit interrupter. Employees were exposed to electrical hazards.
Recent events (1)
- — Z (S) $3298
1926.405 B02
- Issued
- Sep 20, 2018
- Penalty
- Initial $3,298 · Current $3,298
General-duty citation text
29 CFR 1926.405(b)(2): In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy: Temporary power area: A metal junction box used to power a Bosch portable hammer drill and battery chargers was missing the faceplate. Employees were exposed to fire and electrical hazards.
Recent events (1)
- — Z (S) $3298
1926.405 D
- Issued
- Sep 20, 2018
- Penalty
- Initial $4,398 · Current $4,398
General-duty citation text
29 CFR 1926.405(d): A panelboard was not dead front. Temporary power area: The 150 amp panelboard was missing its dead front cover. Employees were exposed to arc flash and electrical hazards.
Recent events (1)
- — Z (S) $4398
More inspections at Yantze Corporation