OSHA Inspection: JAY CORPORATION

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of JAY CORPORATION in RENOVATION OF RETAIL SPACE INTO WATABE WEDDING SALON TUMON SANDS PLAZA, PALE SAN VITORES ROAD, TAMUNING, GU 96913 (NAICS 238110). OSHA activity number 338915549.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch JAY Corporation — free Get an email when a new federal OSHA severe-injury report for JAY Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
JAY CORPORATION
Site address
RENOVATION OF RETAIL SPACE INTO WATABE WEDDING SALON TUMON SANDS PLAZA, PALE SAN VITORES ROAD
City
TAMUNING
State
GU
ZIP
96913
Mailing
PO BOX 9345, TAMUNING, GU 96931
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238110
Employees
9
Ownership type
A

2 citations on file for this inspection.

1926.417 B

Serious Gravity 1 1 instance 4 exposed
Issued
May 22, 2013
Abate by
May 31, 2013
Penalty
Initial $1,020 · Current $1,020
29 CFR 1926.417(b): Equipment or circuits that were deenergized were not rendered inoperative and did not have tags attached at all points where such equipment or circuits can be energized:  (a) In the storage area electrical panel on or about February 21, 2013, and at times prior thereto, several 110 VAC circuit breakers, labeled for lights, were in the off position, but they were not rendered inoperable by removing the wires from the breakers, and they did not have tags.  Some flexible cords hung from the ceilings with bare wires exposed about four feet from the floor.  The wires in the electrical box and outlet, located in a demolished concrete wall, were energized.  The walls were demolished with electric jack hammers.
Recent events (1)
  • — Z (S) $1020

1926.850 C

Serious Gravity 1 1 instance 4 exposed
Issued
May 22, 2013
Abate by
May 29, 2013
Penalty
Initial $0 · Current $0
29 CFR 1926.850(c): All electric, gas, water, steam, sewer, and other service lines were not shut off, capped, or otherwise controlled, outside the building line before demolition work was started:   (a) In the storage area electrical panel on or about February 21, 2013, and at times prior thereto, several 110 VAC circuit breakers, labeled for lights, were in the off position, but they were not rendered inoperable by removing the wires from the breakers, and they did not have tags.  Some flexible cords hung from the ceilings with bare wires exposed about four feet from the floor.  The wires in the electrical box and outlet, located in a demolished concrete wall, were energized.  The walls were demolished with electric jack hammers.