Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ALASKA WEST EXPRESS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ALASKA WEST EXPRESS, INC. in 1 OCEAN DOCK ROAD WHITTIER TERMINAL, WHITTIER, AK 99693 (NAICS 488320). OSHA activity number 339035420.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Alaska West Express, INC. — free Get an email when a new federal OSHA severe-injury report for Alaska West Express, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1 OCEAN DOCK ROAD WHITTIER TERMINAL
City
WHITTIER
State
AK
ZIP
99693
Mailing
1048 WHITNEY ROAD, ANCHORAGE, AK 99501
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488320
Employees
10
Ownership type
A

4 citations on file for this inspection.

1910.303 E01 II

Serious Gravity 5 1 instance 1 exposed
Issued
May 10, 2013
Abate by
Jun 10, 2013
Penalty
Initial $2,380 · Current $1,428 Reduced
29 CFR 1910.303(e)(1)(ii): Electrical equipment was used when the markings giving voltage, current, wattage, or other ratings as necessary were missing.   Back-up Generator Room; on or about 01 May 2013 and times prior thereto, a 480 volt electrical panel was not marked indicating the voltage, current, wattage or other ratings. This condition exposed employees to an electrical shock and electrical burn hazards.
Recent events (2)
  • — I (S) $1428
  • — Z (S) $2380

1910.304 F01 IV

Serious Gravity 5 1 instance 10 exposed
Issued
May 10, 2013
Abate by
Jun 10, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel.  Whittier Port Facility; on or about 01 May 2013 and times prior thereto, the employer did not ensure that the electrical panel was readily accessible in the event of an electrical emergency. Area in front of the panel was used to store equipment impeding access to the circuit breaker panel. This condition exposed employees to an electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
May 10, 2013
Abate by
Jun 10, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  Back-up Generator Room; on or about 01 May 2013 and times prior thereto, the employer did not ensure that the electrical panel was effectively closed. A knockout plug was missing on the left side of the 480 volt electrical panel. This condition exposed employees to a electrical shock and electrical burn hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 1 2 instances 10 exposed
Issued
May 10, 2013
Abate by
Jun 10, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws.   (a)    Mechanics Room; on or about 01 May 2013 and times prior thereto; strain relief was not provided on a 50-foot blue extension cord. Cord type unknown. This condition exposed employees to an electrical shock hazard.   (b)   Reefer Container; on or about 01 May 2013 and times prior thereto; strain relief was not provided on a 480 volt power cord.  Cord type unknown. This condition exposed employees to an electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Alaska West Express, INC.'s full OSHA safety record →