Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,194,531Inspections Most recent open 2026-08-11 Last loaded 2026-08-14

OSHA Inspection: AMERICAN TINNING & GALVANIZING COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AMERICAN TINNING & GALVANIZING COMPANY in 552 WEST 12TH STREET, ERIE, PA 16501 (NAICS 332813). OSHA activity number 339106825.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch American Tinning & Galvanizing Company for free Get an email when a new federal OSHA severe-injury report for American Tinning & Galvanizing Company is published. One employer, no account, unsubscribe in one click.
Site address
552 WEST 12TH STREET
City
ERIE
State
PA
ZIP
16501
Mailing
552 WEST 12TH STREET, ERIE, PA 16501
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332813
Employees
73
Ownership type
Private (A)

11 citations on file for this inspection.

1910.147 E03

Serious Gravity 5 2 instances 2 exposed
Issued
Dec 5, 2013
Abate by
Jan 2, 2014
Penalty
Initial $2,800 · Current $1,500 Reduced
29 CFR 1910.147(e)(3): Lockout or tagout devices removal. Each lockout or tagout device shall be removed from each energy isolating device by the employee who applied the device:       a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 7, 2013, lockout devices (i.e. locks) were capable of being removed under normal conditions by personnel who did not apply the lockout device. Maintenance employees were utilizing locks that were keyed alike for the control of hazardous energy.
Recent events (2)
  • · I (S) $1500
  • · Z (S) $2800

1910.215 B09

Serious Gravity 5 2 instances 4 exposed
Issued
Dec 5, 2013
Penalty
Initial $2,380 · Current $1,500 Reduced
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:     a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 11, 2013 the Dayton Grinder, model 1Z707 in the maintenance area had a tongue guard that was approximately 9/16 inch from the wheel.
Recent events (2)
  • · I (S) $1500
  • · Z (S) $2380

1910.215 A04

Serious Gravity 5 1 instance 4 exposed
Issued
Dec 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:  a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 11, 2013 the grinder in the plastic fabrication room was measured at approximately ¼ inch from the grinding wheel.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.242 B

Serious Gravity 5 3 instances 8 exposed
Issued
Dec 5, 2013
Penalty
Initial $2,380 · Current $1,500 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:    a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 11, 2013 a compressed air nozzle in the zinc and cadmium area was tested at levels around 100 psi.
Recent events (2)
  • · I (S) $1500
  • · Z (S) $2380

1910.303 B01

Serious Gravity 5 1 instance 4 exposed
Issued
Dec 5, 2013
Abate by
Jan 2, 2014
Penalty
Initial $2,800 · Current $1,500 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards likely to cause death or serious physical harm:    a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 11, 2013 in the aluminum anodizing area in the South West corner of dip room 2 the control for the 500 pound hoist had exposed wires. The outer jacket of the cable going into the electrical box came down and exposed the wires underneath.
Recent events (2)
  • · I (S) $1500
  • · Z (S) $2800

1910.334 A02 II

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
Dec 5, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service:  a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 11, 2013 an industrial Dayton fan in the plastic fabrication area had exposed wires at the power switch on the fan.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.303 B07 IV

Serious Gravity 5 1 instance 16 exposed
Issued
Dec 5, 2013
Abate by
Jan 2, 2014
Penalty
Initial $3,500 · Current $0 Reduced
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, or cut:    a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 11, 2013 the drinking fountain located by the office/lab in the zinc and cadmium electroplating area was missing a corner large enough that a hand could inadvertently go into electrical wires in the drinking fountain.
Recent events (2)
  • · I (S) $0
  • · Z (S) $3500

1910.305 B01 I

Deleted Serious Gravity 5 2 instances 10 exposed
Issued
Dec 5, 2013
Abate by
Jan 2, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:   a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA --- at the rear of the zinc & cadmium electroplating area: On or about June 11, 2013 there were two electrical boxes controlling an Electro lift 1/4 ton hoist with a serial number of 200172. The openings in the electrical boxes for the conductors were not closed. The edges around the openings provided abrasion hazards to the conductors.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.132 D02

Deleted Other-than-serious 1 instance 73 exposed
Issued
Dec 5, 2013
Abate by
Jan 2, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(2): The employer did not verify, through a written certification, the identity of the workplace evaluated, the person certifying that the evaluation had been performed, and the date the hazard assessment was done:   a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 7, 2013 the company did not have a written and certified hazard assessment of the facility.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.147 C06 II

Other-than-serious 1 instance 2 exposed
Issued
Dec 5, 2013
Abate by
Jan 2, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed:  a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 7, 2013 the company did not document or certify periodic annual inspections of the energy control procedures were completed.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

1910.151 C

Other-than-serious 1 instance 12 exposed
Issued
Dec 5, 2013
Abate by
Jan 2, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:  a) American Tinning & Galvanizing Company / 552 West 12th Street, Erie, PA: On or about June 7, 2013 company employees were working around various chemicals used in the metal plating process. An emergency eyewash station in the vicinity of the aluminum anodizing area was not in compliance with ANSI 358.1-1998 for Emergency Eyewash and Shower Equipment in that the eyewash station was not activated weekly to verify proper operations. Weekly inspections of the equipment were not conducted.