Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: US DEPARTMENT OF AGRICULTURE SIX RIVERS NATIONAL FOREST

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of US DEPARTMENT OF AGRICULTURE SIX RIVERS NATIONAL FOREST in MAD RIVER HOT SHOT WORK CENTER, SIX RIVERS NATIONAL FOREST, EUREKA, CA 95501 (NAICS 924120). OSHA activity number 339183212.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch US Department of Agriculture SIX Rivers National Forest for free Get an email when a new federal OSHA severe-injury report for US Department of Agriculture SIX Rivers National Forest is published. One employer, no account, unsubscribe in one click.
Site address
MAD RIVER HOT SHOT WORK CENTER, SIX RIVERS NATIONAL FOREST
City
EUREKA
State
CA
ZIP
95501
Mailing
1330 BAYSHORE WAY, EUREKA, CA 95501
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
50
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.22 A01

Serious Gravity 5 1 instance 24 exposed
Issued
Nov 13, 2013
Abate by
Dec 3, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition:   Six Rivers National Forest, Hot Shots Mad River Compound Work Center: On July 28, 2013, and at times prior thereto, housekeeping in the storage and workshop area was not maintained.  Clutter, equipment and materials were not kept in an orderly condition exposing workers to fire and other emergencies requiring safe egress from the facility.  Employees were also exposed to slips, trips and falls.
Recent events (1)
  • · Z (S) $0

1910.37 B02

Serious Gravity 5 1 instance 12 exposed
Issued
Nov 13, 2013
Abate by
Nov 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   Six Rivers National Forest, Hot Shots Mad River Compound Work Center: On July 28, 2013, and at times prior thereto, the exit door throughout the facility were not clearly marked with an Exit sign.  Employees were exposed to injuries including smoke inhalation and burns in the event of a fire and other emergencies requiring safe egress.
Recent events (1)
  • · Z (S) $0

1910.157 C01

Serious Gravity 5 3 instances 12 exposed
Issued
Nov 13, 2013
Abate by
Nov 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):  Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:    Six Rivers National Forest, Hot Shots Mad River Compound Work Center: On July 28, 2013, and at times prior thereto, portable fire extinguishers in the facility were not properly mounted and not readily accessible. A lack of readily accessible extinguishers in emergencies that require a fire to be controlled or extinguished exposed workers to serious fire related injuries including smoke inhalation and burns.
Recent events (1)
  • · Z (S) $0

1910.303 F02

Serious Gravity 1 1 instance 24 exposed
Issued
Nov 13, 2013
Abate by
Nov 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2):  Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    Six Rivers National Forest, Hot Shots Mad River Compound Work Center: On July 28, 2013, and at times prior thereto,   branch circuits on the facility's main breaker panel was not marked to indicate its purpose or location. Employees were exposed to electrical and mechanical hazards during emergencies and other situations requiring the shut off of the correct circuits and/or equipment.  Inaccurate labeling of circuit breakers in the electrical cabinet hinder and delay an employees' ability to identify and shut down the appropriate circuit breakers during an electrical or equipment emergency.  Delays in shutting down electrical equipment increase the potential for serious injuries to employees during an emergency.
Recent events (1)
  • · Z (S) $0

1910.303 G01

Serious Gravity 5 1 instance 12 exposed
Issued
Nov 13, 2013
Abate by
Nov 20, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment:  Six Rivers National Forest, Hot Shots Mad River Compound Work Center: On July 28, 2013, and at times prior thereto,  the work space around the work center compound's main electrical switches was not readily accessible to employees due to the storage of materials in front and around the equipment.  This condition hinders and delays an employees' ability to access and shut down the appropriate electrical circuits during an electrical or equipment emergency.  Delays in shutting down electrical equipment increase the potential for serious injuries to employees during an emergency.
Recent events (1)
  • · Z (S) $0

1910.304 G05

Serious Gravity 1 1 instance 12 exposed
Issued
Nov 13, 2013
Abate by
Nov 25, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective.  Six Rivers National Forest, Hot Shots Mad River Compound Work Center: On July 28, 2013, and at times prior thereto, the electrical wall outlet near the entrance to the main work center compound's building had a faulty ground. Employees were exposed to accidental electrical shock hazards when connecting equipment, cords and extension strips.
Recent events (1)
  • · Z (S) $0

1910.303 G02 I

Serious Gravity 10 1 instance 12 exposed
Issued
Oct 4, 2013
Abate by
Oct 15, 2013
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i):     Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    a)    Six Rivers National Forest, Hot Shots Mad River Compound Work Center: On July 28, 2013, and at times prior thereto, the main electrical power panel had an open breaker exposing the energized conductors.   Employees were exposed to the hazard of electric shock while performing maintenance and other electrical work on and around the electrical panel.
Recent events (1)
  • · Z (S) $0

View US Department of Agriculture SIX Rivers National Forest's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339183212.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.