ATLANTA, GA —
OSHA Inspection: AMERICAN AIR FILTER COMPANY, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of AMERICAN AIR FILTER COMPANY, INC. in 2624 WEAVER WAY, ATLANTA, GA 30340 (NAICS 333411). OSHA activity number 339316234.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- AMERICAN AIR FILTER COMPANY, INC.
- Site address
- 2624 WEAVER WAY
- City
- ATLANTA
- State
- GA
- ZIP
- 30340
- Mailing
- 2624 WEAVER WAY, ATLANTA, GA 30340
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 333411
- Employees
- 168
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.147 F03 II D
- Issued
- Jan 21, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $5,500 · Current $3,300 Reduced
General-duty citation text
29 CFR 1910.147(f)(3)(ii)(D): Each authorized employee did not affix a personal lockout or tagout device to the group lockout device before working on the machine or equipment: On or about 8/4/2013 at 2624 Weaver Way Atlanta, GA; a temporary employee was exposed to struck-by and caught-in hazards where the employer applied a lock to the machine for the temporary employee to clean. The temporary employee was not provided his own lock.
Recent events (2)
- — I (S) $3300
- — Z (S) $5500
1910.147 C07 I
- Issued
- Jan 21, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that employees acquired the knowledge and skills required for the safe application, usage and removal of energy control devices: On or about 8/4/2013 at 2624 Weaver Way Atlanta, GA; employees were exposed to struck-by and caught-in hazards where the employer failed to provide training to temporary employees performing cleaning operations of machinery.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.212 A01
- Issued
- Jan 21, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $5,500 · Current $3,300 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by struck-by and caught-in hazards: On or about 8/16/2013 at 2624 Weaver Way Atlanta, GA; employees were performing scraping operations at the M6 line to remove glue while the machine was in operation exposing the employees to struck-by and caught-in hazards.
Recent events (2)
- — I (S) $3300
- — Z (S) $5500
1910.305 B01 I
- Issued
- Jan 21, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $3,300 · Current $1,980 Reduced
General-duty citation text
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: On or about 08/16/2013 at 2624 Weaver Way Atlanta, GA; employees working at the M6, high volume line were exposed to electrical shock and burn hazards where the 240V electrical cable at panel 7 ckt 2-4-6 for the M6 conveyor system was not properly protected against abrasions with a collar or similar protective device.
Recent events (2)
- — I (S) $1980
- — Z (S) $3300
1910.305 B02 I
- Issued
- Jan 21, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $3,740 · Current $2,250 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: On or about 08/16/2013 at 2624 Weaver Way Atlanta, GA; employees working at the M6, high volume strip feeder were exposed to electrical shock and burn hazards where the 115/230 V Dayton motor wiring was not isolated to keep employees from making contact with the wiring that was sticking out of an open box.
Recent events (2)
- — I (S) $2250
- — Z (S) $3740
1910.305 G02 III
- Issued
- Jan 21, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $7,000 · Current $4,200 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about 08/16/2013 at 2624 Weaver Way Atlanta, GA; employees working at the M6, high volume line were exposed to electrical shock and burn hazards where electrical wiring was not protected with a strain relief device at: a. The 300V, electrical wiring for the strip feeder, b. The 115V, electrical wiring for the M6 speed control box at the AP and in-feed conveyor, and c. The 115V, electrical wiring for the M6 speed control box at the conveyor.
Recent events (2)
- — I (S) $4200
- — Z (S) $7000
1910.303 B02
- Issued
- Jan 21, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $38,500 · Current $23,470 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about 08/16/2013 at 2624 Weaver Way Atlanta, GA; employees working at the M6, high volume line were exposed to electrical shock and burn hazards where: a. the 120V metallic quad-receptacle at the in-feed conveyor to case packager was used as a pendant powering the Dayton model 1UM36 floor fan, the take-away conveyor from APM, in-feed conveyor, and the 120 V plastic dual receptacle (Reverse wired) b. the 120V plastic duplex receptacle that was powered by reverse wiring and by daisy chain from the metallic quad receptacle was used to power the in-feed conveyor and Dayton hard mounted fan. c. a 120 V plastic duplex electrical box was used to power by daisy chain a 120 V metallic duplex box that was used to power a pump and to power via daisy chain a 120 V metallic duplex box that was used to power a 90 V Direct Current motor and a glue gun. American Air Filter Corporation, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.303(b)(2), which was contained in OSHA inspection number 312524432, citation number 01, item number 008a and was affirmed as a final order on 04/10/2009, with respect to a workplace located at 2624 Weaver Way Atlanta, GA.
Recent events (2)
- — I (R) $23470
- — Z (R) $38500
1910.305 B01 II
- Issued
- Jan 21, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $500 · Current $500
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: On or about 08/16/2013 at 2624 Weaver Way Atlanta, GA; employees working at the M6, high volume line were exposed to electrical shock and burn hazards where: a. A 120 V metallic, electrical box with missing knockouts and cover not effectively closed was located in the immediate work area of the employees working at the M6 line conveyor and strip feeder; b. A 120 V power switch for the fan was not closed at the electrical line of the M6 line; c. A 120 V power box cover at the M6 line was not effectively closed; American Air Filter Corporation, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.305(b)(1)(ii), which was contained in OSHA inspection number 312524432, citation number 01, item number 008c and was affirmed as a final order on 04/10/2009, with respect to a workplace located at 2624 Weaver Way Atlanta, GA.
Recent events (2)
- — I (R) $500
- — Z (R) $500
1910.147 C06 I
- Issued
- Jan 21, 2014
- Abate by
- Mar 10, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: On or about 8/16/2013 at 2624 Weaver Way Atlanta, GA; the employer failed to provide annual audits of lockout/tagout specific procedures that were developed in January of 2009 for equipment including but not limited to the M6 high speed line.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at American AIR Filter Company, INC.
View American AIR Filter Company, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 333411)
More inspections in GA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339316234.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.