Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SABIN METAL CORPORATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SABIN METAL CORPORATION in 1647 WHEATLAND CENTER ROAD, SCOTTSVILLE, NY 14546 (NAICS 331419). OSHA activity number 339515512.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sabin Metal Corporation — free Get an email when a new federal OSHA severe-injury report for Sabin Metal Corporation is published. One employer, no account, unsubscribe in one click.
Site address
1647 WHEATLAND CENTER ROAD
City
SCOTTSVILLE
State
NY
ZIP
14546
Mailing
1647 WHEATLAND CENTER ROAD, SCOTTSVILLE, NY 14546
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331419
Employees
143
Ownership type
A

6 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 2 instances 12 exposed
Issued
Feb 13, 2014
Abate by
Mar 16, 2014
Penalty
Initial $5,000 · Current $3,500 Reduced
OSH ACT of 1970 Section (5)(a)(1): Section 5(a)(1) of the Occupational Safety and Health Act of 1970:  The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing for likely to cause death or serious physical harm to employees in that employees were exposed to being struck by damaged or ruptured steam piping;     a) On or about 1/13/13 in the High Purity area; employees who use steam jacketed kettles, were exposed to being struck by damaged or ruptured steam piping when the steam relief valves ( Kunkle 6010EDM01-AM-0800) on each of the thirty six steam jacket kettles were not inspected on an annual basis.        b) On or about 1/13/13 in the High Grade Processing area; employees use steam jacketed kettles, were exposed to being struck by damaged or ruptured steam piping when the steam relief valves ( Kunkle 6010EDM01-AM-0800 ) on each of the eight steam jacketed kettles were not inspected and an annual basis.      Abatement Documentation Required
Recent events (2)
  • — I (S) $3500
  • — Z (S) $5000

1910.107 B05 IV

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 13, 2014
Abate by
Sep 16, 2014
Penalty
Initial $4,000 · Current $2,800 Reduced
29 CFR 1910.107(b)(5)(iv): Space within the spray booth on the downstream and upstream sides of filters were not protected with approved automatic sprinklers:    a) On or about 12/13/13 in the Garage area; the totally enclosed spray booth, where Class IB flammables, such as but not limited to, Epoxy Primer Catalyst - Code DP 401LF, Premium Coating Enamel FPC, Black - Code PCC135B, Crossfire Plus Reducer - Code CR733, are sprayed, was not protected with a fire protection system exposing employees to contact with a flash fire hazard.       Abatement Certification Required
Recent events (2)
  • — I (S) $2800
  • — Z (S) $4000

1910.107 B10

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 13, 2014
Abate by
Mar 16, 2014
Penalty
Initial $4,000 · Current $2,800 Reduced
29 CFR 1910.107(b)(10): 29 CFR 1910.107(b)(10):  Illumination panels did not effectively isolate the spraying area from the area in which the lighting unit is located.     a) On or about 12/13/13 in the Garage area; located on the southwest wall inside the totally enclosed spray booth, where Class IB flammables, such as but not limited to, Epoxy Primer Catalyst - Code DP 401LF, Premium Coating Enamel FPC, Black - Code PCC135B, Crossfire Plus Reducer - Code CR733, are sprayed, one of the glass lighting panels was cracked exposing employees to contact with a flash fire hazard.       Abatement Certification Required
Recent events (2)
  • — I (S) $2800
  • — Z (S) $4000

1910.147 C06 I B

Other-than-serious 1 instance 12 exposed
Issued
Feb 13, 2014
Abate by
Mar 16, 2014
Penalty
Initial $4,000 · Current $0 Reduced
29 CFR 1910.147(c)(6)(i)(B): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirements of this standard are being followed:     a) On or about 01/28/14 throughout the plant; employees, conducting service and maintenance work were exposed to caught between or struck by hazards when the employer did not conduct periodic inspections of the Lockout Specific procedures, such as but not limited to, Harsell #1 fan, Cleaver Brooks Boiler, Furnaces C&D in calendar year 2013.       Abatement Certification Required
Recent events (2)
  • — I (O) $0
  • — Z (S) $4000

1910.305 B02 I

Serious Gravity 5 2 instances 6 exposed
Issued
Feb 13, 2014
Penalty
Initial $4,000 · Current $2,800 Reduced
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:     a) On or about 12/10/13 in Building 5, Water Recovery Department of the High Grade Process; employees were exposed to contact with electrical current ( 120 volts AC ) when the electrical outlets located between Mix Tank 1 and 2 and Mix Tank 2 and 3 were missing covers.       No Abatement Certification Required
Recent events (2)
  • — I (S) $2800
  • — Z (S) $4000

1910.107 B08

Other-than-serious 1 instance 3 exposed
Issued
Feb 13, 2014
Abate by
Sep 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.107(b)(8): Each spray booths was not separated from other operations by not less than 3 feet, or by a greater distance, or by such partition or wall as to reduce the danger from juxtaposition of hazardous operations.    a) On or about 12/13/13 in the Garage area; located on either outside wall of the totally enclosed spray booth, where Class IB flammables such as but not limited to Epoxy Primer Catalyst - Code DP 401LF, Premium Coating Enamel FPC, Black - Code PCC135B, Crossfire Plus Reducer - Code CR733 are sprayed, were three flammable storage cabinets used to store these flammables, a pallet of small cardboard boxes, a large cardboard box leaning against one of the glass lighting panels and other discarded equipment and supplies, exposing employees to a flash fire hazard.       Abatement Certification Required
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Sabin Metal Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339515512.