UNIONTOWN, PA —
OSHA Inspection: UNITED DAIRY, INC.
Planned inspection · Health discipline
At a glance
On , OSHA opened a planned health inspection of UNITED DAIRY, INC. in 47 WEST CRAIG STREET, UNIONTOWN, PA 15401 (NAICS 112120). OSHA activity number 340447473.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- UNITED DAIRY, INC.
- Site address
- 47 WEST CRAIG STREET
- City
- UNIONTOWN
- State
- PA
- ZIP
- 15401
- Mailing
- 47 WEST CRAIG STREET, UNIONTOWN, PA 15401
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Health
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 112120
- Employees
- 122
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.119 D03 I B
- Issued
- Jun 15, 2015
- Penalty
- Initial $2,700 · Current $3,400
General-duty citation text
29 CFR 1910.119(d)(3)(i)(B): The employer's piping and instrument diagrams were not accurate and did not represent equipment that was existing and was part of the process. (a) Ammonia System: On or about March 6, 2015, the employer did not update the P&ID to depict the current process of the ammonia system.
Recent events (2)
- — I (S) $3400
- — Z (S) $2700
1910.119 D03 II
- Issued
- Jun 15, 2015
- Abate by
- Jul 18, 2015
- Penalty
- Initial $2,700 · Current $0 Reduced
General-duty citation text
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: a) In the facility, on or about April 29, 2015 - The employer did not document that equipment complies with recognized and generally accepted good engineering practices (RAGAGEP) in that the ammonia machinery room was not equipped with a tight-fitting door on the south entrance to the building. ANSI/ASHRAE Standard 15-2010, Section 8.12, Paragraph D, is an applicable RAGAGEP that describes the requirements for refrigerating machinery rooms.
Recent events (2)
- — I (S) $0
- — Z (S) $2700
More inspections at United Dairy, INC.