Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CONWOOD PRODUCTS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CONWOOD PRODUCTS, INC. in 125 U S ARMY JUAN C. FEJEREN ST., BARRIGADA, GU 96913 (NAICS 493110). OSHA activity number 340578012.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Conwood Products, INC. — free Get an email when a new federal OSHA severe-injury report for Conwood Products, INC. is published. One employer, no account, unsubscribe in one click.
Site address
125 U S ARMY JUAN C. FEJEREN ST.
City
BARRIGADA
State
GU
ZIP
96913
Mailing
P.O. BOX 21448, GMF, BARRIGADA, GU 96921
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493110
Employees
21
Ownership type
A

10 citations on file for this inspection.

1910.305 B01 I

Serious Gravity 1 1 instance 10 exposed
Issued
Jun 17, 2015
Abate by
Jul 13, 2015
Penalty
Initial $1,785 · Current $1,250 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions:  Warehouse A, outside - A Samsung air conditioner unit cabinet was not closed where conductors entered.
Recent events (2)
  • — I (S) $1249.5
  • — Z (S) $1785

1910.305 G01 IV A

Serious Gravity 1 2 instances 10 exposed
Issued
Jun 17, 2015
Abate by
Jul 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A):   Flexible cords and cables were used for purposes prohibited by subparagraphs (a) through (f) of this paragraph in the following location, flexible cord was used in lieu of permanent wiring:   Warehouse A, outside - A Samsung air conditioner unit was energized by an orange Romex electrical line and beverage dispenser was energized through yellow extension cord.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 1 2 instances 10 exposed
Issued
Jun 17, 2015
Abate by
Jul 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:  Warehouse A, outside - A Samsung air conditioner unit was energized by an orange Romex electrical line and a beverage dispenser was energized through yellow extension cord;  electrical lines powering both appliances were run through external walls.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.23 D01

Other-than-serious 1 instance 10 exposed
Issued
Jun 17, 2015
Abate by
Jul 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.23(d)(1): Every flight of stairs having four or more risers was not be equipped with standard stair railings or standard handrails as specified in paragraphs (d)(1)(i) through (v) of this section, the width of the stair to be measured clear of all obstructions except handrails:   Warehouse B, stairs leading to mezzanine level - The right side ascending stair railing did not extend the full length of the stairs.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.23 E02

Other-than-serious 3 instances 10 exposed
Issued
Jun 17, 2015
Abate by
Jul 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.23(e)(2): Stair rails did not consist of a top rail, intermediate rail and/or posts, with the vertical height not more than 34 inches (86.36 cm) nor less than 30 inches (76.2 cm) from upper surface of top rail to surface of tread in line with face of riser at forward edge  of tread:  Warehouses A & B - The stair railings leading to the second floor mezzanines in both warehouses were inadequate in the following ways:   a.  Warehouse A - Both the left and right side stair railings were less than 30" in height.  Measurements ranged from 26"-28".      b.  Warehouse B - The stair railing was less than 30" in height.  Measurements ranged from 26"-28".     *ABATEMENT NOTE - Warehouse A - The 11th stair of the right side stairs leading to the storage mezzanine was cracked completely through and needs to be replaced.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.36 G02

Other-than-serious 1 instance 10 exposed
Issued
Jun 17, 2015
Abate by
Jun 23, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points:   Warehouse A - An aisle was partially blocked by containers of paint and not maintained at least 28" wide.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.132 D02

Other-than-serious 1 instance 10 exposed
Issued
Jun 17, 2015
Abate by
Jul 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification which included the requirements as outlined in 29 CFR 1910.132(d)(2):   Warehouses - Employees have been provided personal protective equipment such as gloves and safety shoes to protect them against hazards such as sharp edges or heavy materials falling on their feet in warehouses,  face shields and disposable masks when weed whacking, and safety glasses when cutting metal.  A hazard assessment has not been performed to include the following elements:      1.  Select and have each affected employee use the types of PPE that will protect them from the hazards identified in the hazard assessment;  2.  Communicate the selection decisions to each affected employee and;  3.  Select PPE that properly fits each affected employee.      *ABATEMENT NOTE: The employer shall verify that the required workplace hazard assessment has been performed through a written certification that identifies the workplace evaluated; the person certifying that the evaluation has been performed; the date(s) of the hazard assessment; and, which identifies the document as a certification of hazard assessment.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.141 D02 III

Other-than-serious 1 instance 10 exposed
Issued
Jun 17, 2015
Abate by
Jun 23, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.141(d)(2)(iii): Lavatories were not provided with hand soap or similar cleansing agent:  Men's room - It was observed that the restroom did not have soap.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.141 D02 IV

Other-than-serious 1 instance 10 exposed
Issued
Jun 17, 2015
Abate by
Jun 23, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.141(d)(2)(iv): Lavatories were not provided with individual hand towels or sections thereof, of cloth or paper, warm air blowers or clean individual sections of continuous cloth toweling:   Men's Room - The restroom was not provided with any means to dry hands.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.334 A01

Other-than-serious 1 instance 10 exposed
Issued
Jun 17, 2015
Abate by
Jul 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(1): Flexible electric cords were fastened with staples or otherwise hung in such a fashion as could damage the outer jacket or insulation:   Warehouse A, right side mezzanine - Yellow Romex electrical line running across the mezzanine floor was secured with bent nails.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Conwood Products, INC.'s full OSHA safety record →