LAS VEGAS, NV —
OSHA Inspection: U.S DEPARTMENT OF THE INTERIOR, BUREAU OF LAND MANAGEMENT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S DEPARTMENT OF THE INTERIOR, BUREAU OF LAND MANAGEMENT in 1000 SCENIC LOOP DRIVE, LAS VEGAS, NV 89161 (NAICS 924120). OSHA activity number 340872647.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 1000 SCENIC LOOP DRIVE
- City
- LAS VEGAS
- State
- NV
- ZIP
- 89161
- Mailing
- 4701 N. TORREY PINES DRIVE, LAS VEGAS, NV 89130
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 11000
- Ownership type
- D
Citations
11 citations on file for this inspection.
1910.36 G02
- Issued
- Nov 13, 2015
- Abate by
- Nov 30, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. (a) At the Red Rock Canyon Outdoor Recreation Planner's Office, exit access/egress was approximately 19 inches and obstructed by office furniture and file cabinet.
Recent events (1)
- — Z (S) $0
1910.157 C04
- Issued
- Nov 13, 2015
- Abate by
- Nov 30, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(c)(4): Portable fire extinguishers were not kept in their designated places at all times except during use. (a) At the Red Rock Canyon Admin, entry to employee cubicle area, two portable fire extinguishers were located under the employee cubicle with one extinguisher's safety pin pulled out.
Recent events (1)
- — Z (S) $0
1910.157 E02
- Issued
- Nov 13, 2015
- Abate by
- Nov 30, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly. (a) At the BLM, Red Rock Canyon NCA Visitor Center, AFM-RR/S office , the portable fire extinguisher was last inspected in March 2014. (b) At the Information Tech area, portable fire extinguisher not inspected monthly, last inspection date was March 2014. (c) Red Rock Canyon Visitor Center Store, storage area portable fire extinguisher last inspection date was March 2015. (d) Red Rock Canyon Fee Station #1, portable fire extinguisher last inspection date was March 2015.
Recent events (1)
- — Z (S) $0
1910.304 B03 I
- Issued
- Nov 13, 2015
- Abate by
- Dec 9, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in wet locations were not equipped with ground-fault circuit-interrupter protection for personnel. (a) At the Red Rock Canyon, upper parking lot, outside the restroom, south east outdoor electrical outlet receptacles were non-GFCI.
Recent events (1)
- — Z (S) $0
1910.304 F01 IV
- Issued
- Nov 13, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel. (a) At the Red Rock Canyon Visitor Center Janitor room, electrical power panel A was obstructed by bags of cleaning supplies.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Nov 13, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. (a) At the Red Rock Canyon Visitor Center, a black extension cord was used to energize the coin machines for more than three months.
Recent events (1)
- — Z (S) $0
1910.305 J01 I
- Issued
- Nov 13, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lamp holders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact. (a) At the Red Rock Canyon, Admin building cultural specialist's desk top, the portable lamp was plugged-in without a light bulb.
Recent events (1)
- — Z (S) $0
1910.37 B02
- Issued
- Nov 13, 2015
- Abate by
- Nov 30, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": (a) At the Red Rock Canyon Archeology Lab, west door exit was not marked "EXIT". (b) At Red Rock Canyon Admin building storage room, two exit doors were not marked "EXIT". The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(b)(2) which was contained in OSHA inspection number 315607481, citation number 1, item number 1 and was affirmed as a final order on 9/16/2011, with respect to a workplace located at 1340 Financial Blvd., Reno, NV 89520. The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(b)(2) which was contained in OSHA inspection number 315495255, citation number 1, item number 1 and was affirmed as a final order on 3/30/2011, with respect to a workplace located at 351 Pacu Lane, Bishop, CA. 93541. The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(b)(2) which was contained in OSHA inspection number 315492413, citation number 1, item number 1 and was affirmed as a final order on 3/30/2011, with respect to a workplace located at 300 South Richmond Road, Ridgecrest, CA. 93555.
Recent events (1)
- — Z (R) $0
1910.37 B05
- Issued
- Nov 13, 2015
- Abate by
- Nov 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet). (a) At the Red Rock Canyon Visitor Center Admin building, door leading to the storage room was not marked "NOT AN EXIT". The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(b)(5) which was contained in OSHA inspection number 315491621, citation number 2, item number 1 and was affirmed as a final order on 7/07/2011, with respect to a workplace located at 9828 N. 31st Ave., Phoenix, AZ 85051. The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(b)(5) which was contained in OSHA inspection number 315495255, citation number 1, item number 2 and was affirmed as a final order on 3/30/2011, with respect to a workplace located at 351 Pacu Lane, Bishop, CA. 93541. The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(b)(5) which was contained in OSHA inspection number 315681775, citation number 1, item number 2 and was affirmed as a final order on 10/27/2011, with respect to a workplace located at 1340 Financial Blvd., Reno, NV 89502.
Recent events (1)
- — Z (R) $0
1910.303 B02
- Issued
- Nov 13, 2015
- Abate by
- Nov 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. (a) At the Red Rock Canyon Admin Office, the cyclone household fan was used for air circulation in the outside restroom. The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2) which was contained in OSHA inspection number 315492298, citation number 1, item number 2A and was affirmed as a final order on 8/30/2011, with respect to a workplace located at 1400 S. Front Street, Caliente, NV 89008. The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2) which was contained in OSHA inspection number 315492413, citation number 1, item number 3 and was affirmed as a final order on 9/29/2011, with respect to a workplace located at 300 S. Richmond Road, Ridgecrest, CA 93555. The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2) which was contained in OSHA inspection number 315681775, citation number 1, item number 4 and was affirmed as a final order on 10/27/2011, with respect to a workplace located at 1340 Financial Blvd., Reno, NV 89502.
Recent events (1)
- — Z (R) $0
1910.176 B
- Issued
- Nov 13, 2015
- Abate by
- Nov 30, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.176(b): Material stored in tiers was not stacked, blocked, interlocked or limited in height so that it was stable and secure against sliding and collapse. (a) At the Red Rock Canyon Visitor Center Interpretive Storage, haphazardly stored materials on top of storage bins were not secured from collapsing and or sliding.
Recent events (1)
- — Z (O) $0
More inspections at U.S Department of the Interior, Bureau of Land Management
View U.S Department of the Interior, Bureau of Land Management's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340872647.