Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: THE CONNECTICUT LIGHT AND POWER COMPANY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of THE CONNECTICUT LIGHT AND POWER COMPANY in BULKELEY HIGH SCHOOL 300 WETHERSFIELD AVENUE, HARTFORD, CT 06114 (NAICS 221122). OSHA activity number 340891639.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Connecticut Light and Power Company — free Get an email when a new federal OSHA severe-injury report for The Connecticut Light and Power Company is published. One employer, no account, unsubscribe in one click.
Site address
BULKELEY HIGH SCHOOL 300 WETHERSFIELD AVENUE
City
HARTFORD
State
CT
ZIP
06114
Mailing
107 SELDEN STREET, BERLIN, CT 06037
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
1083
Ownership type
A

1 citation on file for this inspection.

1910.269 O02 I

Serious Gravity 10 1 instance 8 exposed
Issued
Dec 3, 2015
Abate by
Apr 15, 2016
Penalty
Initial $7,000 · Current $4,550 Reduced
29 CFR 1910.269(o)(2)(i): The employer did not establish and enforce work practices for the protection of each worker from the hazards of high-voltage or high-power testing at all test areas, temporary and permanent:    Jobsite located at 300 Wethersfield Avenue, Hartford, Connecticut:  On, or about, June 13, 2015, the employer had not established and enforced work practices to protect each worker involving in testing operations related to a cable fault repair.  An employee was subjected to an arc flash incident when he attempted to reapply a protective ground after removing a test lead from a phase in pad mounted switchgear.  The cable that was being tested re-energized due to a failure in a vacuum switch.
Recent events (2)
  • — I (S) $4550
  • — Z (S) $7000

View The Connecticut Light and Power Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340891639.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.