Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: THE CONNECTICUT LIGHT AND POWER COMPANY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of THE CONNECTICUT LIGHT AND POWER COMPANY in 174 FRANKLIN STREET, TORRINGTON, CT 06790 (NAICS 221122). OSHA activity number 343672069.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Connecticut Light and Power Company — free Get an email when a new federal OSHA severe-injury report for The Connecticut Light and Power Company is published. One employer, no account, unsubscribe in one click.
Site address
174 FRANKLIN STREET
City
TORRINGTON
State
CT
ZIP
06790
Mailing
107 SELDEN STREET, BERLIN, CT 06037
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
56
Ownership type
A

8 citations on file for this inspection.

1910.101 B

Other-than-serious 2 instances 10 exposed
Issued
Jan 14, 2019
Penalty
Initial $3,887 · Current $0 Reduced
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6:  Ref. CGA P-1-2006, Section 5.7.4 as referenced by CGA P-1-1965, Section 3.3.1.      Substation Operations Building, Aisle near Building Entrance:  On, or about, December 12, 2018, two compressed air cylinders that contained sulfur hexafluoride (SF6) were stored, unsecured, next to a fence and storage cabinet.
Recent events (2)
  • — I (O) $0
  • — Z (S) $3887

1910.184 E01

Serious Gravity 1 1 instance 6 exposed
Issued
Jan 14, 2019
Penalty
Initial $3,887 · Current $3,000 Reduced
29 CFR 1910.184(e)(1): Alloy steel sling(s) did not have permanently affixed durable identification stating size, grade, rated capacity, and reach:       Substation Operations Building, Maintenance Shop:  On, or about, December 12, 2018, a three foot long, two legged chain alloy sling was not provided with an identification tag.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $3887

1910.184 E03 I

Serious Gravity 1 1 instance 5 exposed
Issued
Jan 14, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.184(e)(3)(i): A thorough periodic inspection of alloy steel chain slings was not made on a regular basis and/or were done at intervals greater than once every 12 months:  Substation Operations Building, Maintenance Shop:  On, or about, December 12, 2018, a three foot long, two legged chain alloy sling was not subject to periodic, documented inspections.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.212 A01

Serious Gravity 5 1 instance 3 exposed
Issued
Jan 14, 2019
Penalty
Initial $5,183 · Current $5,000 Reduced
29 CFR 1910.212(a)(1): Machine guarding was not provided to protect operator(s) and other employees from hazard(s) created by rotating parts and flying chips:      Fleet Garage, Tire Room:  On, or about, December 12, 2018, a chuck guard had not been provided on the lathe portion of the Smith Midas 1220 LTD three in one lathe/mill/drill machine.
Recent events (2)
  • — I (S) $5000
  • — Z (S) $5183

1910.215 B09

Serious Gravity 5 3 instances 12 exposed
Issued
Jan 14, 2019
Penalty
Initial $5,183 · Current $5,000 Reduced
29 CFR 1910.215(b)(9): Guard for abrasive wheel machine where the operator stands in front of the machine was not constructed so that the peripheral protecting member could be adjusted to the constantly decreasing diameter of the wheel: or the distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:      On, or about, December 12, 2018, in the following locations off-hand grinders were not provided with proper tongue guards:     A.  Line Cage:  A Milwaukee bench mounted grinder was not provided with a tongue guard on the right side.      B.  Fleet Garage, Tire Room:  The tongue guard provided on the Blue-Point pedestal mounted grinder was not adjusted within one quarter of an inch from the wheel and the tongue guard was not installed perpendicular to the wheel.    C.  Substation Operations Building, Maintenance Shop:  The tongue guard provided on the left side of the Millers Falls bench grinder was adjusted over the outer guard and not in position to offer protection from wheel breakage.
Recent events (2)
  • — I (S) $5000
  • — Z (S) $5183

1910.303 G01 I A

Other-than-serious 2 instances 10 exposed
Issued
Jan 14, 2019
Abate by
Mar 4, 2019
Penalty
Initial $4,573 · Current $3,000 Reduced
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:       A.  Fleet Garage, Electrical Room:  On, or about, December 12, 2018, a refrigerator was located across from Panel A-4, a General Electric 480/277 volt panelboard.  The working space had been reduced to 37 inches.      B.  Substation Operations Building, Maintenance Shop:  On, or about, December 12, 2018, a workbench and battery charger were located in the working space for Panel S9, a General Electric 120/208 volt panelboard.
Recent events (2)
  • — I (O) $3000
  • — Z (S) $4573

1910.303 G01 II

Other-than-serious 2 instances 4 exposed
Issued
Jan 14, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:    A.  Fleet Garage, Upper Landing for Mezzanine Stairs:  On, or about, December 20, 2018, cardboard boxes had been left on the floor in front of a bank of electrical disconnects.    B.  Fleet Garage, Electrical Room:  On, or about, December 20, 2018, items such as a cardboard box, sign holders and angled material were stored on the floor in the working space of Panel 5-6, a General Electric 480/277 volt panelboard.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.304 B04 II B

Other-than-serious 1 instance 10 exposed
Issued
Jan 14, 2019
Penalty
Initial $5,183 · Current $2,000 Reduced
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4:    Substation Operations Building, Electricians Day Room:  On, or about, December 12, 2018, a GE refrigerator, GE microwave oven and a Keurig coffee maker were energized through a Belkin 15 ampere relocatable power tap.  Both the microwave oven and coffee maker exceeded the 12 ampere (80% load) permitted on the power tap.
Recent events (2)
  • — I (O) $2000
  • — Z (S) $5183

View The Connecticut Light and Power Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343672069.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.