OSHA Inspection: US AIR FORCE, NELLIS AIR FORCE BASE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of US AIR FORCE, NELLIS AIR FORCE BASE in BLDG. 808, 6020 BEALE AVENUE, NELLIS AFB, NV 89191 (NAICS 928110). OSHA activity number 341460889.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch US AIR Force, Nellis AIR Force Base — free Get an email when a new federal OSHA severe-injury report for US AIR Force, Nellis AIR Force Base is published. One employer, no account, unsubscribe in one click.
Site address
BLDG. 808, 6020 BEALE AVENUE
City
NELLIS AFB
State
NV
ZIP
89191
Mailing
99 ABW/SE 4430 GRISSOM AVENUE, STE 206, NELLIS AFB, NV 89191
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
10
Ownership type
D

6 citations on file for this inspection.

1910.36 G02

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 17, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  (a) At Building 808 Heavy Equipment Shop, mezzanine egress was obstructed by a file cabinet reducing the exit access/egress to 23 inches wide.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 17, 2016
Abate by
Jul 13, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  (a) At Building 808, Heavy Equipment Shop, the portable fire extinguisher was obstructed by a tool box, shop tools and lumber.
Recent events (1)
  • — Z (S) $0

1910.303 B08 II

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 17, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(8)(ii): Electric equipment that depends on the natural circulation of air and convection principles for cooling of exposed surfaces were not installed so that room airflow over such surfaces is not prevented by walls or by adjacent installed equipment. For equipment designed for floor mounting, clearance between top surfaces and adjacent surfaces were not provided to dissipate rising warm air.  (a) At Building 808 Heavy Equipment Shop break room, the air cooled pad mounted transformer was obstructed by furniture preventing the needed natural air circulation.
Recent events (1)
  • — Z (S) $0

1960.8 A

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 17, 2016
Abate by
Jul 13, 2016
Penalty
Initial $0 · Current $0
29 CFR 1960.8(a):  The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm:  (a) At Building 808 Maintenance Bay, the west roll up door cover was loose and detaching from its fastening screws.  Employees were exposed to struck by hazards of the falling cover.
Recent events (1)
  • — Z (S) $0

1910.303 B01 II

Repeat Gravity 5 1 instance 2 exposed
Issued
Jun 17, 2016
Abate by
Jul 1, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(1)(ii): Electrical equipment was not free from recognized hazards, based on the mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided:  (a) At Building 808 Heavy Equipment Storage area, the duplex convenience outlet used to plug-in shop equipment have broken outlet cover exposing energized copper wires.  (b) At Building 808 Break room, circuit #1, panel S2480, light switch cover is cracked or damaged.  The US Air Force, Nellis AFB was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(1)(ii) which was contained in OSHA inspection number 536678, citation number 1, item number 2 and was affirmed as a final order on 10/26/2012, with respect to a workplace located at Nellis AFB HVAC Shop.
Recent events (1)
  • — Z (R) $0

1910.179 G01 V

Other-than-serious 1 instance 2 exposed
Issued
Jun 17, 2016
Abate by
Jul 1, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.179(g)(1)(v): Pendant control box(es) were not clearly marked for identification of functions:  (a) At Building 808 Maintenance Bay, crane DEMAG SGUH controls were not clearly marked for identification of functions.
Recent events (1)
  • — Z (O) $0

View US AIR Force, Nellis AIR Force Base's full OSHA safety record →