NELLIS AFB, NV —
OSHA Inspection: US AIR FORCE, NELLIS AIR FORCE BASE
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of US AIR FORCE, NELLIS AIR FORCE BASE in 6020 BEALE AVENUE, NELLIS AFB, NV 89191 (NAICS 928110). OSHA activity number 347026627.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- US AIR FORCE, NELLIS AIR FORCE BASE
- Site address
- 6020 BEALE AVENUE
- City
- NELLIS AFB
- State
- NV
- ZIP
- 89191
- Mailing
- 4430 GRISSOM AVENUE STE 206, NELLIS AFB, NV 89191
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 1000
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.138 A
- Issued
- Jan 8, 2024
- Abate by
- Mar 25, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.138(a):The employer did not select and require employees to use appropriate hand protection when employees hands were exposed to hazardous condition(s): On or about October 11, 2023, an employee tasked with adding refrigerant to a (York) chiller located in the HVAC shop on Nellis Air Force base sustained injuries to his hands when he inadvertently made contact with the R401A refrigerant. The employer failed to access and provide appropriate personal protective equipment (chemical resistant gloves) to employees exposed to chemical hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.146 C01
- Issued
- Jan 8, 2024
- Abate by
- Mar 25, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.146(c)(1):The employer did not evaluate the workplace to determine if any spaces were permit-required confined spaces: On or about October 11, 2022, employees tasked with servicing machinery such as but not limited to a York chiller (model YLA0125, serial number SKDM648470) located at building 1780 on Nellis Air Force Base were not protected from atmospheric hazards in that, the entry/exit points of the machinery were not evaluated for confined space(s). Employees who regularly crawl underneath the unit(s) when turning valves, attaching gauges, and attaching hoses could become incapacitated or their ability to self-rescue impaired if the oxygen in the air somehow became displaced or otherwise compromised.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C04 I
- Issued
- Jan 8, 2024
- Abate by
- Mar 25, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: On or about October 11, 2023, and at least 4 weeks prior, written procedures instructing employees on how to properly isolate, blocked, or render safe stored or residual energy, were not developed and/or used at the facility. Employees assigned to perform maintenance and repairs on equipment such as but not limited to, a York chiller (YLAA0125 serial number SKDM648470) were potentially exposed to electrical hazards. Energy sources used at the facility include electricity, thermal energy, and pneumatic energy. The U.S. Air Force was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA inspection number 1597100, citation number 1, item number 01 and was affirmed as a final order on December 2, 2022, with respect to a workplace located at Building 507, Hill Air Force Base, Utah.
Recent events (2)
- — I (R) $0
- — Z (R) $0
1904.39 A02
- Issued
- Jan 8, 2024
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1904.39(a)(2):The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye: Building 1780, Nellis Air Force Base. The employer failed to report the hospitalization of an employee within (24) twenty-four hours as required. On September 22, 2023, an employee in the process of servicing the facility's York chiller (YLAA0125 serial number SKDM648470) was injured when his hands inadvertently contacted the R-401A refrigerant. Hospitalized for three (3) days, the incident was not reported until October 3, 2023. The U.S. Air Force was previously cited for a violation of this occupational safety and health standard, which was contained in OSHA inspection number 1375330, citation number 01, item number 01 and was affirmed as a final order on June 5, 2019, with respect to a workplace located at Gate 14, Robins Air Force Base, Georgia.
Recent events (2)
- — I (R) $0
- — Z (R) $0
More inspections at US AIR Force, Nellis AIR Force Base
View US AIR Force, Nellis AIR Force Base's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 347026627.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.