Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NAPOLEON SPRING WORKS, INC.

Follow-up inspection · Safety discipline

On , OSHA opened a follow-up safety inspection of NAPOLEON SPRING WORKS, INC. in 111 WEIRES DR., ARCHBOLD, OH 43502 (NAICS 332612). OSHA activity number 341883759.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Napoleon Spring Works, INC. — free Get an email when a new federal OSHA severe-injury report for Napoleon Spring Works, INC. is published. One employer, no account, unsubscribe in one click.
Site address
111 WEIRES DR.
City
ARCHBOLD
State
OH
ZIP
43502
Mailing
111 WEIRES DR., ARCHBOLD, OH 43502
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332612
Employees
150
Ownership type
A

5 citations on file for this inspection.

1910.333 A01

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 24, 2017
Abate by
May 24, 2018
Penalty
Initial $8,963 · Current $4,000 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them:    a. Napoleon Spring Works, Inc. - Archbold, Ohio: On or about October 31, 2016, an employee was exposed to electrical hazards in that the upstream electrical power distribution panel was not deenergized and locked out before employees accessed the downstream electrical panel used to power the punch table in the roll form department.  The employee was exposed to a 480 volt electrical hazard while working near live parts in the disconnect box to remove/replace fuses.
Recent events (3)
  • — F (S) $4000
  • — C (S) $8963
  • — Z (S) $8963

1910.335 A02 I A

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 24, 2017
Abate by
May 24, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(2)(i)(A): Fuse handling equipment, insulated for the circuit voltage, was not used to remove or install fuses when the fuse terminals are energized.    a. Napoleon Spring Works, Inc. - Archbold, Ohio: On or about October 31, 2016, an employee that removed and installed fuses for a 480 volt electrical panel used to power the punch table in the roll form department was exposed to electrical hazards in that insulated fuse pullers were not utilized.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.335 A01 I

Serious Gravity 5 1 instance 3 exposed
Issued
Apr 24, 2017
Abate by
May 24, 2018
Penalty
Initial $8,963 · Current $4,000 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:    a. Napoleon Spring Works, Inc. - Archbold, Ohio: On or about October 31, 2016, the employer did not ensure that employees who perform troubleshooting and change fuses were provided with and used personal protective equipment to protect against electrical hazards.  An employee removing/replacing a fuse in a 480 volt electrical panel used to power the punch table in the roll form department was exposed to electrical shock and arc flash hazards in that flame resistant clothing, leather gloves, hard hat, and arc rated face shield were not worn during the electrical work.
Recent events (3)
  • — F (S) $4000
  • — C (S) $8963
  • — Z (S) $8963

1910.303 B01 VIII

Serious Gravity 5 1 instance 6 exposed
Issued
Apr 24, 2017
Abate by
May 24, 2018
Penalty
Initial $8,963 · Current $4,000 Reduced
29 CFR 1910.303(b)(1)(viii): Electrical equipment was not free from recognized hazards based on other factors that contribute to the practical safeguarding of persons using or likely to come in contact with the equipment:    a. Napoleon Spring Works, Inc. - Archbold, Ohio: On or about November 1, 2016, employees using the 480 volt main electrical panel to turn power off/on to the punch table each day were exposed to electrical hazards in that the external disconnect was damaged.
Recent events (3)
  • — F (S) $4000
  • — C (S) $8963
  • — Z (S) $8963

1910.178 L04 III

Repeat Gravity 5 1 instance 50 exposed
Issued
Apr 24, 2017
Abate by
Nov 24, 2017
Penalty
Initial $17,927 · Current $8,000 Reduced
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years:    a. Napoleon Spring Works, Inc. - Archbold, Ohio: On or about November 1, 2016, the employer did not ensure that each forklift operators driving performance was evaluated at least once every three years.  The employer did not evaluate driving performance in the workplace after some drivers had received prior classroom training.    Napoleon Spring Works, Inc. was previously cited for a violation of an equivalent occupational safety and health standard 29 CFR 1910.178(l)(1)(i), which was contained in OSHA inspection number 905594, citation number 1, item number 6 and was affirmed as a final order on November 7, 2013, with respect to a workplace located at 111 Weires Dr., Archbold, Ohio 43502.
Recent events (3)
  • — F (R) $8000
  • — C (R) $17927
  • — Z (R) $17927

View Napoleon Spring Works, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341883759.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.