TRAVIS AFB, CA —
OSHA Inspection: U.S. AIR FORCE 60TH LOGISTICS READINESS SQUADRON
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. AIR FORCE 60TH LOGISTICS READINESS SQUADRON in 350 HANGER AVENUE BLDG. 549, TRAVIS AFB, CA 94535 (NAICS 928110). OSHA activity number 341975704.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. AIR FORCE 60TH LOGISTICS READINESS SQUADRON
- Site address
- 350 HANGER AVENUE BLDG. 549
- City
- TRAVIS AFB
- State
- CA
- ZIP
- 94535
- Mailing
- 400 BRENNAN CIRCLE BUILDING 51, ROOM 240, TRAVIS AFB, CA 94535
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 50
- Ownership type
- D
Citations
8 citations on file for this inspection.
1910.184 I09 III
- Issued
- Feb 27, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.184(i)(9)(iii): Synthetic web sling(s) with snags, punctures, tears or cuts were not immediately removed from service. General Purpose Shop Bldg. 139: On 12/2/2016, a 10 foot synthetic web sling was torn and not immediately removed from service.
Recent events (1)
- — Z (S) $0
1910.304 G05
- Issued
- Feb 27, 2017
- Abate by
- Mar 23, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): 29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective: In the following two instances fan plugs were missing grounding pins: a) General Purpose Shop, Bldg.139: On 12/01/2016, the plug on the LASK pedestal fan serial No. 581594. b) Welding Shop, Bldg.919: On 12/01/2016, the plug on the Dayton 36-inch fan model 3C674D.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Feb 27, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: Warehouse Area Bldg. 549: On 11/30/2016, a junction box with energized conductors hanging out of it was not provided with a cover.
Recent events (1)
- — Z (S) $0
1910.303 F02
- Issued
- Feb 27, 2017
- Abate by
- Mar 23, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Heavy Equipment Shop, Bldg. 139: On 12/01/2016, one disconnect knife switch type located on the back wall was energized and had no markings which indicated its purpose. The U.S. Air Force 60th was previously cited for a violation of this occupational safety and health standard 1910.303(f)(2), which was contained in OSHA inspection number 191646, citation number 01, item number 004 and was affirmed as a final order on 08/22/2012, with respect to a workplace located at 241 V Street at Travis AFB, CA 94535.
Recent events (1)
- — Z (R) $0
1910.305 B01 II
- Issued
- Feb 27, 2017
- Abate by
- Mar 23, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: Warehouse Area Bldg. 549: On 11/30/2016, an electrical panel board, Panel A 120V/208V, had a missing planks and live electrical parts were exposed. The U.S. Air Force 60th Logistics Readiness Squadron was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(1)(ii), which was contained in OSHA inspection number 191744, citation number 01, item number 003 and was affirmed as a final order on 08/22/2012, with respect to a workplace located at 350 Hanger Ave., Bldg. 549 at Travis AFB, CA 94535.
Recent events (1)
- — Z (R) $0
1910.305 G01 IV A
- Issued
- Feb 27, 2017
- Abate by
- Mar 23, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Vehicle Management, Bldg. 139: On 12/01/2016, an extension cord was used in lieu of permanent wiring to energize a Frigidaire refrigerator. The U.S. Air Force 60th Aerial Port Squadron was previously cited for a violation of this occupational safety and health standard 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 190542, citation number 01, item number 004a and was affirmed as a final order on 08/22/2012, with respect to a workplace located at 90 Ragsdale Street Travis AFB, CA 94535.
Recent events (1)
- — Z (R) $0
1910.37 B04
- Issued
- Feb 27, 2017
- Abate by
- Mar 23, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent and the line-of-sight to an exit was not clearly visible: Warehouse Area, Bldg. 549: On 11/30/2016, exit signs were not posted along exit routes to indicate the direction of travel to the nearest exit. The posted exit signs were not visible.
Recent events (1)
- — Z (O) $0
1910.242 B
- Issued
- Feb 27, 2017
- Abate by
- Mar 23, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: Warehouse Area ,Bldg. 549: On 11/30/2016, the compressed air used for cleaning was not reduced to 30 p.s.i.
Recent events (1)
- — Z (O) $0
More inspections at U.S. AIR Force 60TH Logistics Readiness Squadron
View U.S. AIR Force 60TH Logistics Readiness Squadron's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341975704.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.