Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: USDA-FOREST SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of USDA-FOREST SERVICE in 1201 CALLE CEIBA JARDIN BOTANICO SUR, SAN JUAN, PR 00926 (NAICS 924120). OSHA activity number 341975977.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Usda-Forest Service — free Get an email when a new federal OSHA severe-injury report for Usda-Forest Service is published. One employer, no account, unsubscribe in one click.
Establishment
USDA-FOREST SERVICE
Site address
1201 CALLE CEIBA JARDIN BOTANICO SUR
City
SAN JUAN
State
PR
ZIP
00926
Mailing
1201 CALLE CEIBA JARDIN BOTANICO SUR, SAN JUAN, PR 00926
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
68
Ownership type
D

5 citations on file for this inspection.

1910.36 D01

Serious Gravity 1 2 instances 10 exposed
Issued
Feb 6, 2017
Abate by
Feb 10, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:  a. On or about December 19, 2016, at the library basement/bottom stairway area, a designated exit route door was locked from the inside due to a door knob that was defective and non-operational.     b. On or about December 20, 2016, at the chemical laboratory/basement area, a designated exit route door was locked from the inside due to non-operational push bar.   NOTE: Certification of abatement is not required for this citation item since it was submitted prior to citation issuance.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 1 1 instance 3 exposed
Issued
Feb 6, 2017
Abate by
Feb 24, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  a. On or about December 19, 2016, at the library basement back room storage area, a designated exit access was not marked by an exit sign or any other means.  NOTE:  Certification of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c).
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 4 instances 6 exposed
Issued
Feb 6, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a. On or about December 15, 2016, at the Forestry technicians cubicle/GIS bldg., an uninterruptible APC 700 power supply was not directly connected to a permanently installed branch circuit receptacle.  b. On or about December 19, 2016, at the Technical Information Specialist cubicle/Library bldg., an uninterruptible APC Pro 1000 power supply was not directly connected to a permanently installed branch circuit receptacle.  c. On or about December 19, 2016, at the Directors' work area/Library bldg., an uninterruptible APC Pro 1000 power supply was not directly connected to a permanently installed branch circuit receptacle.  d. On or about December 19, 2016, at the Purchasing Agent's cubicle/Procurement Department, an uninterruptible APC 750 power supply was not directly connected to a permanently installed branch circuit receptacle.  NOTE: Certification of abatement is not required for this citation item as abatement was documented by the compliance safety and health officer during the inspection.
Recent events (1)
  • — Z (S) $0

1910.303 G01

Serious Gravity 1 1 instance 1 exposed
Issued
Feb 6, 2017
Abate by
Mar 13, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  a. On or about December 15, 2016, at the sorting laboratory, an electrical service panel was not readily accessible; there was a fixed laboratory cabinet below the panel.   NOTE:  Certification of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c).
Recent events (1)
  • — Z (S) $0

1910.37 B06

Other-than-serious 5 instances 3 exposed
Issued
Feb 6, 2017
Abate by
Feb 24, 2017
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  a. On or about December 19, 2016, at the library building, all self luminous exit signs located above the exit doors and exit routes were not operational and were not replaced on or before the manufacturers' date of September 2004.    NOTE:  Certification of abatement must be submitted for this citation item as required by 29 CFR 1903.19(c).
Recent events (1)
  • — Z (O) $0

View Usda-Forest Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341975977.