OSHA Inspection: MID-OHIO CONTRACTING SERVICES, LTD.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MID-OHIO CONTRACTING SERVICES, LTD. in 117 N. FRONT STREET, COLUMBUS, OH 43215 (NAICS 236220). OSHA activity number 341984714.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mid-Ohio Contracting Services, LTD. — free Get an email when a new federal OSHA severe-injury report for Mid-Ohio Contracting Services, LTD. is published. One employer, no account, unsubscribe in one click.
Site address
117 N. FRONT STREET
City
COLUMBUS
State
OH
ZIP
43215
Mailing
1400 DUBLIN ROAD, COLUMBUS, OH 43215
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
2
Ownership type
A

4 citations on file for this inspection.

1926.405 A02 II B

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 2, 2017
Abate by
Feb 14, 2017
Penalty
Initial $3,984 · Current $1,992 Reduced
29 CFR 1926.405(a)(2)(ii)(B): Branch circuits shall originate in a power outlet or panelboard. Conductors shall be run as multiconductor cord or cable assemblies or open conductors, or shall be run in raceways. All conductors shall be protected by overcurrent devices at their ampacity. Runs of open conductors shall be located where the conductors will not be subject to physical damage, and the conductors shall be fastened at intervals not exceeding 10 feet (3.05 m). No branch-circuit conductors shall be laid on the floor. Each branch circuit that supplies receptacles or fixed equipment shall contain a separate equipment grounding conductor if the branch circuit is run as open conductors.  a. At the worksite located at 117 North Front Street, Columbus, Ohio, the branch-circuit conductors that provided power for employees at the site was laid on the floor and subject to physical damage, thereby exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $1992
  • — Z (S) $3984

1926.405 J01 II

Serious Gravity 5 4 instances 2 exposed
Issued
Feb 2, 2017
Abate by
Feb 16, 2017
Penalty
Initial $0 · Current $0
29 CFR 1926.405(j)(1)(ii): Support. Fixtures, lampholders, rosettes, and receptacles shall be securely supported. A fixture that weighs more than 6 pounds (2.72 kg) or exceeds 16 inches (406 mm) in any dimension shall not be supported by the screw shell of a lampholder.   a. At the worksite located at 117 North Front Street, Columbus, Ohio, employees used a receptacle that was not securely supported to power two strings of temporary lighting, thereby exposing employees to an electrical hazard.     b. At the worksite located at 117 North Front Street, Columbus, Ohio, employees used a receptacle that was not securely supported to power a DeWalt radio, thereby exposing employees to an electrical hazard.     c. At the worksite located at 117 North Front Street, Columbus, Ohio, employees used a receptacle that was not securely supported to power one string of temporary lighting, thereby exposing employees to an electrical hazard.    d. At the worksite located at 117 North Front Street, Columbus, Ohio, employees used a receptacle that was not securely supported to power two space heaters and a rotary hammer drill by extension cord, thereby exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 2, 2017
Abate by
Feb 14, 2017
Penalty
Initial $3,984 · Current $1,992 Reduced
29 CFR 1926.405(g)(2)(iii): Splices. Flexible cords shall be used only in continuous lengths without splice or tap. Hard service flexible cords No. 12 or larger may be repaired if spliced so that the splice retains the insulation, outer sheath properties, and usage characteristics of the cord being spliced.   a. At the worksite located at 117 North Front Street, Columbus, Ohio, employees used a string of temporary lighting with the flexible cord spliced, thereby exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $1992
  • — Z (S) $3984

1926.405 J01 I

Serious Gravity 5 3 instances 2 exposed
Issued
Feb 2, 2017
Abate by
Feb 14, 2017
Penalty
Initial $3,984 · Current $1,992 Reduced
29 CFR 1926.405(j)(1)(i): Live parts. Fixtures, lampholders, lamps, rosettes, and receptacles shall have no live parts normally exposed to employee contact. However, rosettes and cleat-type lampholders and receptacles located at least 8 feet (2.44 m) above the floor may have exposed parts.   a. At the worksite located at 117 North Front Street, Columbus, Ohio, employees used a receptacle without a faceplate installed to power two strings of temporary lighting, thereby exposing employees to an electrical hazard.     b. At the worksite located at 117 North Front Street, Columbus, Ohio, employees used a receptacle without a faceplate installed to power one string of temporary lighting, thereby exposing employees to an electrical hazard.    c. At the worksite located at 117 North Front Street, Columbus, Ohio, employees used a receptacle without a faceplate installed to power two space heaters and a rotary hammer drill by extension cord, thereby exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $1992
  • — Z (S) $3984