SAN FRANCISCO, CA —
OSHA Inspection: THE PRESIDIO TRUST
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of THE PRESIDIO TRUST in 1750 LINCOLN BLVD - UTILITY, SAN FRANCISCO, CA 94129 (NAICS 924120). OSHA activity number 342267788.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE PRESIDIO TRUST
- Site address
- 1750 LINCOLN BLVD - UTILITY
- City
- SAN FRANCISCO
- State
- CA
- ZIP
- 94129
- Mailing
- P.O. BOX 29052, SAN FRANCISCO, CA 94129
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 322
- Ownership type
- D
Citations
7 citations on file for this inspection.
1910.335 A01 II
- Issued
- Jun 16, 2017
- Abate by
- Jun 28, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.335(a)(1)(ii): Protective equipment was not maintained in a safe, reliable condition and/or was not periodically inspected or tested: Building 1750- Power Distribution Section: On April 24, 2017, voltage rated gloves were not tested every six months. The last tested date was June 25, 2014.
Recent events (1)
- — Z (S) $0
1910.37 A03
- Issued
- Jun 16, 2017
- Abate by
- Jun 28, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed: Building 1243- Warehouse/Salvage: On April 20, 2017 the exit was blocked with miscellaneous items which obstructed the path to the outside. The Presidio Trust was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.37(a)(3), which was contained in OSHA inspection number 957077, notice 2, item 1 and was affirmed as a final order on 5/12/14, with respect to a workplace located at The Presidio Trust, San Francisco, CA.
Recent events (1)
- — Z (R) $0
1910.212 A03 II
- Issued
- Jun 16, 2017
- Abate by
- Jul 13, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(a)(3)(ii): The point of operation of machines whose operation exposes an employee to injury, shall be guarded. The guarding device shall be in conformity with any appropriate standards therefor, or, in the absence of applicable specific standards, shall be so designed and constructed as to prevent the operator from having any part of his body in the danger zone during the operating cycle. Carpentry Shop Building 1750: On April 20, 2017, the electric drill, Powermatic # 10 Model #200, Serial # 4-5114 was not guarded. It was used for drilling metal and wood. The Presidio Trust was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.212(a)(3)(ii), which was contained in OSHA inspection number 957077, notice 2, item 3 and was affirmed as a final order on 4/24/15, with respect to a workplace located at The Presidio Trust, San Francisco, CA.
Recent events (1)
- — Z (R) $0
1910.303 B02
- Issued
- Jun 16, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: In the following locations, surge protectors were used as permanent wiring: Building 1750- Breakroom: April 24, 2017, a surge protector with portable extension cord were used as fixed wiring for the Black and Decker Toaster Oven and the Panasonic Microwave. Building 1353- Toads and Trails: On April 24, 2017, a surge protector was used attached to the wall near the door entrance which was used to power tools and miscellaneous equipment. The Presidio Trust was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 957077, notice 3, item 1 and was affirmed as a final order on 4/24/15, with respect to a workplace located at The Presidio Trust, San Francisco, CA.
Recent events (1)
- — Z (R) $0
1910.303 G01
- Issued
- Jun 16, 2017
- Abate by
- Jun 28, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Building 1241- Warehouse/Appliance: On April 20, 2017, the electric panel load center controlling the lights and outlets was blocked by appliances, the area was used for storage preventing direct access for operators and maintenance employees. Building 1243- Warehouse/Salvage: On April 20, 2017, the electric shut off controlling the compressor and panels for lights, and Fire Control Panel was blocked by equipment including gardening tools whereby preventing direct access for operators and maintenance employees. Building 1355- Mechanic Shop: On April 24, 2017, the electric shut off controlling the compressor and panel load center controlling the lights was blocked by combustible material and other spill absorbent material preventing direct access for operators and maintenance employees. The Presidio Trust was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(g)(1)(I)(A), which was contained in OSHA inspection number 957077, Notice 1, item 1, and was affirmed as a final order on 4/24/15, with respect to a workplace located at the Presidio Trust, San Francisco, CA.
Recent events (1)
- — Z (R) $0
1910.305 B02 I
- Issued
- Jun 16, 2017
- Abate by
- Jul 13, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: Building 1353 - Roads and Trails/Tree Crew: On April 24,2017, two electric boxes were missing faceplates. The outlets were used by the employees for maintenance tasks and they were exposed to electrical hazards. The Presidio Trust was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(b)(2)(i), which was contained in OSHA inspection number 957077, notice 2, item 5 and was affirmed as a final order on 4/24/15, with respect to a workplace located at The Presidio Trust, San Francisco, CA.
Recent events (1)
- — Z (R) $0
1910.157 E03
- Issued
- Jun 16, 2017
- Abate by
- Jun 28, 2017
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): The employer shall assure that portable fire extinguishers are subjected to an annual maintenance check. Stored pressure extinguishers do not require an internal examination. The employer shall record the annual maintenance date and retain this record for one year after the last entry or the life of the shell, whichever is less. The record shall be available to the Assistant Secretary upon request. In the following locations, fire extinguishers had not been inspected annually as indicated by their expired tags: Building 1243 Warehouse /Salvage: Amerex ABC # 1801 Building 1241 Warehouse/Appliance: Amerex ABC Building 1355/Breakroom: Amerex ABC Outside Warehouse/Salvage: Toyota Forklift First Alert ABC Building 1752 Warehouse/General: Yale Electric Forklift Amerex ABC Building 1752 Warehouse/General: hallway between Plumbing and Carpentry
Recent events (1)
- — Z (O) $0
More inspections at The Presidio Trust
View The Presidio Trust's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342267788.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.