Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: J.A.M. CONSTRUCTION GUAM

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of J.A.M. CONSTRUCTION GUAM in INFUSION COFFEE & TEA NAVY BASE, SANTA RITA, GU 96915 (NAICS 236220). OSHA activity number 342723889.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch J.A.M. Construction Guam — free Get an email when a new federal OSHA severe-injury report for J.A.M. Construction Guam is published. One employer, no account, unsubscribe in one click.
Site address
INFUSION COFFEE & TEA NAVY BASE
City
SANTA RITA
State
GU
ZIP
96915
Mailing
P.O. BOX 7121 SVRB, SAIPAN, MP 96950
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
11
Ownership type
A

3 citations on file for this inspection.

1926.404 B01 II

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 19, 2018
Penalty
Initial $2,217 · Current $2,217
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection:  Main Working Area: A yellow extension cord was directly plugged in a wall outlet that was not provided with a ground fault circuit interrupter for personal protection. The extension cord was being used to power a fan and a floor light.
Recent events (1)
  • — Z (S) $2217

1926.404 F06

Serious Gravity 1 1 instance 2 exposed
Issued
Jan 19, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:   Main Working Area: The attachment plug installed on the power cord, being used to energize portable industrial Comfort Zone fan, was missing the ground pin.
Recent events (1)
  • — Z (S) $0

1926.95 A

Other-than-serious 1 instance 1 exposed
Issued
Jan 19, 2018
Penalty
Initial $0 · Current $0
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided:   Main Working Area: An employee was spreading wet concrete mix and setting floor tiles without utilizing hand protection as instructed by the cement manufacturer.
Recent events (1)
  • — Z (O) $0

View J.A.M. Construction Guam's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 342723889.