On , OSHA opened a complaint safety inspection of RGS PRODUCTS, INC. in 455 WEST 2ND STREET, WATERFORD, PA 16441 (NAICS 339999). OSHA activity number 343113056.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch RGS Products, INC. — free Get an email when a new federal OSHA severe-injury report for RGS Products, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
RGS PRODUCTS, INC.
Site address
455 WEST 2ND STREET
City
WATERFORD
State
PA
ZIP
16441
Mailing
P.O. BOX 11, WATERFORD, PA 16441
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
339999
Employees
20
Ownership type
A

6 citations on file for this inspection.

1910.303 B07 I

Serious Gravity 5 4 instances 20 exposed
Issued
Sep 25, 2018
Penalty
Initial $5,497 · Current $3,848 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:  A.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Electrical Breaker Panel Box B supplies power to equipment including, but not limited to, electrical receptacle and lighting.  Positions including, but not limited to, #1, #3, and #23 had openings that were not equipped with breakers or knockout covers.    B.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Electrical Breaker Panel Box C supplies power to equipment including, but not limited to, weld booths, a robot and an iron worker.  Positions including, but not limited to, #2, #15, #17, #37, #38, #40 and #42 had openings that were not equipped with breakers or knockout covers.    C.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Electrical Breaker Panel Box D had a 2-1/2-inch circular opening on the bottom right side of the box that was equipped with a flexible cord.  The opening in the box was not effectively closed.    D.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  The electrical disconnect that powered weld booth #4 had a 1-1/2-inch circular opening on the bottom left side of the box.  The opening in the box was not effectively closed.
Recent events (2)
  • — I (S) $3847.9
  • — Z (S) $5497

1910.303 F02

Serious Gravity 1 2 instances 20 exposed
Issued
Sep 25, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  A.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Electrical Breaker Panel Box A supplies power to equipment including, but not limited to, an air compressor, a smog hog, drill presses, and saws.  The electrical breakers with the electrical breaker panel box were not identified as to their purpose.    B.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Electrical Breaker Panel Box C supplies power to equipment including, but not limited to, weld booths, a robot and an iron worker.  The electrical breakers with the electrical breaker panel box were not identified as to their purpose.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 1 4 instances 20 exposed
Issued
Sep 25, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  A.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Items including, but not limited to, a King Air fan were stored with 3-feet of Electrical Breaker Panel Box C.    B.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Items including, but not limited to, a box of rags, a plastic crate and a plastic toolbox were stored within 3-feet of the electrical disconnect that powered the DSA Air Box.    C.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Items including, but not limited to, a Lincoln Electric welding unit, were stored within 1-foot of the electrical disconnect that powered weld booth #1.    D.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Items including, but not limited to, a Lincoln Electric welding unit, were stored within 1-foot of the electrical disconnect that powered weld booth #4.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.22 A02

Other-than-serious 1 instance 2 exposed
Issued
Sep 25, 2018
Abate by
Oct 22, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.22(a)(2): The floor of each workroom was not maintained in a clean and, to the extent feasible, in a dry condition:  A.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Accumulations of metal turnings were located on the floor from operations including, but not limited to, saw cutting.  The accumulations presented a slip and fall hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 E02

Other-than-serious 1 instance 20 exposed
Issued
Sep 25, 2018
Abate by
Oct 29, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly:  A.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Employees are provided with, and permitted to use, portable multi-purpose dry chemical fire extinguishers.  The employer did not inspect the fire extinguishers on a monthly basis.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 G02

Other-than-serious 2 instances 20 exposed
Issued
Sep 25, 2018
Abate by
Oct 29, 2018
Penalty
Initial $0 · Current $0
29 CFR 1910.157(g)(2): The educational program to familiarize employees with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting was not provided to all employees upon initial employment, and at least annually thereafter:  A.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Employees are provided with, and permitted to use, portable multi-purpose dry chemical fire extinguishers.  Employees did not have annual refresher training on the use of the portable fire extinguishers.  B.)  RGS Products, Inc., 455 West 2nd Street, Waterford, PA  16441, on or about April 25, 2018 and times prior thereto:  Employees are provided with, and permitted to use, portable multi-purpose dry chemical fire extinguishers.  Employees did not have initial training on the use of the portable fire extinguishers.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View RGS Products, INC.'s full OSHA safety record →