GILMAN, CT —
OSHA Inspection: THE GILMAN BROTHERS COMPANY
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of THE GILMAN BROTHERS COMPANY in 1 GILMAN ROAD, GILMAN, CT 06336 (NAICS 326150). OSHA activity number 343177556.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE GILMAN BROTHERS COMPANY
- Site address
- 1 GILMAN ROAD
- City
- GILMAN
- State
- CT
- ZIP
- 06336
- Mailing
- P.O. BOX 38, GILMAN, CT 06336
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 326150
- Employees
- 81
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.106 H07 I A
- Issued
- Sep 27, 2018
- Abate by
- Nov 15, 2018
- Penalty
- Initial $9,959 · Current $4,980 Reduced
General-duty citation text
29 CFR 1910.106(h)(7)(i)(a): Precautions shall be taken to prevent the ignition of flammable vapors. Sources of ignition include but are not limited to open flames; lightning; smoking; cutting and welding; hot surfaces; frictional heat; static, electrical, and mechanical sparks; spontaneous ignition, including heat-producing chemical reactions; and radiant heat: Area around Extruder: On, or about, June 19, 2018, static electricity was generated from the production process that created potential ignition sources for the iso-butane, a Category 1 flammable liquid, that was off-gassed in the production area. An ionizing unit was found to be not functional. The company had not determined all potential areas where static could be present and had not taken effective steps to control the static charge. Fires occurred in the process area on March 9, 2018 and May 29, 2018.
Recent events (2)
- — I (S) $4979.5
- — Z (S) $9959
1910.106 H07 III A
- Issued
- Sep 27, 2018
- Abate by
- Oct 31, 2019
- Penalty
- Initial $9,959 · Current $4,980 Reduced
General-duty citation text
29 CFR 1910.106(h)(7)(iii)(a): All electrical wiring and equipment shall be installed in accordance with subpart S of this part: Area around Extruder: On, or about, June 19, 2018, the following electrical equipment that was designed for use in non-classified locations was used in areas classified as Class 1, Division 2 using the classification method contained in National Fire Protection Association (NFPA) Standard 497, Recommended Practice for the Classification of Flammable Liquids, Gases or Vapors and of Hazardous (Classified) Locations for Electrical Installations of Chemical Process Areas as required under 29 CFR 1910.119(d)(3)(i)(C). On March 26, 2018, a fire occurred at the extruder outlet due to exposed heater wires: A. Area 4 (as identified on the Fuss & O"Neill 2011 classification document) Process Piping Between Pump Shed and Indoor Extruder. The following equipment was located in the designated Class 1, Division 2 area: 1. T27: 460 volt isolation transformer. 2. T28: 460 volt isolation transformer. 3. D90: Harrell Melt Pump drive. 4. T29: Federal Pacific transformer. 5. D91: Harrel Extruder drive. 6. T30: HPS step down transformer. 7. Raceway and various wiring under the extruder. B. Area 5 (as identified on the Fuss & O'Neill 2011 classification document) Indoor Extruder Area. The following equipment was located in the designated Class 1, Division 2 area: 1. Dayton fan. 2. Dayton fan. 3. T31 transformer. 4. Duplex outlet. 5. Blue/gray traverse motor. 6. Dayton fan under web. 7. Dayton fan under web. 8. Extruder thermocouple wiring. Abatement Note: Under 29 CFR 1910.119(l)(1), Management of Change must be conducted because the blowing agent has changed from iso-pentane to iso-butane. The classification recommendation may change as a result of the lower flash and boiling points of iso-butane and the recent history of fires in the process area.
Recent events (2)
- — I (S) $4979.5
- — Z (S) $9959
1910.119 L01
- Issued
- Sep 27, 2018
- Abate by
- Dec 15, 2018
- Penalty
- Initial $9,959 · Current $4,980 Reduced
General-duty citation text
29 CFR 1910.119(l)(1): The employer did not implement procedures to manage changes to process chemicals, technology, equipment, and procedures, and changes to facilities that affect a covered process: Facility: On, or about, June 19, 2018, the company had not followed Management of Change procedures when the blowing agent was changed from iso-pentane to iso-butane. Aspects of the process including, but not limited to, updating the Process Hazard Analysis, updating Process Safety Information, verifying/updating piping and relief design, verifying/updating Class 1areas, reviewing any impact on equipment on the process and verifying/updating Standard Operating Procedures were not addressed.
Recent events (2)
- — I (S) $4979.5
- — Z (S) $9959
1910.119 J04 I
- Issued
- Sep 27, 2018
- Abate by
- Nov 30, 2018
- Penalty
- Initial $35,570 · Current $17,785 Reduced
General-duty citation text
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment: Facility: On, or about, June 19, 2018, the company had not performed monthly inspections on the Draeger system to ensure that it was functioning properly and would shut down the iso-butane delivery system in the event of a leak or spill. The Gilman Brothers Company was previously cited for a violation of this Occupational Safety and Health Standard, which was contained in OSHA Inspection Number 909370, Citation Number 2, Item Number 1a and was affirmed as a Final Order on December 17, 2014, with respect to a workplace located at Gilman, Connecticut.
Recent events (2)
- — I (R) $17785
- — Z (R) $35570
More inspections at The Gilman Brothers Company
View The Gilman Brothers Company's full OSHA safety record →
More inspections in this industry (NAICS 326150)
More inspections in CT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 343177556.