Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MFA ENTERPRISES, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MFA ENTERPRISES, INC. in 302 OAK ST., EMPORIA, KS 66801 (NAICS 311119). OSHA activity number 343649083.

Watch MFA Enterprises, INC. — free Get an email when a new federal OSHA severe-injury report for MFA Enterprises, INC. is published. One employer, no account, unsubscribe in one click.
Site address
302 OAK ST.
City
EMPORIA
State
KS
ZIP
66801
Mailing
STANLEY J. THESSEN 201 RAY YOUNG DRIVE, COLUMBIA, MO 65201
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311119
Employees
18
Ownership type
A

9 citations on file for this inspection.

1910.28 B03 II

Serious Gravity 1 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $5115.00 · Current $3069.00 Reduced
29 CFR 1910.28(b)(3)(ii): Each employee was not protected from tripping into or stepping into or through any hole that was less than 4 feet (1.2 m) above a lower level by covers or guardrail systems:  a) Employees were exposed to tripping and fall hazards. Employees engaged in housekeeping and grain handling activities in the feed mill behind the South Shaker by the top floor level were exposed to tripping and fall hazards into open floor hole of 3.5 by 8.5 inches. The employer did not assure covers were readily available and installed for all floor holes. b) Employees were exposed to tripping hazards. Employees engaged in housekeeping and grain handling activities in the feed mill by Bin #11 of the top floor level were exposed to tripping hazards into an open floor hole of 3 inches in the grate. The employer did not assure covers were readily available and installed for all floor holes.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $3069
  • — Z (S) $5115

1910.36 D01

Deleted Serious Gravity 1 3 instances 7 exposed
Issued
Abate by
Penalty
Initial $5115.00 · Current $0.00 Reduced
29 CFR 1910.36(d)(1): Employees were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:   Employees were exposed to tripping, egress and fire hazards in case of emergency. Employees engaged in housekeeping and grain handling activities in the Feed Mill and Elevator at the following areas were exposed to tripping, egress and fire hazards in case of emergency in that the exit doors were locked by metal latches or blocked by plywood. The exit doors were not equipped with panic type hardware. Employees have to flip up the metal switch/latch to open the doors.  a) Feed Mill by the Top Floor exit area, locked by metal latch. b) Feed Mill by the Third Floor exit area, locked by metal latch and a full metal bar across the door. c) Elevator by the tunnel East exit area, blocked by plywood.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5115

1910.36 E02

Deleted Serious Gravity 5 3 instances 7 exposed
Issued
Abate by
Penalty
Initial $8525.00 · Current $0.00 Reduced
29 CFR 1910.36(e)(2): The door that connects any room to an exit route did not swing out in the direction of exit travel if the room is designed to be occupied by more than 50 people or if the room was a high hazard area (i.e., contains contents that are likely to burn with extreme rapidity or explode):  Employees were exposed to tripping, egress, explosion and fire hazards in case of emergency created by accumulation of grain dust. Employees engaged in housekeeping and grain handling activities in the Feed Mill and Elevator at the following areas were exposed to tripping, egress, explosion and fire hazards in case of emergency in that the employer failed to implement in compliance with industry practices for the installation of emergency egress doors that would by design open outward from the working areas to comply with NFPA, and life safety codes. The doors that open inward impedes the employees egress from a potentially hazardous environment in the event of fire or explosion.  a) Feed Mill by the Top Floor exit area. b) Feed Mill by the Third Floor exit area. c) Elevator by the tunnel East exit area.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $0
  • — Z (S) $8525

1910.303 B02

Serious Gravity 5 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $8525.00 · Current $2100.00 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   Employees were exposed to fire and electrical shock hazards. Employees engaged in tooling activities in the Work Shop of the Feed Mill were exposed to fire and electrical shock hazards in that three (3) of the 4-inch square fourplex metal electrical boxes designed for fixed installation were used to energize portable power tools such as the Jet 10" Bench Grinder and the Dewalt saw, were wired with a black flexible cord, were not listed, labeled or certified for this application, and were not securely affixed to any surface.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $8525

1910.303 F02

Serious Gravity 5 8 instances 7 exposed
Issued
Abate by
Penalty
Initial $8525.00 · Current $5800.00 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  Employees were exposed to fire and electrical shock hazards. Employees engaged in housekeeping and grain handling activities in the feed mill and elevator were exposed to fire and electrical shock hazards in that the disconnecting means, branch circuits, and circuit breaker boxes at the following locations were not properly labeled to indicate their intended use for the equipment listed below:  a) Feed Mill - Top Floor - Electrical Room - The 10Amp ON/OFF safety switch box not labeled. b) Feed Mill - Top Floor - Electrical Room - The fuse/circuit breaker box slots #1, 3, 6, and #9 not labeled. c) Feed Mill - Top Floor - East Electrical Room - The fuse/circuit breaker box #375 slots #7, and #10 not label. d) Feed Mill - Top Floor - East Electrical Room - The fuse/circuit breaker box #376 slots #7, 8, 11, 13, 29, 30, 33, 35, and #37 not labeled. e) Feed Mill - Top Floor - West Electrical Room - The Disconnect 480V ON/OFF safety switch box #388 not labeled. f) Elevator - Gallery area - The Disconnect 120/240V Disconnect switch box #409 not labeled. g) Elevator - Top Floor - The West Leg Service Disconnect Square D box not labeled. h) Elevator - Outside Roof area - The ON/OFF safety switch boxes not labeled.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $5800
  • — Z (S) $8525

1910.305 A01 I

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $8525.00 · Current $0.00 Reduced
29 CFR 1910.305(a)(1)(i): Metal raceways, cable armor, and other metal enclosures for conductors were not connected to all boxes, fittings, and cabinets to provide effective electrical continuity:  Employees were exposed to fire, explosion and electrical shock hazards. Employees engaged in housekeeping and grain handling activities in the elevator main floor (gallery area) by the man-lift were exposed to fire, explosion and electrical shock hazards in that the electrical metal conduit was not completely connected or closed to provide effective electrical continuity and to avoid accumulation of dust coming inside for the integrity of the entire system of the elevator.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $0
  • — Z (S) $8525

1910.305 B02 I

Serious Gravity 1 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $5115.00 · Current $2500.00 Reduced
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, outlet boxes and fittings were not provided with covers approved for the purpose; and each fitting in completed installations did not have a cover, faceplate, or fixture canopy:  a) Employees were exposed to fire and electrical shock hazards. Employees engaged in housekeeping and grain handling activities in the Feed Mill Main Mixing Floor inside the Control Room were exposed to fire and electrical shock hazards in that the control box for the fan to run the dust system had the top knob/button missing, thus exposing energized electrical wires. b) Employees were exposed to fire and electrical shock hazards. Employees engaged in housekeeping and grain handling activities in the Feed Mill Main Mixing Floor by the scale of the main mixing area were exposed to fire and electrical shock hazards in that the Drug Scale was not effectively closed, thus there was no protection from contacting the exposed energized electrical wires.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $5115

1910.305 G02 III

Serious Gravity 1 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $5115.00 · Current $2500.00 Reduced
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  Employees were exposed to fire and electrical shock hazards. Employees engaged in housekeeping and grain handling activities in the elevator West side tunnel by the sump pump were exposed to fire and electrical shock hazards in that the plug-in to the outlet to power the sump pump was loose at the end connection, thus exposing energized wires. There was no strain relief to ensure effective electrical continuity contact.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $5115

1910.37 B06

Other-than-serious 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and was not distinctive in color:  Employees were exposed to tripping, egress and fire hazards in case of emergency and power loss. Employees engaged in housekeeping and grain handling activities in the tunnel of the elevator by the East exit area were exposed to tripping, egress and fire hazards in case of emergency and power loss in that the exit sign was not equipped with lighting.  29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View MFA ENTERPRISES, INC.'s full OSHA safety record →