Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: BUREAU OF LAND MANAGEMENT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUREAU OF LAND MANAGEMENT in P.O. BOX 147 MILE 186.5 GLENN HWY, GLENNALLEN, AK 99588 (NAICS 924120). OSHA activity number 343960605.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bureau of Land Management for free Get an email when a new federal OSHA severe-injury report for Bureau of Land Management is published. One employer, no account, unsubscribe in one click.
Site address
P.O. BOX 147 MILE 186.5 GLENN HWY
City
GLENNALLEN
State
AK
ZIP
99588
Mailing
P.O. BOX 147 MILE 186.5 GLENN HWY, GLENNALLEN, AK 99588
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
15
Ownership type
Federal government (D)

6 citations on file for this inspection.

1910.212 B

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 26, 2019
Abate by
Jul 30, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving.  Wood shop: on or about 22 April 2019, the employer did not ensure that the Delta Drill Press, serial number R9421, Cat. 70-20 was securely mounted to prevent movement.  This condition exposed employees to a struck by hazard.
Recent events (1)
  • · Z (S) $0

1910.303 G02 II

Serious Gravity 1 2 instances 2 exposed
Issued
Jun 26, 2019
Abate by
Jul 30, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage.  Well house: on or about 22 April 2019, two instances were noted where incandescent light bulbs were not guarded:       a)  Inside the well house, and overhead incandescent light fixture measuring six feet four inches from the floor was not guarded.       b)  Outside the well house, adjacent to left side of the entry door; a wall mounted incandescent light fixture measuring six feet six inches from the ground was not guarded.  This condition exposed employees to electrical shock and electrical burn hazards.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 26, 2019
Abate by
Jul 30, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure.  Resources building, boiler room: on or about 22 April 2019, energized exterior wiring was spliced into a plug cord set and attached to a relocatable power tap. This condition exposed employees to electrical shock and electrical burn hazards.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV B

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 26, 2019
Abate by
Jul 30, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used to run through holes in walls, ceilings, or floors.  Well house; on or about 22 April 2019 and times prior thereto; an energized electrical plug and cord set was used as permanent wiring and routed through a wall opening. This condition exposed employees to electrical shock and electrical burn hazards.
Recent events (1)
  • · Z (S) $0

1910.334 A02 I

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 26, 2019
Abate by
Jul 30, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket).  Wood shop: on or about 22 April 2019, an energized 25-foot heavy duty yellow extension cord had damaged to the receptacle plug.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • · Z (S) $0

1910.1200 F05

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 26, 2019
Abate by
Jul 30, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(f)(5): The employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged, or marked with the identity and appropriate hazard warnings regarding the chemicals contained therein:  Old Hazmat Storage area: on or about 22 April 2019, an unmarked 55-gallon steel drum barrel containing an unknown chemical substance was not marked identifying the product and the hazard warnings associated with it. This condition exposed employees to chemical burns, poisoning, and skin dermatitis.
Recent events (1)
  • · Z (S) $0

View Bureau of Land Management's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 343960605.