Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NORKOL CONVERTING CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of NORKOL CONVERTING CORPORATION in 1731 TREBLE DR., HUMBLE, TX 77338 (NAICS 322299). OSHA activity number 344073796.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Norkol Converting Corporation — free Get an email when a new federal OSHA severe-injury report for Norkol Converting Corporation is published. One employer, no account, unsubscribe in one click.
Site address
1731 TREBLE DR.
City
HUMBLE
State
TX
ZIP
77338
Mailing
1731 TREBLE DR., HUMBLE, TX 77338
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322299
Employees
31
Ownership type
A

8 citations on file for this inspection.

1910.303 F02

Serious Gravity 5 3 instances 31 exposed
Issued
Aug 8, 2019
Abate by
Aug 16, 2019
Penalty
Initial $8,525 · Current $4,263 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:      1.  On or about June 12, 2019 at the Square D breaker box which was not labeled to identify each breaker.  2.  On or about June 12, 2019 at the Cutler Hammer breaker box which was not labeled to identify each breaker.   3.  On or about June 12, 2019 at the Siemens breaker box which was not labeled to identify each breaker.
Recent events (2)
  • — I (S) $4262.5
  • — Z (S) $8525

1910.303 G02 I

Serious Gravity 5 3 instances 31 exposed
Issued
Aug 8, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):    1.  On or about June 12, 2019 at the L2 extruder machine where employees were exposed to electrical hazards when a 480 volt fuse compartment did not have its covers shut. 2.  On or about June 12, 2019 below the breaker box located next to the exit door employees were exposed to electrical hazards when a metal conduit body cover was not completely closed. 3.  On or about June 12, 2019 at the L6 extruder machine where employees were exposed to electrical hazards when a 480 volt breaker fuse compartment did not have its cover shut.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B01

Serious Gravity 5 1 instance 31 exposed
Issued
Aug 8, 2019
Abate by
Aug 16, 2019
Penalty
Initial $8,525 · Current $4,263 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:    On or about June 12, 2019 at the facility where employees were operating an extruder machine that had a missing handle to a GE 240 volt knife switch.
Recent events (2)
  • — I (S) $4262.5
  • — Z (S) $8525

1910.305 B01 II

Serious Gravity 5 20 instances 31 exposed
Issued
Aug 8, 2019
Abate by
Aug 15, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:    1.     On or about June 12, 2019 between the L2 and L6 extruder machines employees were exposed to electrical hazards when using an electrical breaker box that had an unused opening. 2.     On or about June 12, 2019 at the L4 extruder machine, employees were exposed to electrical hazards from an unused opening at the roll press control panel. 3.     On or about June 12, 2019 at the L4 extruder machine, employees were exposed to electrical hazards from seven unused openings on the control panel. 4.     On or about June 12, 2019 at the L4 extruder machine, employees were exposed to electrical hazards from an unused opening at the stairwell breaker box. 5.     On or about June 12, 2019 at the L6 extruder machine ,employees were exposed to electrical hazards from five unused openings at the roll press control panel. 6.     On or about June 12, 2019 at the L6 extruder machine, employees were exposed to electrical hazards from two unused openings at the control panel. 7.     On or about June 12, 2019 at the L6 extruder winder, employees were exposed to electrical hazards from two unused openings.  8.     On or about June 12, 2019 at the L6 extruder machine,  employees were exposed to electrical hazards from an electrical box that had an unused opening.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 5 1 instance 31 exposed
Issued
Aug 8, 2019
Penalty
Initial $8,525 · Current $4,263 Reduced
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:    On or about June 12, 2019 at the facility, employees were exposed to an electrical hazard from an extension cord that was through the wall and metal stud of the building.
Recent events (2)
  • — I (S) $4262.5
  • — Z (S) $8525

1910.1200 E01

Other-than-serious 1 instance 31 exposed
Issued
Aug 8, 2019
Abate by
Aug 22, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met:   On or about June 12, 2019 at the facility, employees were using chemicals such as, but not limited to, high heat plastic resin without a written hazard communication program in place.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 G01

Other-than-serious 1 instance 31 exposed
Issued
Aug 8, 2019
Abate by
Aug 22, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(g)(1): Employers did not have a safety data sheet in the workplace for each hazardous chemical which they use:    On or about June 12, 2019 employees did not have safety data sheets for the high heat plastic resin that was in use.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 H01

Other-than-serious 1 instance 31 exposed
Issued
Aug 8, 2019
Abate by
Aug 22, 2019
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area:     On or about June 12, 2019 at the facility, employees were using chemicals such as, but not limited to, high heat plastic resin, and had not been trained on the hazards of the chemicals in their work area.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Norkol Converting Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344073796.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.